Plan Review Details - Permit 10110512
| Plan Review Stops For Permit 10110512 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2010-12-13 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2010-12-13 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2010-12-13 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2010-12-03 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2010-12-03 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2010-12-03 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2010-12-03 11:35:53 | 1. APPLICANT FAILED TO PROVIDE AN ENGINEER OF RECORD AS | | | PREVIOUSLY REQUESTED IN ACCORDANCE WITH FBC SECTION | | | 105.3.1.2. PROPOSED CHANGES TO THE ELECTRICAL SYSTEM | | | MUST BE SIGNED AND SEALED. | | | 2. THE NEW METER CAN AND DISCONNECT MUST BE PRECISELY | | | LOCATED ON THE PLANS TO SCALE OR DIMENSIONED. | | | 3. VERIFY THE NEW ELECTRICAL X-RAY EQUIPMENT AND | | | CONTROLLERS ARE LISTED BY A NATIONALLY RECOGNIZED | | | TESTING AGENCY. | | | 4. PROVIDE DETAIL FOR THE EQUIPMENT TRANSFORMER | | | INCLUDING CONNECTION SCHEMATIC WITH APPROPRIATE | | | CIRCUITRY DETAIL. | | | 5. PROVIDE A GROUNDING DETAIL FOR THE NEW SERVICE. NEC | | | 2008 SECTION 250-24 | | | | | | R. LECKY, ELECTRICAL PLANS EXAMINER, WPB CONSTRUCTION | | | SERVICES . PHONE 561-805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-12-03 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-12-03 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-12-03 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2010-12-03 13:57:50 | SECOND SUBMITTAL, 11/18/10 ORIGINAL HAS BEEN MISPLACED. |
|
|
|
Account Summary | Usage Policy | Privacy Policy