Plan Review Details - Permit 10110644
| Plan Review Stops For Permit 10110644 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2011-02-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-02-11 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-02-11 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2011-02-11 14:52:10 | ****PROVISOS**** | | | ****REVISION REQUIRED**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | | | | 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS | | | DOOR, EXTERIOR DOORS, FAC9N-3. SUBMIT PRODUCT APPROVALS | | | AS A REVISION PRIOR TO INSTALLATION. | | | | | | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP | | | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN | | | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP | | | REQUIREMENTS IS REQUIRED. PRIOR TO FINAL INSPECTION, | | | PROVIDE A "FINISHED CONSTRUCTION" ELEVATION | | | CERTIFICATE. THIS MUST BE A SIGNED, SEALED DATED | | | ORIGINAL. PLEASE SUBMIT FOR REVIEW PRIOR TO FINAL | | | INSPECTION. | | | | | | 3. PRIOR TO FINAL INSPECTION, EITHER SUBMIT ENGINEERING | | | FOR THE ENGINEERED FLOOD OPENINGS OR SHOW COMPLIANCE | | | WITH NFIP REQUIREMENTS. | | | | | | 4. RESOLVE ALL EXPIRED PERMIT FOR THIS ADDRESS PRIOR TO | | | FINAL INSPECTION. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2011-02-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-02-09 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-02-09 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2011-02-09 12:32:30 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | COMMENTS FROM PREVIOUS LISTS: | | | | | | 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS | | | DOOR, EXTERIOR DOORS, FAC9B72. (PROVISO ITEM) | | | | | | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP | | | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN | | | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP | | | REQUIREMENTS IS REQUIRED. BASED ON THE ELEVATION | | | CERTIFICATE PROVIDED, FLOOD OPENINGS, ITEM A8 ON | | | ELEVATION CERTIFICATE, DO NOT COMPLY WITH NFIP | | | REQUIREMENTS. SEE THE FEMA WEBSITE FOR MORE INFORMATION | | | REGARDING REQUIREMENTS AND COMPLIANCE: | | | | | | HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD | | | S/SI.SHTM | | | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579 | | | | | | ALSO SEE THE WALKWAY BETWEEN THE GARAGE AND MAIN HOUSE. | | | THIS APPEARS TO BE HABITABLE SPACE (SHOWS WINDOWS, | | | ROOF, FLOOR). SHOW THAT THIS AREA MEETS THE NFIP | | | REQUIREMENTS (MINIMUM 7'6"). | | | | | | FOURTH REVIEW, SEE FEMA TECHNICAL BULLETIN 11, | | | CRAWLSPACE CONSTRUCTION. BOTTOM OF FLOOR JOISTS APPEARS | | | TO BE BELOW 7'6" IN PORTIONS OF THE HOUSE. PLEASE | | | REVISE PLAN AND/OR ELEVATION CERTIFICATE/SURVEY TO SHOW | | | COMPLIANCE WITH NFIP REQUIREMENTS. | | | | | | SEE FEMA DOCUMENT REGARDING FLOOD OPENINGS. AN | | | EVALUATION AND STATEMENT BY A DESIGN PROFESSIONAL IS | | | REQUIRED. SEE P. 24 | | | | | | 3. THE FOLLOWING COMMENTS PERTAIN TO THE ELEVATION | | | CERTIFICATE PROVIDED. PLEASE ALSO SEE ELEVATION | | | CERTIFICATE INSTRUCTIONS, | | | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1383. | | | | | | A. SEE COMMENT #2 REGARDING FLOOD OPENINGS, A8 ON | | | ELEVATION CERTIFICATE. PRIOR TO FINAL INSPECTION, A | | | "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WHICH | | | SHOWS COMPLIANCE WITH NFIP REQUIREMENTS IS REQUIRED. | | | | | | B. PROVISO, FINISHED CONSTRUCTION ELEVATION CERTIFICATE | | | WILL BE REQUIRED PRIOR TO FINAL INSPECTION. | | | | | | C. ADDRESSED. | | | | | | D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE | | | ELEVATION CERTIFICATE INSTRUCTIONS (NEED SIGNATURE ON | | | ELEVATION CERTIFICATE). | | | | | | E. N/A (SEE OTHER COMMENTS REGARDING FLOOR ELEVATION). | | | | | | 4. PROVISO - SEPARATE PERMIT MECHANICAL. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2011-02-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-02-02 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-02-02 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2011-02-02 08:04:08 | PERMIT NOT TO BE ISSUED PER JORGE ALVA, P.E. UNTIL HE | | | HAS HAD AN OPPORTUNITY TO REVIEW PLANS, COMMENTS, AND | | | POSSIBLE PROVISO ITEMS | | | | | | | | | ****PROVISOS**** | | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | | | | 1. OWNER, CONTRACTOR, AND ARCHITECT UNDERSTAND AND | | | ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S | | | NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW | | | CONSTRUCTION (PROJECT IS SUBSTANTIAL IMPROVEMENT). | | | | | | 2. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS | | | DOOR, EXTERIOR DOORS, FAC9B72. SUBMIT AS A REVISION | | | PRIOR TO INSTALLATION. | | | | | | 2. FLOOD OPENINGS IN COMPLIANCE WITH NFIP REQUIREMENTS | | | REQUIRED. SUBMIT A DETAIL AND A REVISED ELEVATION | | | CERTIFICATE SHOWING COMPLIANCE. | | | | | | HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD | | | S/SI.SHTM | | | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579 | | | | | | 3. INCLUDE WALKWAY BETWEEN GARAGE AND HOUSE ELEVATION | | | ON THE SURVEY, MINIMUM 7'6" REQUIRED. | | | | | | 4. SUBMIT A "CONSTRUCTION DRAWINGS" ELEVATION | | | CERTIFICATE REVISED AS FOLLOWS: | | | | | | A. SEE A8 ON ELEVATION CERTIFICATE. PRIOR TO FINAL | | | INSPECTION, A "FINISHED CONSTRUCTION" ELEVATION | | | CERTIFICATE WHICH SHOWS COMPLIANCE WITH NFIP | | | REQUIREMENTS IS REQUIRED. PROVIDE A DETAIL TO SHOW HOW | | | COMPLIANCE IS PROPOSED. | | | | | | B. THE ELEVATION CERTIFICATE PROVIDED AT PERMIT | | | APPLICATION IS FOR "FINISHED CONSTRUCTION." AS NEW | | | CONSTRUCTION IS PROPOSED (NEW MECHANICAL EQUIPMENT AND | | | SLAB, SUBSTANTIAL IMPROVEMENT), THREE ELEVATION | | | CERTIFICATES WILL BE REQUIRED FOR THE RENOVATION; | | | CONSTRUCTION DRAWINGS, BUILDING UNDER CONSTRUCTION, AND | | | FINISHED CONSTRUCTION. PLEASE PROVIDE A REVISED | | | ELEVATION CERTIFICATE, "CONSTRUCTION DRAWINGS." | | | | | | C. SEE INSTRUCTIONS, A5, WHEN LATITUDE AND LONGITUDE | | | ARE PROVIDED BY A SURVEYOR, PROVIDE METHOD USED IN | | | COMMENTS. | | | | | | D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE | | | ELEVATION CERTIFICATE INSTRUCTIONS. | | | | | | E. SEE C2 A, 6.7 FEET IS STATED AS "TOP OF BOTTOM FLOOR | | | (INCLUDING BASEMENT, CRAWLSPACE, OR ENCLOSURE FLOOR)." | | | I WAS UNABLE TO LOCATE THIS ELEVATION ON THE SURVEY. | | | THIS ELEVATION CONFLICTS WITH ARCHITECT'S DETAIL FOR | | | MECHANICAL DUCTWORK. IF NECESSARY, USE THE COMMENTS | | | SECTION TO CLARIFY AND TO SHOW COMPLIANCE WITH NFIP | | | REQUIREMENTS. OWNER AND ARCHITECT ACKNOWLEDGE | | | RESPONSIBILITY FOR FLOOR (INCLUDING BOTTOM OF JOISTS) | | | AND MECHANICAL EQUIPMENT (INCLUDING DUCTWORK) TO BE | | | ABOVE 7'6". A REVISED ELEVATION CERTIFICATE TO BE | | | SUBMITTED. | | | | | | 4. INCORPORATE THE DETAIL FOR DUCTWORK INTO THE PLAN. | | | NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. PROPOSED | | | ELEVATION IS TO BE INCLUDED ON THE ELEVATION | | | CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B). | | | SEE ALSO | | | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR | | | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL | | | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH | | | NFIP REQUIREMENTS. MECHANICAL PLAN TO BE SUBMITTED | | | EITHER WITH THE MECHANICAL APPLICATION OR AS A | | | REVISION. | | | | | | 5. UNDER STAIR STORAGE IS SHOWN. SHOW COMPLIANCE WITH | | | FBC R311.2.2., UNDER STAIR PROTECTION (UNDERSIDE OF | | | STAIR/CEILING OF STORAGE AREA). REVISE DETAIL. | | | | | | 6. PLEASE RESOLVE EXPIRED PERMITS ON THIS ADDRESS PRIOR | | | TO JOB COMPLETION. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2011-01-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-01-27 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-01-26 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2011-01-27 14:06:02 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS | | | DOOR, EXTERIOR DOORS, FAC9B72. | | | | | | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP | | | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN | | | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP | | | REQUIREMENTS IS REQUIRED. BASED ON THE ELEVATION | | | CERTIFICATE PROVIDED, FLOOD OPENINGS, ITEM A8 ON | | | ELEVATION CERTIFICATE, DO NOT COMPLY WITH NFIP | | | REQUIREMENTS. SEE THE FEMA WEBSITE FOR MORE INFORMATION | | | REGARDING REQUIREMENTS AND COMPLIANCE: | | | | | | HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD | | | S/SI.SHTM | | | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579 | | | | | | ALSO SEE THE WALKWAY BETWEEN THE GARAGE AND MAIN HOUSE. | | | THIS APPEARS TO BE HABITABLE SPACE (SHOWS WINDOWS, | | | ROOF, FLOOR). SHOW THAT THIS AREA MEETS THE NFIP | | | REQUIREMENTS (MINIMUM 7'6"). | | | | | | 3. THE FOLLOWING COMMENTS PERTAIN TO THE ELEVATION | | | CERTIFICATE PROVIDED. PLEASE ALSO SEE ELEVATION | | | CERTIFICATE INSTRUCTIONS, | | | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1383. | | | | | | A. SEE COMMENT #2 REGARDING FLOOD OPENINGS, A8 ON | | | ELEVATION CERTIFICATE. PRIOR TO FINAL INSPECTION, A | | | "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WHICH | | | SHOWS COMPLIANCE WITH NFIP REQUIREMENTS IS REQUIRED. | | | | | | B. THE ELEVATION CERTIFICATE PROVIDED IS FOR "FINISHED | | | CONSTRUCTION." AS NEW CONSTRUCTION IS PROPOSED (NEW | | | MECHANICAL EQUIPMENT AND SLAB, SUBSTANTIAL | | | IMPROVEMENT), THREE ELEVATION CERTIFICATES WILL BE | | | REQUIRED FOR THE RENOVATION; CONSTRUCTION DRAWINGS, | | | BUILDING UNDER CONSTRUCTION, AND FINISHED CONSTRUCTION. | | | PLEASE PROVIDE A REVISED ELEVATION CERTIFICATE, | | | "CONSTRUCTION DRAWINGS." | | | | | | C. SEE INSTRUCTIONS, A5, WHEN LATITUDE AND LONGITUDE | | | ARE PROVIDED BY A SURVEYOR, PROVIDE METHOD USED IN | | | COMMENTS. | | | | | | D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE | | | ELEVATION CERTIFICATE INSTRUCTIONS. | | | | | | E. SEE C2 A, 6.7 FEET IS STATED AS "TOP OF BOTTOM FLOOR | | | (INCLUDING BASEMENT, CRAWLSPACE, OR ENCLOSURE FLOOR)." | | | I WAS UNABLE TO LOCATE THIS ELEVATION ON THE SURVEY. | | | THIS ELEVATION CONFLICTS WITH ARCHITECT'S DETAIL FOR | | | MECHANICAL DUCTWORK. IF NECESSARY, USE THE COMMENTS | | | SECTION TO CLARIFY AND TO SHOW COMPLIANCE WITH NFIP | | | REQUIREMENTS. | | | | | | 4. INCORPORATE THE DETAIL FOR DUCTWORK INTO THE PLAN. | | | NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. PROPOSED | | | ELEVATION IS TO BE INCLUDED ON THE ELEVATION | | | CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B). | | | SEE ALSO | | | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR | | | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL | | | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH | | | NFIP REQUIREMENTS. | | | | | | 5. UNDER STAIR STORAGE IS SHOWN. SHOW COMPLIANCE WITH | | | FBC R311.2.2., UNDER STAIR PROTECTION (UNDERSIDE OF | | | STAIR/CEILING OF STORAGE AREA). | | | | | | 6. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-12-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-12-07 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-12-06 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2010-12-07 11:33:50 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PRODUCT APPROVALS REQUIRED FOR COMPONENTS & CLADDING | | | (DOORS, WINDOWS, MULLIONS), FAC9B72. PRODUCT APPROVALS | | | ARE TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL. | | | | | | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP | | | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN | | | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH ALL REQUIREMENTS | | | TO BE SHOWN ON THE PLAN. SEE ALSO CITY OF WEST PALM | | | BEACH MUNICIPAL CODE 94-546(B). NOTE THAT THIS | | | STRUCTURE IS LOCATED IN THE A5 FLOOD ZONE, 7'6" MINIMUM | | | ELEVATION REQUIRED. PLEASE REFER TO FEMA WEBSITE FOR | | | FURTHER GUIDANCE. PLEASE FEEL FREE TO CONTACT ME FOR | | | FURTHER ASSISTANCE. | | | | | | 3. PROVIDE AN ELEVATION CERTIFICATE; HTTP://WWW.FEMA.GO | | | V/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORDS/SI.SHTM. | | | | | | 4. NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. | | | PROPOSED ELEVATION IS TO BE INCLUDED ON THE ELEVATION | | | CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B). | | | SEE ALSO | | | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR | | | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL | | | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH | | | NFIP REQUIREMENTS. | | | | | | 5. REVISE SITE PLAN TO SHOW LOCATION OF MECHANICAL | | | EQUIPMENT RELATIVE TO THE PROPERTY LINE, FBC106. | | | | | | 6. DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING | | | 401.4. | | | | | | 7. DECLARE WIND DESIGN CRITERIA FBC 1603.1.4, FBC R301. | | | | | | 8. IMPACT PROTECTION REQUIRED FOR GLAZING, FBC R | | | 301.2.1.2. IF SHUTTERS ARE PROPOSED, THE FOLLOWING | | | INFORMATION WILL BE REQUIRED: | | | | | | A. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_F | | | OR_INSTALLATION.PDF | | | | | | B. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | | INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609, | | | FBC*106. | | | | | | C. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. | | | | | | 9. IT APPEARS THAT UNDER STAIR STORAGE IS SHOWN. SHOW | | | COMPLIANCE WITH FBC R311.2.2., UNDER STAIR PROTECTION. | | | | | | 10. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-12-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2010-12-27 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2010-12-22 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-12-02 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2010-12-02 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2010-12-02 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2011-02-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-02-10 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-02-10 |
Time |
10:49 |
Sent To |
B |
|
| Notes |
| 2011-02-10 10:50:58 | NEW SOFFITS SUBMITTALS PACKAGE AND ORIGINAL PERMIT | | | PACKAGE SENT TO S. HILL'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2011-02-08 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-08 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-08 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2011-02-08 10:17:06 | GAVE TO SAMANTHA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-01-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-01-28 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-01-14 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-02-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-01-03 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-11-29 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2010-11-29 15:13:00 | *************EXPEDITED************* | | | R--14 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2011-02-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-02-02 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-02-02 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2011-02-02 08:05:24 | MU 2011-1827 | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2010-12-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-12-30 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-12-30 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2010-12-30 09:59:04 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISE PLAN TO INCLUDE: | | | | | | EXISTING SQUARE FOOT AREA UNDER AIR | | | PROPOSED NEW SQUARE FOOT AREA UNDER AIR | | | | | | 2. IMPACT FEE ASSESSMENT REQUIRED. PLEASE CONTACT | | | 561-233-5025 FOR MORE INFORMATION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
N |
Date |
2010-12-22 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-12-22 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-12-22 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2010-12-22 09:19:16 | ***LANDSCAPE REVIEW NOT REQUIRED*** | | | | | | PLEASE REFER TO PERMIT #10120337 FOR LANDSCAPE | | | PLAN.---RAK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2011-02-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-02-03 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-02-03 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2011-02-03 13:30:21 | REMOVE MECHANICAL PLAN PRIOR TO ISSUANCE | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2011-02-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-01-31 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-01-31 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2011-02-02 07:48:37 | ****PROVISOS**** | | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6732 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. OWNER, CONTRACTOR AND ARCHITECT UNDERSTAND AND | | | ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S | | | NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW | | | CONSTRUCTION (PROJECT IS A SUBSTANTIAL IMPROVEMENT). | | | | | | 2. FBC R M1401.5, SUBMIT A "CONSTRUCTION DRAWINGS" | | | ELEVATION CERTIFICATE WHICH INCLUDES THE FOLLOWING | | | INFORMATION: | | | | | | PROPOSED ELEVATION FOR MECHANICAL EQUIPMENT, MINIMUM | | | 7.5' | | | | | | CLARIFICATION REGARDING LOWEST FLOOR (CAN BE INCLUDED | | | IN "COMMENTS" SECTION) IN ORDER TO SHOW COMPLIANCE WITH | | | REQUIREMENT THAT DUCTWORK IS INSTALLED ABOVE 7.5'; 6.7 | | | IS SHOWN ON C2A BUT THAT ELEVATION IS NOT ON THE SURVEY | | | (7.63 SHOWN AS CRAWLSPACE ELEVATION). | | | | | | | | | 3. REVISE PLAN TO INCORPORATE THE NEW MECHANICAL | | | DUCTWORK INSTALLATION DETAIL (DUCTWORK INSTALLED ABOVE | | | 7'6"). | | | | | | 4. FBC R 1411.3.1, PER ARCHITECT, DRAIN FROM AUXILIARY | | | DRAIN PAN TO BE REDIRECTED OR REMOVED, REVISE DETAIL | | | "SUSPENDED AIR HANDLERS," SHEET M1. | | | | | | 5. PER ARCHITECT, DUCTWORK UNDER HOUSE WILL BE LINED, | | | FBC R 1601.1.2, 1601.3.10. INCORPORATE REQUIREMENT INTO | | | PLAN. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2011-01-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-01-28 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-01-28 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2011-01-28 11:07:08 | ****CORRECTIONS**** | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6732 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH | | | HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT | | | IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE | | | 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED | | | ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED | | | ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION | | | CERTIFICATE. | | | | | | 2ND REVIEW, ELEVATION CERTIFICATE DOES NOT CORRELATE | | | WITH PLANS AND ARCHITECT'S INFORMATION. SEE BUILDING | | | COMMENTS. ELEVATION CERTIFICATE AT CONSTRUCTION | | | DOCUMENT PHASE IS TO INCLUDE PROPOSED ELEVATION FOR NEW | | | EQUIPMENT AND FOR DUCTWORK. DETAIL SHOWING THAT | | | DUCTWORK TO BE INSTALLED ABOVE 7.5' TO BE INCORPORATED | | | INTO THE PLAN. | | | | | | 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE | | | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR | | | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL | | | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH | | | NFIP REQUIREMENTS. | | | | | | 2ND REVIEW, SEE COMMENT #1. | | | | | | 3-5. ADDRESSED. | | | | | | 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO | | | RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE | | | ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT. | | | HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT | | | STATEMENT. | | | | | | 2ND REVIEW, NO ANCHORS SPECIFIED FOR BOTTOM OF STAND. | | | | | | 7. ADDRESSED. | | | | | | 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY | | | DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES | | | NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE. | | | | | | 2ND REVIEW, FLOAT SWITCH IS NOTED. HOWEVER, THE DRAIN | | | LINE FROM THE AUXILIAIRY DRAIN PAN TO CONDENSATE DRAIN | | | LINE IS NOT PERMITTED. PLEASE REMOVE OR REROUTE AS PER | | | FBC R1411.3. | | | | | | 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2, | | | 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE. | | | | | | 2ND REVIEW, DUCT IS NOTED AS INSULATED. PLEASE INCLUDE | | | REQUIREMENT THAT DUCT IS TO BE LINED (INSIDE OF DUCT) | | | FOR UNDER HOUSE DUCTWORK. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-02-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-01-03 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-02-02 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2011-01-03 09:59:24 | ****CORRECTIONS**** | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6732 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH | | | HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT | | | IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE | | | 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED | | | ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED | | | ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION | | | CERTIFICATE. | | | | | | 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE | | | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR | | | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL | | | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH | | | NFIP REQUIREMENTS. | | | | | | 3. FBC 106, THE SITE PLAN HAS A HANDWRITTEN NOTE WHICH | | | STATES NOT TO EXCEED 2FT SETBACK. THE BUILDING IS SHOWN | | | AT 4.8FT FROM PROPERTY LINE, M1 SHOWS 1FT BETWEEN UNIT | | | AND BUILDING AND 34IN DEPTH FOR THE UNIT. PLEASE | | | CONFIRM UNIT SIZE AND LOCATION AND DISTANCE TO PROPERTY | | | LINE. | | | | | | 5. M1, HVAC GENERAL NOTE 6, R4 DUCTS DO NOT COMPLY WITH | | | FBC R TABLE 1110.AB.2.1. THIS APPEARS TO BE A GENERAL | | | NOTE NOT APPLICABLE TO DETAILS SPECIFIC TO THIS JOB; | | | EITHER REMOVE OR COMPLY. | | | | | | 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO | | | RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE | | | ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT. | | | HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT | | | STATEMENT. | | | | | | 7. AHU 3 GROUND FLOOR DOOR ENCROACHES ON THE UNIT | | | SPACE, DOES NOT APPEAR THAT THE DOOR SHOWN ON M2 CAN | | | CLOSE, AND WHAT APPEARS TO BE THE RETURN AIR REGISTER | | | IS OUTSIDE THE DOOR. ACCESS TO THE UNIT IS NOT CLEAR. | | | ARCHITECTURAL SHEETS ARE NOT CONSISTENT WITH M2 SHEETS | | | REGARDING AHU 3 DOOR. | | | | | | 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY | | | DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES | | | NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE. | | | | | | 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2, | | | 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-01-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-01-28 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-01-28 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2010-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-12-17 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-12-17 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2010-12-17 10:48:47 | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO SETS OF SANITARY ISOMETRIC DRAWINGS FOR | | | THE PROJECT AS REQUIRED BY FBC 106.3.5.4. SPECIFY THE | | | PIPE SIZES, CLEAN OUTS, TRAPS, FIXTURE TYPES, ETC. | | | | | | 2) THE PLUMBING PLAN ON PL-1 SHOWS THE 4" BUILDING | | | DRAIN TYING INTO A NEW 3" BUILDING DRAIN AT THE PANTRY | | | AREA AND CONTINUING TO AN EXISTING 3" BUILDING SEWER. | | | FBC R 3005.1.7 DOES NOT ALLOW THE SIZE OF THE DRAINAGE | | | PIPING TO BE REDUCED IN SIZE IN THE DIRECTION OF THE | | | FLOW. PLEASE CORRECT. | | | | | | 3) THE PLUMBING FIXTURE SCHEDULE ON PL-1 CONTAINS | | | NUMEROUS ERRORS. THE TRAP SIZES ARE INCORRECT. SEE FBCR | | | TABLE P3201.7. THE SHOWERS ARE MARKED P3, THE SINKS ARE | | | MARKED P4 ON THE PLANS AND THE SCHEDULE DOES NOT | | | CORRESPOND. PLEASE CORRECT. | | | | | | 4) THE TOTAL FIXTURE UNIT COUNT IS NOT CORRECT. SEE | | | FBCR TABLE P3004.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2011-01-19 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2011-01-19 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2011-01-19 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2011-01-19 16:55:34 | LANDSCAPE PERMIT APPLIED FOR UNDER SEPERATE PERMIT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-12-02 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2010-12-02 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2010-12-02 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2010-12-02 15:11:50 | PLANNING AND ZONING: ***** FAILED**** | | | | | | 1. THE VALUE OF THE CONSTRUCTION ($198,000) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($132,070) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN SHALL BE INCLUDED WITH THE PERMIT | | | RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO ARTICLE | | | XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A | | | SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL | | | BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO | | | CONFORMITY. | | | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | | | 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES AS WELL AS PAD AND | | | EQUIPTMENT SIZES. PURSUANT TO SECTION 94-305(B)(4) OF | | | THE ZLDR: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE | | | THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1457 | | | E-MAIL: [email protected] | | | |
|
|
|