Plan Review Details - Permit 10110538
| Plan Review Stops For Permit 10110538 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-11-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-11-23 |
Time |
15:57 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2010-11-23 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2010-11-29 11:27:24 | BUILDING PLAN REVIEW | | | PERMIT: 10110538 | | | ADD: 901 45TH ST CATH LAB | | | CONT: WESTBROOKE CORPORATION | | | TEL: (561)239-7133 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | PLEASE CORRECT PLANS, BETWEEN THE G-020 LIFE SAFETY, | | | A-101GROUND FLOOR & M-201 AS TO WHICH WALLS ARE FIRE | | | AND OR SMOKE RATED VERSES DAMPERS AND REQUIREMENTS FOR | | | FIRE AND SMOKE RATINGS IN CORRIDOR 157 & 55. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-11-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2010-11-29 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2010-11-29 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-11-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-11-23 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-11-23 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2010-11-23 15:40:54 | 901 45TH STREET | | | PERMIT #10110538 | | | REVIEW COMMENTS - FIRE | | | | | | PROVIDE SPRINKLER COVERAGE TO ACCOMMODATE ANY LACK OF | | | FLOOR COVERGE CAUSED BY THE TEMPORARY 1-HOUR FIRE/SMOKE | | | PARTITION. | | | | | | ENSURE SPRINKLER COVERAGE NOT OBSTRUCTED BY STATIONARY | | | GE EQUIPMENT CEILING RAIL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-11-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-11-29 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-11-19 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-11-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2010-11-23 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2010-11-23 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2010-11-23 14:41:04 | PASS PROVISO | | | PLEASE EXPLAIN HOW THE SMOKE FIRE DAMPERS CHANGE TO | | | FIRE DAMPERS IN THE EXIT CORRIDOR. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-11-20 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-11-20 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-11-20 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2010-11-20 09:59:23 | MED GAS PERMIT REQUIRED |
|
|
|