Plan Review Details - Permit 10110584
Plan Review Stops For Permit 10110584
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-12-01 Cont ID  
Sent By jwitmer Date 2010-12-01 Time 15:35 Rev Time 0.50
Received By jwitmer Date 2010-12-01 Time 15:05 Sent To  
Notes
2010-12-01 15:39:50 
 BUILDING PLAN REVIEW
 PERMIT: 10110584
 ADD: 222 LAKEVIEW AVE/ 14TH FLOOR
 CONT: ROYAL ASSET SECURITY INC
 TEL: (561)504-5800
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1008.1.3.4 ACCESS-CONTROLLED EGRESS DOORS
  
 BUILDING PROVISO:
  
 1008.1.3.4 ACCESS-CONTROLLED EGRESS DOORS. THE ENTRANCE
 DOORS IN A MEANS OF EGRESS IN BUILDINGS WITH AN
 OCCUPANCY IN GROUP A, B, D, E, M, R-1 OR R-2 AND
 ENTRANCE DOORS TO TENANT SPACES IN OCCUPANCIES IN
 GROUPS A, B, D, E, M, R-1 AND R-2 ARE PERMITTED TO BE
 EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM WHICH SHALL BE INSTALLED IN ACCORDANCE
 WITH ALL OF THE FOLLOWING CRITERIA:
  
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE
 ARRANGED TO DETECT AN OCCUPANT APPROACHING THE DOORS.
 THE DOORS SHALL BE ARRANGED TO UNLOCK BY A SIGNAL FROM
 OR LOSS OF POWER TO THE SENSOR.
  
 2. LOSS OF POWER TO THAT PART OF THE ACCESS CONTROL
 SYSTEM WHICH LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS.
  
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK FROM A MANUAL
 UNLOCKING DEVICE LOCATED 40 INCHES TO 48 INCHES (1016
 MM TO 1219 MM) VERTICALLY ABOVE THE FLOOR AND WITHIN 5
 FEET (1524 MM) OF THE SECURED DOORS. READY ACCESS SHALL
 BE PROVIDED TO THE MANUAL UNLOCKING DEVICE AND THE
 DEVICE SHALL BE CLEARLY IDENTIFIED BY A SIGN THAT READS
 "PUSH TO EXIT." WHEN OPERATED, THE MANUAL UNLOCKING
 DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO
 THE LOCK???INDEPENDENT OF THE ACCESS CONTROL SYSTEM
 ELECTRONICS???AND THE DOORS SHALL REMAIN UNLOCKED FOR A
 MINIMUM OF 30 SECONDS.
  
 4. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOORS, AND THE
 DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RESET.
  
 5. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOORS. THE DOORS SHALL REMAIN UNLOCKED UNTIL
 THE FIRE ALARM SYSTEM HAS BEEN RESET.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-10 Cont ID  
Sent By rlecky Date 2010-12-10 Time 14:19 Rev Time 0.00
Received By rlecky Date 2010-12-10 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-27 Cont ID  
Sent By wjolin Date 2010-12-08 Time 13:57 Rev Time 0.00
Received By wjolin Date 2010-12-08 Time 13:27 Sent To  
Notes
2010-12-08 13:57:24222 LAKEVIEW AVENUE, 14TH FLOOR
 PERMIT #10110584
 REVIEW COMMENTS - FIRE
  
 SEE MASTER PERMIT FOR ACCESS-CONTROLLED EGRESS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-10 Cont ID  
Sent By rlecky Date 2010-12-10 Time 14:22 Rev Time 0.00
Received By rlecky Date 2010-12-01 Time 11:25 Sent To  
Notes
2010-12-01 11:26:25SENT TO B21

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-08 Cont ID  
Sent By aaponte Date 2010-12-08 Time 16:42 Rev Time 0.00
Received By aaponte Date 2010-12-08 Time 16:42 Sent To  
Notes
***NONE***