Plan Review Details - Permit 10110699
Plan Review Stops For Permit 10110699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By jwitmer Date 2011-01-24 Time 16:06 Rev Time 0.20
Received By jwitmer Date 2011-01-24 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-02 Cont ID  
Sent By jwitmer Date 2010-12-02 Time 13:02 Rev Time 0.55
Received By jwitmer Date 2010-12-02 Time 13:01 Sent To  
Notes
2010-12-02 13:13:40BUILDING PLAN REVIEW
 PERMIT: 10110699
 ADD: 1300 ALLENDALE RD
 CONT: INSULPRO, INC.
 TEL: (813)486-8164
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE INFORMATION AS TO IF THE BUILDING IS
 FULLY SPRINKLERED? IT WILL DETERMINE WHICH OF THE CODE
 SECTIONS WHICH THIS PROJECT WOULD BE REVIEWED. FOR THIS
 REVIEW IT WILL BE CONSIDERED FIRE SPRINKLERED.
  
 2) THE FOLLOWING INFORMATION WILL REQUIRED TO COMPLETE
 THE REVIEW FOR THE CONSTRUCTION OF A WALK IN FREEZER
 AND COMPLIANCE WITH SECTION 2007 W/2009 SUPPLEMENTS
 FBC-B2603.4.1.2.:
 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM PLASTIC
 INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES (254 MM)
 IN COOLER AND FREEZER WALLS SHALL:
  
 2.1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
  
 2.2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600??F AND 800??F (316??C AND 427??C),
 RESPECTIVELY.
  
 2.3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT. ARE THE PANELS TO BE CONSTRUCTED FROM STEEL
 OR ALUMINUM? PLEASE MARK THE PLANS AS SUCH.
  
 2.4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-22 Cont ID  
Sent By rlecky Date 2010-12-22 Time 14:37 Rev Time 0.00
Received By rlecky Date 2010-12-22 Time 12:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By wjolin Date 2011-01-20 Time 13:09 Rev Time 0.00
Received By wjolin Date 2011-01-20 Time 13:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-10 Cont ID  
Sent By wjolin Date 2010-12-10 Time 10:14 Rev Time 0.00
Received By wjolin Date 2010-12-10 Time 10:13 Sent To  
Notes
2010-12-10 10:14:331300 ALLENDALE ROAD
 PERMIT #10110699
  
 REFER TO BUILDING REVIEW COMMENTS REGARDING AUTOMATIC
 FIRE SPRINKLERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-24 Cont ID  
Sent By jwitmer Date 2011-01-24 Time 16:06 Rev Time 0.00
Received By jwitmer Date 2011-01-06 Time 15:34 Sent To  
Notes
2011-01-06 15:34:39C18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By lmartine Date 2010-12-22 Time 16:10 Rev Time 0.00
Received By lmartine Date 2010-11-30 Time 15:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By lmartine Date 2010-12-22 Time 15:57 Rev Time 0.00
Received By lmartine Date 2010-12-22 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By jwitmer Date 2011-01-24 Time 16:06 Rev Time 0.20
Received By jwitmer Date 2011-01-24 Time 16:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-12-03 Cont ID  
Sent By hmoser Date 2010-12-03 Time 09:08 Rev Time 0.00
Received By hmoser Date 2010-12-03 Time 07:53 Sent To  
Notes
2010-12-03 09:22:29PLAN DENIED
 PLEASE PROVIDE A ENGINEER DETAIL ON THE CONDENSER TIE
 DOWN TO THE CONDENSOR STAND . IF THE STANDS ARE NOT
 EXISTING PROVIDE A ENGINEER DETAIL ON THE STAND TO
 ROOF.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 2 Status P Date 2011-01-13 Cont ID  
Sent By astelly Date 2011-01-13 Time 16:35 Rev Time 0.00
Received By astelly Date 2011-01-13 Time 16:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By astelly Date 2010-12-17 Time 14:58 Rev Time 0.00
Received By astelly Date 2010-12-17 Time 14:58 Sent To  
Notes
2010-12-17 15:29:22AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SITE PLAN THAT SHOWS THE LOCATION OF
 THE PROPOSED PROJECT. ALSO PROVIDE A FLOOR PLAN SHOWING
 THE LOCATION OF THE WORK IN RELATION TO THE REST OF THE
 FACILITY.
  
 IN ADDITION, PLEASE PROVIDE ELEVATIONS OF THE PROPOSED
 PROJECT IN CONTEXT WITH THE EXISTING STRUCTURE.
  