Plan Review Details - Permit 10110685
Plan Review Stops For Permit 10110685
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-14 Cont ID  
Sent By jwitmer Date 2011-03-14 Time 09:54 Rev Time 0.77
Received By jwitmer Date 2011-03-14 Time 09:54 Sent To  
Notes
2011-03-14 10:08:47BUILDING PLAN REVIEW
 PERMIT:10110685
 ADD: 410 EVERNIA ST
 CONT:BESSENROTH BUILDERS INC/ CBC1255316
 TEL: (561)324-4871
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING PROVISO:
 THE CURRENT CONTRACTOR BESSENROTH BUILDERS/ CBC1255316
 WILL ONLY BE LIMITED TO CUTTING THE FIRST FLOOR SLAB,
 NO SAW CUTTING OR REMOVAL OF MEZZANINE SLAB WITH A CBC
 LICENSE, OTHERWISE IT WOULD BE WORKING BEYOND THEIR
 SCOPE OF LICENSURE. FL S 489.105(B) BUILDING
 CONTRACTOR.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-03-14 Cont ID  
Sent By jwitmer Date 2011-01-28 Time 10:18 Rev Time 0.77
Received By jwitmer Date 2011-03-14 Time 09:54 Sent To  
Notes
2011-01-28 10:41:46BUILDING PLAN REVIEW
 PERMIT:10110685
 ADD: 410 EVERNIA ST
 CONT:BESSENROTH BUILDERS INC/ CBC1255316
 TEL: (561)324-4871
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THERE ARE NO ARCHITECTURAL PLANS SUBMITTED
 INDICATING SLAB CUT AND REPAIR FOR PLUMBING WASTE PIPES
 NOR HOW VENT LINES TO BE INSTALLED.
  
 2) THE PLANS FAIL TO PROVIDE VERTICAL ACCESSIBILITY TO
 THE MEZZANINE LEVEL, THIS BUILDING WAS ORIGINALLY
 DESIGNED AS RESIDENTIAL NOT REQUIRING
 VERTICAL ACCESSIBILITY. 11-4.1.6(1)(K)(III).
  
 3) THE CURERNT CONTRACTOR BESSENROTH BUILDERS/
 CBC1255316 WILL BE WORKING BEYOND THEIR SCOPE OF
 LICENSURE. FL S 489.105(B)
 BUILDING CONTRACTOR??? MEANS A CONTRACTOR WHOSE
 SERVICES ARE LIMITED TO CONSTRUCTION OF COMMERCIAL
 BUILDINGS AND SINGLE-DWELLING OR MULTIPLE-DWELLING
 RESIDENTIAL BUILDINGS, WHICH COMMERCIAL OR RESIDENTIAL
 BUILDINGS DO NOT EXCEED THREE STORIES IN HEIGHT, AND
 ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING,
 REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE
 SERVICES "DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING." WE BELIEVE THAT CUTTING THE FIRST FLOOR SLAB
 AND CORE BORING THE MEZZANINE FLOOR SLAB WOULD BE
 AFFECTING STRUCTURAL MEMBERS.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-13 Cont ID  
Sent By jwitmer Date 2010-12-13 Time 14:58 Rev Time 0.56
Received By jwitmer Date 2010-12-13 Time 14:57 Sent To  
Notes
2010-12-13 15:03:14BUILDING PLAN REVIEW
 PERMIT:10110685
 ADD: 410 EVERNIA ST
 CONT: DELCO CONSTRUCTION
 TEL: (561)436-4106
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THERE ARE NO ARCHITECTURAL PLANS SUBMITTED
 INDICATING SLAB CUT AND REPAIR FOR PLUMBING WASTE PIPES
 NOR HOW VENT LINES TO BE INSTALLED.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-15 Cont ID  
Sent By rlecky Date 2011-03-15 Time 12:27 Rev Time 0.00
Received By rlecky Date 2011-03-15 Time 12:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-06 Cont ID  
Sent By jleahy Date 2010-12-06 Time 10:18 Rev Time 0.00
Received By jleahy Date 2010-12-06 Time 10:18 Sent To  
Notes
2010-12-06 10:19:40SEE NOTES ON PLAN FOR EMERGENCY CIRCUITS , LIGHTING
 SPACE CONTROL, AND RESIDENTIAL LOAD CALCULATION
  
 JAKE LEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By wjolin Date 2011-02-03 Time 12:22 Rev Time 0.00
Received By wjolin Date 2011-02-03 Time 11:59 Sent To  
Notes
2011-02-03 12:22:34410 EVERNIA STREET, SUITE #117
 PERMIT #10110685
 REVIEW COMMENTS - FIRE
  
 NOTE: DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 PROVIDE SEPARATE PLANS AND PERMITS FOR ANY FIRE ALARM
 AND FIRE SPRINKLER INSTALLATION OR MODIFICATIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 16:53 Rev Time 0.00
Received By wjolin Date 2010-12-16 Time 15:33 Sent To  
Notes
2010-12-16 16:53:30410 EVERNIA STREET SUITE#117
 PERMIT #10110685
 REVIEW COMMENTS - FIRE
  
 PERMIT APPLICATION SHOWS SUITE NUMBER 117; SUBMITTED
 PLANS REFER TO LOFT NUMBER 5. PLEASE CLARIFY THE
 CORRECT SUITE OR LOFT ASSOCIATED WITH THIS PROJECT.
  
 IS THIS A CHANGE OF USE OR OCCUPANCY FOR THIS SUITE?
 FLOOR PLANS DO NOT LABEL THE NAMES OR USE OF EACH ROOM.
 NO ARCHITECTURAL PLANS PROVIDED.
  
 THE EXISTING RESIDENTIAL FIRE SPRINKLERS NEED TO BE
 REPLACED WITH COMMERCIAL STYLE FIRE SPRINKLERS.
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 WORK.
  
 PROVIDE COMMERCIALLY TAGGED/CERTIFIED PORTABLE FIRE
 EXTINGUISHERS (2A:10BC MIIMUM).
  
 EXITING THROUGH A KITCHEN IS NOT PERMITTED BY THE
 FLORIDA FIRE PREVENTION CODE (NFPA 101 - LIFE SAFETY
 CODE).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-03-18 Cont ID  
Sent By lmartine Date 2011-03-18 Time 09:41 Rev Time 0.00
Received By lmartine Date 2011-03-09 Time 12:59 Sent To  
Notes
2011-03-09 13:00:02B-8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-19 Cont ID  
Sent By lmartine Date 2011-01-19 Time 09:31 Rev Time 0.00
Received By lmartine Date 2011-01-19 Time 09:31 Sent To  
Notes
2011-01-19 09:40:13B--10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By shill Date 2010-12-22 Time 17:19 Rev Time 0.00
Received By shill Date 2010-11-30 Time 11:12 Sent To  
Notes
2010-12-22 16:39:50ON MISC 3
2010-12-09 14:45:44B24
  
2010-11-30 11:12:56INCOMING SENT TO PLUMBING <$5,000.00 JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-03-18 Cont ID  
Sent By lmartine Date 2011-03-18 Time 09:38 Rev Time 0.00
Received By lmartine Date 2011-03-18 Time 09:38 Sent To  
Notes
2011-03-18 09:41:20SEE #10110685 FOR HAROLD'S APPROVAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-02-15 Cont ID  
Sent By hmoser Date 2011-02-15 Time 11:21 Rev Time 0.00
Received By hmoser Date 2011-02-15 Time 11:21 Sent To  
Notes
2011-02-15 11:26:02NO MECHANICAL PLANS SUBMITTED . NEED PLANS FOR NAIL
 STATIONS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-03-14 Cont ID  
Sent By lwagner Date 2011-03-14 Time 10:39 Rev Time 0.00
Received By lwagner Date 2011-03-14 Time 10:14 Sent To  
Notes
2011-03-14 10:19:27REVISION REQUIRED
  
 1. THIS AREA OF PLUMBING HAS A MIXTURE OF WASTE STACK
 VENTING AND SOVENT PIPING.
 SOVENT IS AN ENGINEERED SYSTEM. CONNECTIONS DOWNSTREAM
 OF THE DEAERATOR VENT MAY BE MADE WITHOUT
 RE-ENGINEERING THE SYSTEM. CONNECTING INTO THE BUILDING
 DRAIN OR BUILDING DRAIN BRANCHES WOULD ALSO BE
 PERMISSIBLE.
  
 2. IF STUDOR VENTS ARE USED, THEN A RELIEF VENT WILL BE
 REQUIRED.
 917.3.2
2011-03-14 10:18:26REVISION REQUIRED
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-01-31 Cont ID  
Sent By lwagner Date 2011-01-31 Time 10:54 Rev Time 0.00
Received By lwagner Date 2011-01-31 Time 10:15 Sent To  
Notes
2011-01-31 10:39:10FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. STUDOR VENTS ARE SHOWN ON PLAN. THE DRAINAGE SYSTEM
 FOR THIS BUILDING IS OVER 4 BRANCH INTERVALS ABOVE.
 917.3.2 A RELIEF VENT WOULD BE REQUIRED.
  
 2. THE RISER DIAGRAM DOES NOT SHOW WHERE THE SANITARY
 PIPEING IS BEING CONNECTED. THIS AREA OF PLUMBING HAS A
 MIXTURE OF WASTE STACK VENTING AND SOVENT PIPING.
 SOVENT IS AN ENGINEERED SYSTEM. CONNECTIONS DOWNSTREAM
 OF THE DEAERATOR VENT MAY BE MADE WITHOUT
 RE-ENGINEERING THE SYSTEM. CONNECTING INTO THE BUILDING
 DRAIN OR BUILDING DRAIN BRANCHES WOULD ALSO BE
 PERMISSIBLE.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-06 Cont ID  
Sent By lwagner Date 2010-12-06 Time 08:19 Rev Time 0.00
Received By lwagner Date 2010-12-06 Time 07:36 Sent To  
Notes
2010-12-06 08:19:15PBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. PLUMBING 403.1 MINIMUM PLUMBING FIXTURES: 1 DRINKING
 FOUNTAIN WILL BE REQUIRED.
  
 2. RESTROOM IS REQUIRED TO MEET FBC BUILDING 2007
 CHAPTER 11 - FLORIDA ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION.
  
 3. BUILDING CHAPTER 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS- 13. PLUMBING RISER DIAGRAM
 REQUIRED( SANITARY AND DOMESTIC WATER).
  
 4. PLUMBING FLAT DRAWING SHOWS DRAINAGE FOR 2 SHAMPOO
 CHAIRS WITH NO VENT. PLUMBING CHAPTER 901.2.1 VENTING
 REQUIRED. EVERY TRAP AND TRAPPED FIXTURE SHALL BE
 VENTED IN ACCORDANCE WITH ONE OF THE VENTING METHODS
 SPECIFIED IN THIS CHAPTER.
  
 NOTE: NO ARCHITECTURAL PLANS WERE SUBMITTED WITH THIS
 SET
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By aaponte Date 2010-12-22 Time 16:39 Rev Time 0.00
Received By aaponte Date 2010-12-22 Time 10:20 Sent To  
Notes
2010-12-22 10:20:54PUT IN ZONING BOX TO MAKE ROOM ON BUILD OUT SPREAD
 SHEET