Plan Review Details - Permit 10120017
Plan Review Stops For Permit 10120017
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-12 Cont ID  
Sent By jwitmer Date 2011-04-12 Time 09:52 Rev Time 0.77
Received By jwitmer Date 2011-04-12 Time 09:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-20 Cont ID  
Sent By jwitmer Date 2010-12-20 Time 13:00 Rev Time 2.22
Received By jwitmer Date 2010-12-20 Time 13:00 Sent To  
Notes
2010-12-20 13:17:27BUILDING PLAN REVIEW
 PERMIT:10120017
 ADD: 900 N FLORIDA MANGO/ AKA1000 OKEECHOBEE RD
 CONT: NELCO DIVERSIFIED INC/ NELCO CONSTRUCTION
 TEL: (813)477-0574
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COVERSHEET:
  
 1A) PLEASE REVIEW TYPE OF OCCUPANCY, THE PLANS INDICATE
 A BUSSINESS OCCUPANCY WHERE AS APPROXIMATELY ONLY 50%
 OF THE FLOOR AREA IS CONSIDERED A BUSINESS OCCUPANCY.
 THE 3RD AND 4TH FLOORS ARE INDICATED TO BE STORAGE
 PLEASE INDICATE IF THE STORAGE OCCUPANCY IS TO BE A S-1
 OR S-2 OCCUPANCY. PLEASE NOTE THAT TABLE 503 LIMITS THE
 HEIGHT OF A TYPE IIB BUILDING TO THREE STORIES. THIS
 BUILDING TO BE CONSIDERED A MIXED USE OCCUPANCY, FBC-B
 508.3.
  
 1B) PLEASE REVIEW THE OCCUPANT LOADS FOR BUSINESS 2ND
 FLOOR @ 100 SQ FT & STORAGE OCCUPANCY @ 300 SQ FT THIS
 WILL EFFECT THE PROPOSED OCCUPANT LOADS FBC-B TABLE
 1004.1.1.
  
 1C) COVER SHEET MEANS OF EGRESS ANALYSIS IS INDICATED
 AS FBC-B SECTION 1015.1, PLEASE ALSO CONSIDER FBC-B
 TABLE 1019.2
 BUILDINGS WITH ONE EXIT PLEASE REVIEW STORAGE 1 STORY &
 100 FT TRAVEL DISTANCE.
  
 2) SHEET A-1:
  
 2A) THIS IS A FOUR STORY BUILDING AND VERTICAL EXIT
 WHICH REQUIRES A 2 HOUR RATED WALL AND 1 1/2 HOUR
 OPENING PROTECTIVE. NOTE 19 DOES NOT PROVIDE ANY RATING
 FOR THIS DOOR PLEASE REVIEW FBC-B TABLE 715.4, AND
 PROVIDE FIRE RATING APPROVALS FOR DOORS.
  
 2B) THE SECOND FLOOR BEING A BUSINESS OCCUPANCY AND AN
 OCCUPANT LOAD GREATER THAN 5 (500 SQ FT) PLEASE PROVIDE
 COMPLIANCE WITH FBC-B 11-4.1.6(1)(K)(III) VERTICAL
 ACCESSIBILITY.
  
 3) PRODUCT APPROVALS:
  
 3A) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3B) FLEMING DOOR FL3341-R2 IT APPEARS THAT THIS DOOR
 DOES NOT MEET THE PRESSURES FOR THE DOOR LEADING ONTO
 THE ROOF, NOR THE EXIT DOOR FROM THE VERTICAL EXIT
 STAIR LOCATED IN A END ZONE.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-28 Cont ID  
Sent By rlecky Date 2011-03-28 Time 09:13 Rev Time 0.00
Received By rlecky Date 2011-03-28 Time 09:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-04 Cont ID  
Sent By rlecky Date 2011-01-04 Time 12:05 Rev Time 0.00
Received By rlecky Date 2011-01-04 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-05-26 Cont ID  
Sent By wjolin Date 2011-05-26 Time 15:43 Rev Time 0.00
Received By wjolin Date 2011-05-26 Time 15:27 Sent To  
Notes
2011-05-26 15:42:59900 NORTH FLORIDA MANGO ROAD
 PERMIT #10120017
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 STAIRWAY STORAGE ACCESS DOORS ARE NOT PERMITTED TO OPEN
 INTO THE STAIR ENCLOSURE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-03-31 Cont ID  
Sent By wjolin Date 2011-03-31 Time 12:25 Rev Time 0.00
Received By wjolin Date 2011-03-31 Time 12:14 Sent To  
Notes
2011-03-31 12:25:04900 NORTH FLORIDA MANGO ROAD
 PERMIT #10120017
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EXISTING BUSINESS OCCUPANCIES REQUIRE A MINIMUM OF TWO
 SEPARATE EXITS PER SECTION 39.2.4 NFPA 101 FLORIDA 2007
 EDITION.
  
 A FIRE ALARM SYSTEM SHALL BE PROVIDED IN EXISTING
 BUSINESS OCCUPANCIES TWO OR MORE STORIES IN HEIGHT
 ABOVE THE LEVEL OF EXIT DISCHARGE PER SECTION 39.3.4
 NFPA 101 FLORIDA 2007 EDITION.
  
 STAIRWAY STORAGE ACCESS DOORS ARE NOT PERMITTED TO OPEN
 INTO THE STAIR ENCLOSURE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-06 Cont ID  
Sent By mcarsill Date 2010-12-06 Time 12:57 Rev Time 0.00
Received By mcarsill Date 2010-12-06 Time 12:46 Sent To  
Notes
2010-12-06 12:57:161000 OLD OKEECHOBEE ROAD
 PERMIT NUMBER 10120017
 COMMERCIAL RENOVATION
 PRIOR TO BEING USED BY THE FLORIDA DEPARTMENT OF
 TRANSPORTATION IT WAS USED BY THE CITY OF WEST PALM
 BEACH FIRE RESCUE DEPARTMENT TO TRAIN ITS PROFESSIONAL
 FIREFIGHTERS AND PARAMEDICS
  
  
 1. BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT LEAST
 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. ALL STAIRWELL DOORS ARE TO BE AT LEAST 90 MINUTE
 FIRE RATED DOORS EQUIPPED WITH SELF-CLOSING DEVICES.
  
 4. PORTABLE FIRE EXTINGUISHERS ARE REQUIRED WHEREBY
 TRAVEL DISTANCE DOES NOT EXCEED 75 FEET OF TRAVEL
 DISTANCE.
  
 5. THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT IS LOCATED AT 401 CLEMATIS STREET NOT
 200-2ND STREET
  
 6. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 7. DEBRIS SHALL BE REMOVED FROM THE BUILDING DAILY.
  
 8. SUITABLE ACCESS IS TO BE PROVIDED FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-12 Cont ID  
Sent By jwitmer Date 2011-04-12 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2011-03-24 Time 11:51 Sent To  
Notes
2011-03-24 11:54:02C--8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-04 Cont ID  
Sent By rlecky Date 2011-01-04 Time 12:14 Rev Time 0.00
Received By rlecky Date 2010-12-02 Time 10:45 Sent To  
Notes
2010-12-02 10:46:00C--8

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-05-18 Cont ID  
Sent By hmoser Date 2011-05-18 Time 13:40 Rev Time 0.00
Received By hmoser Date 2011-05-11 Time 09:07 Sent To  
Notes
2011-05-11 09:07:50C6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-03-28 Cont ID  
Sent By hmoser Date 2011-03-28 Time 13:22 Rev Time 0.00
Received By hmoser Date 2011-03-28 Time 12:57 Sent To  
Notes
2011-03-28 13:29:13PLANS DENIED
 NOTES 22 AND 26 PAGE A-2 SAY YOU ARE ADDING A NEW 1.5
 TON MINI SPLIT AIR CONDITIONING SYSTEM.
 PLEASE PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 PLEASE SHOW THE LOCATION OF THE CONDENSER ON THE PLANS.
 PLEASE PROVIDE ENERGY CALCULATIONS WITH THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-12-28 Cont ID  
Sent By hmoser Date 2010-12-28 Time 12:52 Rev Time 0.00
Received By hmoser Date 2010-12-28 Time 12:51 Sent To  
Notes
2010-12-28 13:03:08PLAN DENIED
 PLEASE PROVIDE AIRCONDITIONING EQUIPMENT SCHEDULE ON
 THE PLANS .
 PLEASE PROVIDE THE LOCATION OF THE CONDENSOR ON THE
 PLANS, REFER TO SECTION 306.5 2007 FBC (M) . EQUIPMENT
 AND APPLIANCES ON ROOFS OR ELEVATED STRUCTURES.
 PLEASE PROVIDE ENERGY CALCULATIONS WITH PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-04-01 Cont ID  
Sent By lwagner Date 2011-04-01 Time 14:56 Rev Time 0.00
Received By lwagner Date 2011-04-01 Time 14:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-20 Cont ID  
Sent By lwagner Date 2010-12-20 Time 10:11 Rev Time 0.00
Received By lwagner Date 2010-12-20 Time 07:59 Sent To  
Notes
2010-12-20 10:10:50FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. A RESTROOM WILL BE REQUIRED ON THE 3RD FLOOR TO BE
 WITHIN ONE STORY LEVEL.
 PLUMBING 403.4.1 LOCATION OF TOILET FACILITIES IN
 OCCUPANCIES OTHER THAN COVERED MALLS. IN OCCUPANCIES
 OTHER THAN COVERED MALLS, THE REQUIRED PUBLIC AND
 EMPLOYEE TOILET FACILITIES SHALL BE LOCATED NOT MORE
 THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED TO BE
 PROVIDED WITH TOILET FACILITIES, AND THE PATH OF TRAVEL
 TO SUCH FACILITIES SHALL NOT EXCEED A DISTANCE OF 500
 FEET (152 M).
  
 2. DRINKING FOUNTIANS ARE REQUIRED IN BUSINESS
 OCCUPANIES.
 TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-05-23 Cont ID  
Sent By astelly Date 2011-05-23 Time 11:36 Rev Time 0.00
Received By astelly Date 2011-05-23 Time 11:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-04-04 Cont ID  
Sent By astelly Date 2011-04-04 Time 14:28 Rev Time 0.00
Received By astelly Date 2011-04-04 Time 14:28 Sent To  
Notes
2011-04-04 14:31:03AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A LANDSCAPE PLAN AND PLANT SCHEDULE
 SHOWING THE NUMBER AND LOCATION OF POTTED LANDSCAPE
 UNITS AND THE TYPES AND QUANTITIES OF PLANTS PROPOSED
 FOR USE.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By astelly Date 2010-12-17 Time 14:05 Rev Time 0.00
Received By astelly Date 2010-12-17 Time 14:05 Sent To  
Notes
2010-12-17 14:08:31AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PER SEC. 94-444(B), THE STORAGE RACK FOR THE AC SYSTEM
 MUST BE SCREENED. SCREENING SHALL BE CONSTRUCTED OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.