Plan Review Details - Permit 10110512
Plan Review Stops For Permit 10110512
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-12-13 Cont ID  
Sent By rlecky Date 2010-12-13 Time 10:21 Rev Time 0.00
Received By rlecky Date 2010-12-13 Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-12-03 Cont ID  
Sent By rlecky Date 2010-12-03 Time 11:00 Rev Time 0.00
Received By rlecky Date 2010-12-03 Time 11:00 Sent To  
Notes
2010-12-03 11:35:531. APPLICANT FAILED TO PROVIDE AN ENGINEER OF RECORD AS
 PREVIOUSLY REQUESTED IN ACCORDANCE WITH FBC SECTION
 105.3.1.2. PROPOSED CHANGES TO THE ELECTRICAL SYSTEM
 MUST BE SIGNED AND SEALED.
 2. THE NEW METER CAN AND DISCONNECT MUST BE PRECISELY
 LOCATED ON THE PLANS TO SCALE OR DIMENSIONED.
 3. VERIFY THE NEW ELECTRICAL X-RAY EQUIPMENT AND
 CONTROLLERS ARE LISTED BY A NATIONALLY RECOGNIZED
 TESTING AGENCY.
 4. PROVIDE DETAIL FOR THE EQUIPMENT TRANSFORMER
 INCLUDING CONNECTION SCHEMATIC WITH APPROPRIATE
 CIRCUITRY DETAIL.
 5. PROVIDE A GROUNDING DETAIL FOR THE NEW SERVICE. NEC
 2008 SECTION 250-24
  
 R. LECKY, ELECTRICAL PLANS EXAMINER, WPB CONSTRUCTION
 SERVICES . PHONE 561-805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-03 Cont ID  
Sent By lmartine Date 2010-12-03 Time 13:56 Rev Time 0.00
Received By lmartine Date 2010-12-03 Time 13:56 Sent To  
Notes
2010-12-03 13:57:50SECOND SUBMITTAL, 11/18/10 ORIGINAL HAS BEEN MISPLACED.