Plan Review Details - Permit 10110538
Plan Review Stops For Permit 10110538
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-11-23 Cont ID  
Sent By jwitmer Date 2010-11-23 Time 15:57 Rev Time 1.00
Received By jwitmer Date 2010-11-23 Time 13:57 Sent To  
Notes
2010-11-29 11:27:24BUILDING PLAN REVIEW
 PERMIT: 10110538
 ADD: 901 45TH ST CATH LAB
 CONT: WESTBROOKE CORPORATION
 TEL: (561)239-7133
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PLEASE CORRECT PLANS, BETWEEN THE G-020 LIFE SAFETY,
 A-101GROUND FLOOR & M-201 AS TO WHICH WALLS ARE FIRE
 AND OR SMOKE RATED VERSES DAMPERS AND REQUIREMENTS FOR
 FIRE AND SMOKE RATINGS IN CORRIDOR 157 & 55.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-11-29 Cont ID  
Sent By jleahy Date 2010-11-29 Time 10:22 Rev Time 0.00
Received By jleahy Date 2010-11-29 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-11-23 Cont ID  
Sent By wjolin Date 2010-11-23 Time 15:40 Rev Time 0.00
Received By wjolin Date 2010-11-23 Time 15:07 Sent To  
Notes
2010-11-23 15:40:54901 45TH STREET
 PERMIT #10110538
 REVIEW COMMENTS - FIRE
  
 PROVIDE SPRINKLER COVERAGE TO ACCOMMODATE ANY LACK OF
 FLOOR COVERGE CAUSED BY THE TEMPORARY 1-HOUR FIRE/SMOKE
 PARTITION.
  
 ENSURE SPRINKLER COVERAGE NOT OBSTRUCTED BY STATIONARY
 GE EQUIPMENT CEILING RAIL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-29 Cont ID  
Sent By jwitmer Date 2010-11-29 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2010-11-19 Time 10:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-11-23 Cont ID  
Sent By hmoser Date 2010-11-23 Time 14:26 Rev Time 0.00
Received By hmoser Date 2010-11-23 Time 14:26 Sent To  
Notes
2010-11-23 14:41:04PASS PROVISO
 PLEASE EXPLAIN HOW THE SMOKE FIRE DAMPERS CHANGE TO
 FIRE DAMPERS IN THE EXIT CORRIDOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-11-20 Cont ID  
Sent By lwagner Date 2010-11-20 Time 09:58 Rev Time 0.00
Received By lwagner Date 2010-11-20 Time 07:58 Sent To  
Notes
2010-11-20 09:59:23MED GAS PERMIT REQUIRED