Plan Review Details - Permit 10110644
Plan Review Stops For Permit 10110644
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2011-02-11 Cont ID  
Sent By shill Date 2011-02-11 Time 11:47 Rev Time 0.00
Received By shill Date 2011-02-11 Time 11:47 Sent To  
Notes
2011-02-11 14:52:10****PROVISOS****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
  
 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS
 DOOR, EXTERIOR DOORS, FAC9N-3. SUBMIT PRODUCT APPROVALS
 AS A REVISION PRIOR TO INSTALLATION.
  
 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP
 DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN
 /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP
 REQUIREMENTS IS REQUIRED. PRIOR TO FINAL INSPECTION,
 PROVIDE A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE. THIS MUST BE A SIGNED, SEALED DATED
 ORIGINAL. PLEASE SUBMIT FOR REVIEW PRIOR TO FINAL
 INSPECTION.
  
 3. PRIOR TO FINAL INSPECTION, EITHER SUBMIT ENGINEERING
 FOR THE ENGINEERED FLOOD OPENINGS OR SHOW COMPLIANCE
 WITH NFIP REQUIREMENTS.
  
 4. RESOLVE ALL EXPIRED PERMIT FOR THIS ADDRESS PRIOR TO
 FINAL INSPECTION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2011-02-09 Cont ID  
Sent By shill Date 2011-02-09 Time 12:31 Rev Time 0.00
Received By shill Date 2011-02-09 Time 12:31 Sent To  
Notes
2011-02-09 12:32:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS
 DOOR, EXTERIOR DOORS, FAC9B72. (PROVISO ITEM)
  
 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP
 DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN
 /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP
 REQUIREMENTS IS REQUIRED. BASED ON THE ELEVATION
 CERTIFICATE PROVIDED, FLOOD OPENINGS, ITEM A8 ON
 ELEVATION CERTIFICATE, DO NOT COMPLY WITH NFIP
 REQUIREMENTS. SEE THE FEMA WEBSITE FOR MORE INFORMATION
 REGARDING REQUIREMENTS AND COMPLIANCE:
  
 HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD
 S/SI.SHTM
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579
  
 ALSO SEE THE WALKWAY BETWEEN THE GARAGE AND MAIN HOUSE.
 THIS APPEARS TO BE HABITABLE SPACE (SHOWS WINDOWS,
 ROOF, FLOOR). SHOW THAT THIS AREA MEETS THE NFIP
 REQUIREMENTS (MINIMUM 7'6").
  
 FOURTH REVIEW, SEE FEMA TECHNICAL BULLETIN 11,
 CRAWLSPACE CONSTRUCTION. BOTTOM OF FLOOR JOISTS APPEARS
 TO BE BELOW 7'6" IN PORTIONS OF THE HOUSE. PLEASE
 REVISE PLAN AND/OR ELEVATION CERTIFICATE/SURVEY TO SHOW
 COMPLIANCE WITH NFIP REQUIREMENTS.
  
 SEE FEMA DOCUMENT REGARDING FLOOD OPENINGS. AN
 EVALUATION AND STATEMENT BY A DESIGN PROFESSIONAL IS
 REQUIRED. SEE P. 24
  
 3. THE FOLLOWING COMMENTS PERTAIN TO THE ELEVATION
 CERTIFICATE PROVIDED. PLEASE ALSO SEE ELEVATION
 CERTIFICATE INSTRUCTIONS,
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1383.
  
 A. SEE COMMENT #2 REGARDING FLOOD OPENINGS, A8 ON
 ELEVATION CERTIFICATE. PRIOR TO FINAL INSPECTION, A
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WHICH
 SHOWS COMPLIANCE WITH NFIP REQUIREMENTS IS REQUIRED.
  
 B. PROVISO, FINISHED CONSTRUCTION ELEVATION CERTIFICATE
 WILL BE REQUIRED PRIOR TO FINAL INSPECTION.
  
 C. ADDRESSED.
  
 D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE
 ELEVATION CERTIFICATE INSTRUCTIONS (NEED SIGNATURE ON
 ELEVATION CERTIFICATE).
  
 E. N/A (SEE OTHER COMMENTS REGARDING FLOOR ELEVATION).
  
 4. PROVISO - SEPARATE PERMIT MECHANICAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-02-03 Cont ID  
Sent By shill Date 2011-02-02 Time 07:56 Rev Time 0.00
Received By shill Date 2011-02-02 Time 07:55 Sent To  
Notes
2011-02-02 08:04:08PERMIT NOT TO BE ISSUED PER JORGE ALVA, P.E. UNTIL HE
 HAS HAD AN OPPORTUNITY TO REVIEW PLANS, COMMENTS, AND
 POSSIBLE PROVISO ITEMS
  
  
 ****PROVISOS****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
  
 1. OWNER, CONTRACTOR, AND ARCHITECT UNDERSTAND AND
 ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S
 NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW
 CONSTRUCTION (PROJECT IS SUBSTANTIAL IMPROVEMENT).
  
 2. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS
 DOOR, EXTERIOR DOORS, FAC9B72. SUBMIT AS A REVISION
 PRIOR TO INSTALLATION.
  
 2. FLOOD OPENINGS IN COMPLIANCE WITH NFIP REQUIREMENTS
 REQUIRED. SUBMIT A DETAIL AND A REVISED ELEVATION
 CERTIFICATE SHOWING COMPLIANCE.
  
 HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD
 S/SI.SHTM
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579
  
 3. INCLUDE WALKWAY BETWEEN GARAGE AND HOUSE ELEVATION
 ON THE SURVEY, MINIMUM 7'6" REQUIRED.
  
 4. SUBMIT A "CONSTRUCTION DRAWINGS" ELEVATION
 CERTIFICATE REVISED AS FOLLOWS:
  
 A. SEE A8 ON ELEVATION CERTIFICATE. PRIOR TO FINAL
 INSPECTION, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WHICH SHOWS COMPLIANCE WITH NFIP
 REQUIREMENTS IS REQUIRED. PROVIDE A DETAIL TO SHOW HOW
 COMPLIANCE IS PROPOSED.
  
 B. THE ELEVATION CERTIFICATE PROVIDED AT PERMIT
 APPLICATION IS FOR "FINISHED CONSTRUCTION." AS NEW
 CONSTRUCTION IS PROPOSED (NEW MECHANICAL EQUIPMENT AND
 SLAB, SUBSTANTIAL IMPROVEMENT), THREE ELEVATION
 CERTIFICATES WILL BE REQUIRED FOR THE RENOVATION;
 CONSTRUCTION DRAWINGS, BUILDING UNDER CONSTRUCTION, AND
 FINISHED CONSTRUCTION. PLEASE PROVIDE A REVISED
 ELEVATION CERTIFICATE, "CONSTRUCTION DRAWINGS."
  
 C. SEE INSTRUCTIONS, A5, WHEN LATITUDE AND LONGITUDE
 ARE PROVIDED BY A SURVEYOR, PROVIDE METHOD USED IN
 COMMENTS.
  
 D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE
 ELEVATION CERTIFICATE INSTRUCTIONS.
  
 E. SEE C2 A, 6.7 FEET IS STATED AS "TOP OF BOTTOM FLOOR
 (INCLUDING BASEMENT, CRAWLSPACE, OR ENCLOSURE FLOOR)."
 I WAS UNABLE TO LOCATE THIS ELEVATION ON THE SURVEY.
 THIS ELEVATION CONFLICTS WITH ARCHITECT'S DETAIL FOR
 MECHANICAL DUCTWORK. IF NECESSARY, USE THE COMMENTS
 SECTION TO CLARIFY AND TO SHOW COMPLIANCE WITH NFIP
 REQUIREMENTS. OWNER AND ARCHITECT ACKNOWLEDGE
 RESPONSIBILITY FOR FLOOR (INCLUDING BOTTOM OF JOISTS)
 AND MECHANICAL EQUIPMENT (INCLUDING DUCTWORK) TO BE
 ABOVE 7'6". A REVISED ELEVATION CERTIFICATE TO BE
 SUBMITTED.
  
 4. INCORPORATE THE DETAIL FOR DUCTWORK INTO THE PLAN.
 NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. PROPOSED
 ELEVATION IS TO BE INCLUDED ON THE ELEVATION
 CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B).
 SEE ALSO
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS. MECHANICAL PLAN TO BE SUBMITTED
 EITHER WITH THE MECHANICAL APPLICATION OR AS A
 REVISION.
  
 5. UNDER STAIR STORAGE IS SHOWN. SHOW COMPLIANCE WITH
 FBC R311.2.2., UNDER STAIR PROTECTION (UNDERSIDE OF
 STAIR/CEILING OF STORAGE AREA). REVISE DETAIL.
  
 6. PLEASE RESOLVE EXPIRED PERMITS ON THIS ADDRESS PRIOR
 TO JOB COMPLETION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-01-27 Cont ID  
Sent By shill Date 2011-01-27 Time 14:05 Rev Time 0.00
Received By shill Date 2011-01-26 Time 14:10 Sent To  
Notes
2011-01-27 14:06:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS
 DOOR, EXTERIOR DOORS, FAC9B72.
  
 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP
 DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN
 /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP
 REQUIREMENTS IS REQUIRED. BASED ON THE ELEVATION
 CERTIFICATE PROVIDED, FLOOD OPENINGS, ITEM A8 ON
 ELEVATION CERTIFICATE, DO NOT COMPLY WITH NFIP
 REQUIREMENTS. SEE THE FEMA WEBSITE FOR MORE INFORMATION
 REGARDING REQUIREMENTS AND COMPLIANCE:
  
 HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD
 S/SI.SHTM
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579
  
 ALSO SEE THE WALKWAY BETWEEN THE GARAGE AND MAIN HOUSE.
 THIS APPEARS TO BE HABITABLE SPACE (SHOWS WINDOWS,
 ROOF, FLOOR). SHOW THAT THIS AREA MEETS THE NFIP
 REQUIREMENTS (MINIMUM 7'6").
  
 3. THE FOLLOWING COMMENTS PERTAIN TO THE ELEVATION
 CERTIFICATE PROVIDED. PLEASE ALSO SEE ELEVATION
 CERTIFICATE INSTRUCTIONS,
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1383.
  
 A. SEE COMMENT #2 REGARDING FLOOD OPENINGS, A8 ON
 ELEVATION CERTIFICATE. PRIOR TO FINAL INSPECTION, A
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WHICH
 SHOWS COMPLIANCE WITH NFIP REQUIREMENTS IS REQUIRED.
  
 B. THE ELEVATION CERTIFICATE PROVIDED IS FOR "FINISHED
 CONSTRUCTION." AS NEW CONSTRUCTION IS PROPOSED (NEW
 MECHANICAL EQUIPMENT AND SLAB, SUBSTANTIAL
 IMPROVEMENT), THREE ELEVATION CERTIFICATES WILL BE
 REQUIRED FOR THE RENOVATION; CONSTRUCTION DRAWINGS,
 BUILDING UNDER CONSTRUCTION, AND FINISHED CONSTRUCTION.
 PLEASE PROVIDE A REVISED ELEVATION CERTIFICATE,
 "CONSTRUCTION DRAWINGS."
  
 C. SEE INSTRUCTIONS, A5, WHEN LATITUDE AND LONGITUDE
 ARE PROVIDED BY A SURVEYOR, PROVIDE METHOD USED IN
 COMMENTS.
  
 D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE
 ELEVATION CERTIFICATE INSTRUCTIONS.
  
 E. SEE C2 A, 6.7 FEET IS STATED AS "TOP OF BOTTOM FLOOR
 (INCLUDING BASEMENT, CRAWLSPACE, OR ENCLOSURE FLOOR)."
 I WAS UNABLE TO LOCATE THIS ELEVATION ON THE SURVEY.
 THIS ELEVATION CONFLICTS WITH ARCHITECT'S DETAIL FOR
 MECHANICAL DUCTWORK. IF NECESSARY, USE THE COMMENTS
 SECTION TO CLARIFY AND TO SHOW COMPLIANCE WITH NFIP
 REQUIREMENTS.
  
 4. INCORPORATE THE DETAIL FOR DUCTWORK INTO THE PLAN.
 NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. PROPOSED
 ELEVATION IS TO BE INCLUDED ON THE ELEVATION
 CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B).
 SEE ALSO
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 5. UNDER STAIR STORAGE IS SHOWN. SHOW COMPLIANCE WITH
 FBC R311.2.2., UNDER STAIR PROTECTION (UNDERSIDE OF
 STAIR/CEILING OF STORAGE AREA).
  
 6. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE
 INFORMATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-07 Cont ID  
Sent By shill Date 2010-12-07 Time 10:51 Rev Time 0.00
Received By shill Date 2010-12-06 Time 16:36 Sent To  
Notes
2010-12-07 11:33:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PRODUCT APPROVALS REQUIRED FOR COMPONENTS & CLADDING
 (DOORS, WINDOWS, MULLIONS), FAC9B72. PRODUCT APPROVALS
 ARE TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL.
  
 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP
 DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN
 /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH ALL REQUIREMENTS
 TO BE SHOWN ON THE PLAN. SEE ALSO CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B). NOTE THAT THIS
 STRUCTURE IS LOCATED IN THE A5 FLOOD ZONE, 7'6" MINIMUM
 ELEVATION REQUIRED. PLEASE REFER TO FEMA WEBSITE FOR
 FURTHER GUIDANCE. PLEASE FEEL FREE TO CONTACT ME FOR
 FURTHER ASSISTANCE.
  
 3. PROVIDE AN ELEVATION CERTIFICATE; HTTP://WWW.FEMA.GO
 V/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORDS/SI.SHTM.
  
 4. NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN.
 PROPOSED ELEVATION IS TO BE INCLUDED ON THE ELEVATION
 CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B).
 SEE ALSO
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 5. REVISE SITE PLAN TO SHOW LOCATION OF MECHANICAL
 EQUIPMENT RELATIVE TO THE PROPERTY LINE, FBC106.
  
 6. DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING
 401.4.
  
 7. DECLARE WIND DESIGN CRITERIA FBC 1603.1.4, FBC R301.
  
 8. IMPACT PROTECTION REQUIRED FOR GLAZING, FBC R
 301.2.1.2. IF SHUTTERS ARE PROPOSED, THE FOLLOWING
 INFORMATION WILL BE REQUIRED:
  
 A. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_F
 OR_INSTALLATION.PDF
  
 B. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 C. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 9. IT APPEARS THAT UNDER STAIR STORAGE IS SHOWN. SHOW
 COMPLIANCE WITH FBC R311.2.2., UNDER STAIR PROTECTION.
  
 10. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE
 INFORMATION.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-27 Cont ID  
Sent By rlecky Date 2010-12-27 Time 11:27 Rev Time 0.00
Received By rlecky Date 2010-12-22 Time 14:36 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-12-02 Cont ID  
Sent By fmittner Date 2010-12-02 Time 15:19 Rev Time 0.00
Received By fmittner Date 2010-12-02 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-02-10 Cont ID  
Sent By jgomez Date 2011-02-10 Time 10:50 Rev Time 0.00
Received By jgomez Date 2011-02-10 Time 10:49 Sent To B
Notes
2011-02-10 10:50:58NEW SOFFITS SUBMITTALS PACKAGE AND ORIGINAL PERMIT
 PACKAGE SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-02-08 Cont ID  
Sent By rlecky Date 2011-02-08 Time 10:16 Rev Time 0.00
Received By rlecky Date 2011-02-08 Time 10:16 Sent To  
Notes
2011-02-08 10:17:06GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-28 Cont ID  
Sent By shill Date 2011-01-28 Time 14:33 Rev Time 0.00
Received By shill Date 2011-01-14 Time 17:22 Sent To  
Notes
2011-01-14 17:22:35R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-02 Cont ID  
Sent By shill Date 2011-01-03 Time 17:21 Rev Time 0.00
Received By shill Date 2010-11-29 Time 15:12 Sent To  
Notes
2010-11-29 15:13:00*************EXPEDITED*************
 R--14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-02-02 Cont ID  
Sent By shill Date 2011-02-02 Time 08:04 Rev Time 0.00
Received By shill Date 2011-02-02 Time 08:04 Sent To  
Notes
2011-02-02 08:05:24MU 2011-1827
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-12-30 Cont ID  
Sent By shill Date 2010-12-30 Time 09:57 Rev Time 0.00
Received By shill Date 2010-12-30 Time 09:57 Sent To  
Notes
2010-12-30 09:59:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PLAN TO INCLUDE:
  
 EXISTING SQUARE FOOT AREA UNDER AIR
 PROPOSED NEW SQUARE FOOT AREA UNDER AIR
  
 2. IMPACT FEE ASSESSMENT REQUIRED. PLEASE CONTACT
 561-233-5025 FOR MORE INFORMATION.
  

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By rkussner Date 2010-12-22 Time 09:18 Rev Time 0.00
Received By rkussner Date 2010-12-22 Time 09:18 Sent To  
Notes
2010-12-22 09:19:16***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #10120337 FOR LANDSCAPE
 PLAN.---RAK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2011-02-03 Cont ID  
Sent By shill Date 2011-02-03 Time 13:29 Rev Time 0.00
Received By shill Date 2011-02-03 Time 13:29 Sent To  
Notes
2011-02-03 13:30:21REMOVE MECHANICAL PLAN PRIOR TO ISSUANCE
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-02-02 Cont ID  
Sent By hmoser Date 2011-01-31 Time 07:22 Rev Time 0.00
Received By hmoser Date 2011-01-31 Time 07:22 Sent To  
Notes
2011-02-02 07:48:37****PROVISOS****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OWNER, CONTRACTOR AND ARCHITECT UNDERSTAND AND
 ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S
 NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW
 CONSTRUCTION (PROJECT IS A SUBSTANTIAL IMPROVEMENT).
  
 2. FBC R M1401.5, SUBMIT A "CONSTRUCTION DRAWINGS"
 ELEVATION CERTIFICATE WHICH INCLUDES THE FOLLOWING
 INFORMATION:
  
 PROPOSED ELEVATION FOR MECHANICAL EQUIPMENT, MINIMUM
 7.5'
  
 CLARIFICATION REGARDING LOWEST FLOOR (CAN BE INCLUDED
 IN "COMMENTS" SECTION) IN ORDER TO SHOW COMPLIANCE WITH
 REQUIREMENT THAT DUCTWORK IS INSTALLED ABOVE 7.5'; 6.7
 IS SHOWN ON C2A BUT THAT ELEVATION IS NOT ON THE SURVEY
 (7.63 SHOWN AS CRAWLSPACE ELEVATION).
  
  
 3. REVISE PLAN TO INCORPORATE THE NEW MECHANICAL
 DUCTWORK INSTALLATION DETAIL (DUCTWORK INSTALLED ABOVE
 7'6").
  
 4. FBC R 1411.3.1, PER ARCHITECT, DRAIN FROM AUXILIARY
 DRAIN PAN TO BE REDIRECTED OR REMOVED, REVISE DETAIL
 "SUSPENDED AIR HANDLERS," SHEET M1.
  
 5. PER ARCHITECT, DUCTWORK UNDER HOUSE WILL BE LINED,
 FBC R 1601.1.2, 1601.3.10. INCORPORATE REQUIREMENT INTO
 PLAN.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-01-28 Cont ID  
Sent By shill Date 2011-01-28 Time 10:56 Rev Time 0.00
Received By shill Date 2011-01-28 Time 10:56 Sent To  
Notes
2011-01-28 11:07:08****CORRECTIONS****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH
 HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT
 IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE
 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED
 ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED
 ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION
 CERTIFICATE.
  
 2ND REVIEW, ELEVATION CERTIFICATE DOES NOT CORRELATE
 WITH PLANS AND ARCHITECT'S INFORMATION. SEE BUILDING
 COMMENTS. ELEVATION CERTIFICATE AT CONSTRUCTION
 DOCUMENT PHASE IS TO INCLUDE PROPOSED ELEVATION FOR NEW
 EQUIPMENT AND FOR DUCTWORK. DETAIL SHOWING THAT
 DUCTWORK TO BE INSTALLED ABOVE 7.5' TO BE INCORPORATED
 INTO THE PLAN.
  
 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 2ND REVIEW, SEE COMMENT #1.
  
 3-5. ADDRESSED.
  
 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO
 RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE
 ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT.
 HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT
 STATEMENT.
  
 2ND REVIEW, NO ANCHORS SPECIFIED FOR BOTTOM OF STAND.
  
 7. ADDRESSED.
  
 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY
 DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES
 NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE.
  
 2ND REVIEW, FLOAT SWITCH IS NOTED. HOWEVER, THE DRAIN
 LINE FROM THE AUXILIAIRY DRAIN PAN TO CONDENSATE DRAIN
 LINE IS NOT PERMITTED. PLEASE REMOVE OR REROUTE AS PER
 FBC R1411.3.
  
 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2,
 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE.
  
 2ND REVIEW, DUCT IS NOTED AS INSULATED. PLEASE INCLUDE
 REQUIREMENT THAT DUCT IS TO BE LINED (INSIDE OF DUCT)
 FOR UNDER HOUSE DUCTWORK.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-02-02 Cont ID  
Sent By hmoser Date 2011-01-03 Time 10:14 Rev Time 0.00
Received By hmoser Date 2011-02-02 Time 07:54 Sent To  
Notes
2011-01-03 09:59:24****CORRECTIONS****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH
 HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT
 IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE
 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED
 ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED
 ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION
 CERTIFICATE.
  
 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 3. FBC 106, THE SITE PLAN HAS A HANDWRITTEN NOTE WHICH
 STATES NOT TO EXCEED 2FT SETBACK. THE BUILDING IS SHOWN
 AT 4.8FT FROM PROPERTY LINE, M1 SHOWS 1FT BETWEEN UNIT
 AND BUILDING AND 34IN DEPTH FOR THE UNIT. PLEASE
 CONFIRM UNIT SIZE AND LOCATION AND DISTANCE TO PROPERTY
 LINE.
  
 5. M1, HVAC GENERAL NOTE 6, R4 DUCTS DO NOT COMPLY WITH
 FBC R TABLE 1110.AB.2.1. THIS APPEARS TO BE A GENERAL
 NOTE NOT APPLICABLE TO DETAILS SPECIFIC TO THIS JOB;
 EITHER REMOVE OR COMPLY.
  
 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO
 RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE
 ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT.
 HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT
 STATEMENT.
  
 7. AHU 3 GROUND FLOOR DOOR ENCROACHES ON THE UNIT
 SPACE, DOES NOT APPEAR THAT THE DOOR SHOWN ON M2 CAN
 CLOSE, AND WHAT APPEARS TO BE THE RETURN AIR REGISTER
 IS OUTSIDE THE DOOR. ACCESS TO THE UNIT IS NOT CLEAR.
 ARCHITECTURAL SHEETS ARE NOT CONSISTENT WITH M2 SHEETS
 REGARDING AHU 3 DOOR.
  
 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY
 DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES
 NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE.
  
 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2,
 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-01-28 Cont ID  
Sent By rmcdouga Date 2011-01-28 Time 11:51 Rev Time 0.00
Received By rmcdouga Date 2011-01-28 Time 09:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By rmcdouga Date 2010-12-17 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2010-12-17 Time 07:38 Sent To  
Notes
2010-12-17 10:48:47DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF SANITARY ISOMETRIC DRAWINGS FOR
 THE PROJECT AS REQUIRED BY FBC 106.3.5.4. SPECIFY THE
 PIPE SIZES, CLEAN OUTS, TRAPS, FIXTURE TYPES, ETC.
  
 2) THE PLUMBING PLAN ON PL-1 SHOWS THE 4" BUILDING
 DRAIN TYING INTO A NEW 3" BUILDING DRAIN AT THE PANTRY
 AREA AND CONTINUING TO AN EXISTING 3" BUILDING SEWER.
 FBC R 3005.1.7 DOES NOT ALLOW THE SIZE OF THE DRAINAGE
 PIPING TO BE REDUCED IN SIZE IN THE DIRECTION OF THE
 FLOW. PLEASE CORRECT.
  
 3) THE PLUMBING FIXTURE SCHEDULE ON PL-1 CONTAINS
 NUMEROUS ERRORS. THE TRAP SIZES ARE INCORRECT. SEE FBCR
 TABLE P3201.7. THE SHOWERS ARE MARKED P3, THE SINKS ARE
 MARKED P4 ON THE PLANS AND THE SCHEDULE DOES NOT
 CORRESPOND. PLEASE CORRECT.
  
 4) THE TOTAL FIXTURE UNIT COUNT IS NOT CORRECT. SEE
 FBCR TABLE P3004.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-01-19 Cont ID  
Sent By fmittner Date 2011-01-19 Time 16:55 Rev Time 0.00
Received By fmittner Date 2011-01-19 Time 16:55 Sent To  
Notes
2011-01-19 16:55:34LANDSCAPE PERMIT APPLIED FOR UNDER SEPERATE PERMIT

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-02 Cont ID  
Sent By fmittner Date 2010-12-02 Time 15:01 Rev Time 0.00
Received By fmittner Date 2010-12-02 Time 15:01 Sent To  
Notes
2010-12-02 15:11:50PLANNING AND ZONING: ***** FAILED****
  
 1. THE VALUE OF THE CONSTRUCTION ($198,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($132,070) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN SHALL BE INCLUDED WITH THE PERMIT
 RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO ARTICLE
 XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A
 SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL
 BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO
 CONFORMITY.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES AS WELL AS PAD AND
 EQUIPTMENT SIZES. PURSUANT TO SECTION 94-305(B)(4) OF
 THE ZLDR: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1457
 E-MAIL: [email protected]
  