Plan Review Details - Permit 10110508
Plan Review Stops For Permit 10110508
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-11-23 Cont ID  
Sent By jwitmer Date 2010-11-23 Time 14:53 Rev Time 2.20
Received By jwitmer Date 2010-11-23 Time 14:53 Sent To  
Notes
2010-11-23 14:58:21NO ROOFING PRODUCT APPROVALS WERE SUBMITTED/ NO ROOFER
 APPLIED ON PERMIT APPLICATION SEPERATE PERMIT, REVIEW
 AND ASSOCIATED FEES.
  
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1.0 SECTION A WILL REQUIRE A BOND BREAK.
 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED
 TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE
 TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND
 THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 2) SHEET S-2.0 DETAIL #8 IS MISSING THE STRAP
 CONNECTION BETWEEN THE TRUSS AND DOUBLE BOTTOM PLATE.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-16 Cont ID  
Sent By rlecky Date 2010-12-16 Time 14:00 Rev Time 0.00
Received By rlecky Date 2010-12-16 Time 12:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-03-07 Cont ID  
Sent By mgonzale Date 2011-03-10 Time   Rev Time 0.00
Received By mgonzale Date 2011-03-07 Time   Sent To  
Notes
2011-03-10 15:32:31PASSED WITH PROVISOS:
  
 #1 ADA TRUNCATED DOMES WILL NEED TO BE BRAUGHT UP TO
 CODE.
 FBC, SECTION 11-4.29.5.( MISSING DETECTABLE WARNINGS)
 (SOME LOCATIONS IN THE ROW OF 7TH STREET WILL NEED
 THESE ELEMENTS AS
 EXISTING CONDITIONS OF TRUNCATED CONCRETE STAMPED
 TRUNCAPTED DOMES HAVE DETERIORATED)
  
 #2 DUMPSTER ENCLOSURE WILL NEED TO MEET MINIMUM CITY OF
 WPB STANDARDS.
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/PDF/STANDARDS/GC-8
 .PDF
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_STANDARDS.HTM
  
 #3 EXISTING PRIVATE FIRE HYDRANT MUST MEET CODE. THE
 HYDRANT LOCATION MUST HAVE CLEARANCE FROM NEAR BYE
 OBJECTS TO BE OPERATIONAL.
 PROPOSED STOP SIGN MUST BE LOCATED SO THAT IT DOES NOT
 HINDER HYDRANT OPERATION.
  
 #4 EXISTING PLANTERS ALONG THE FRONTAGE OF THE SITE IS
 MISSING VEGETATION. PROVIDE PLANTS AS REQUIRED TO MEET
 LANSCAPE CODE.
  
 #5 LOCATIONS IN THE ROW WHERE PLANTS HAVE BEEN REMOVED
 AND PLANTERS WILL NOT BE REQUIRED CONTRACTOR AND/OR
 OWNER MUST
 OBTAIN ROW PERMIT TO REMOVE AND REPLACE WITH CONCRETE.
  
 IF ANY QUESTIONS ON CITY ROAD ROW PLEASE CONTACT:
 DEAN S LAUDERMILK
 UTILITIES ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1083
 FAX: 494-1117
 E-MAIL: [email protected]
  
 *******************************************
  
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-12-14 Cont ID  
Sent By mgonzale Date 2010-12-14 Time   Rev Time 1.00
Received By mgonzale Date 2010-12-14 Time   Sent To  
Notes
2010-12-14 10:58:46FAILED:
  
 A SEPARATE SUBMITTAL WILL NEED TO BE MADE DIRECTLY TO
 ENGINEERING SERVICES DEPARTMENT.
 GO TO
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 GO TO
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/UPLOADS/2010-10-20
 -16-37-34-DEVELOPMENTPERMITPACKAGE2011.PDF
 PRINT AND SUBMIT:
 #1 DEVELOPMENT APPLICATION COVER
 #2 STANDARD APPLICATION FOR DEVELOPMENT PERMIT FORM
 ALONG WITH
 1. ENGINEERING PLANS - SIX (6) SETS OF SIGNED AND
 SEALED PLANS IN THE ORDER LISTED BELOW, ALONG WITH A
 LETTER DESCRIBING THE SUBMITTAL.
 A. COVER SHEET
 B. PAVING, GRADING, AND DRAINAGE PLANS
 C. PAVING, GRADING, AND DRAINAGE DETAILS
 D. WATER AND SEWER PLAN (IF ANY ADDITIONAL LOAD IS
 PLACED ON WATER AND SEWER)
 E. WATER AND SEWER DETAILS* (IF ANY ANY NEW WATER AND
 SEWER SERVICES ARE REQUESTED)
 F. OFFSITE IMPROVEMENTS (DRIVEWAY APRONS, SIDEWALKS,
 SERVICE RELOCATION/MODIFICATIONS, ETC)
 G. STORMWATER POLLUTION PROTECTION PLAN
 2. DRAINAGE CALCULATIONS - 2 COPIES SIGNED AND SEALED
 (INCLUDE SURFACE WATER MANAGEMENT CALCULATIONS IN ACRES
 AND S.F.)
 A.IDENTIFY LOCATION ON OUTFALL OR CITY CONNECTION. IF
 NOT IN USE CITY WILL HAVE DEVELOPER/OWNER CAP AND
 ELIMINATE SUCH SERVICE.
  
 TO: ENGINEERING SERVICES DEPARTMENT
 ATTENTION: MR. BRIAN MOREE,
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
  
 *******************************************************
 **********
  
 GENERAL COMMENTS:
 EXISTING BUILDINGS WHICH HAVE PLUMBING DRAIN OUTLETS AT
 AN ELEVATION 12" OR LESS ABOVE THE GROUND SURFACE OF
 THE NEXT UPSTREAM MANHOLE, WHERE THE ELEVATION OF ANY
 FLOOR IS AT OR BELOW THE INVERT OF THE ADJACENT CITY
 SANITARY SEWER MAIN OR
 IS LESS THAN 12" ABOVE THE GROUND SURFACE OF THE NEXT
 UPSTREAM MANHOLE, OR WHERE A CONDITION EXISTS WHERE A
 PLUG IN THE CITY SANITARY SEWER MAIN WILL CAUSE THE
 HYDRAULIC GRADIENT TO RISE ABOVE THE LOWEST FLOOR
 LEVEL.
  
 CITY ORDINANCE 3132-98, SECTION 32-18(A): "...IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR INDIRECTLY
 DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY OF THE
 PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER SYSTEM
 WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT COMPOSED
 ENTIRELY OF STORM WATER." AND, SECTION 32-18(C): "NO
 PERSON MAY MAINTAIN, USE OR ESTABLISH ANY DIRECT OR
 INDIRECT CONNECTION TO THE STORM WATER SYSTEM THAT
 RESULTS IN ANY DISCHARGE IN VIOLATION OF THIS
 ORDINANCE. THIS PROHIBITION IS RETROACTIVE AND APPLIES
 TO CONNECTIONS MADE IN THE PAST, REGARDLESS OF WHETHER
 MADE UNDER A PERMIT, OR OTHER AUTHORIZATION, OR WHETHER
 PERMISSIBLE UNDER LAWS OR PRACTICES APPLICABLE OR
 PREVAILING AT THE TIME THE CONNECTION WAS MADE."
  
 CHAPTER 62.302, F.A.C. EFFECTIVELY STATES THAT THE SITE
 IS NOT ALLOWED TO DISCHARGE ANY QUANTITY OF WATER THAT
 VIOLATES STATE WATER QUALITY STANDARDS. CITY ORDINANCE
 3132-98, SECTION 32-18(A) STATES THAT IT IS A VIOLATION
 TO DISCHARGE ANYTHING EXCEPT STORM WATER INTO THE
 CITY'S MS4. THE CITY HAS THE AUTHORITY AND OBLIGATION
 TO ENFORCE THESE RESTRICTIONS. IF THE APPLICANT'S
 PROPOSED SYSTEM IS NOT PROVIDING SUFFICIENT WATER
 QUALITY TREATMENT (SO THAT ANY DISCHARGE IS FREE OF ALL
 BUT STORM WATER RUNOFF), THEN APPLICANT MUST RE-DESIGN
 THE SYSTEM.
  
 *******************************************************
 **********
  
 MANUEL JULIAN GONZALEZ
 CONSTRUCTION SERVICE DEPARTMENT ENGINEERING REVIEW
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-03-07 Cont ID  
Sent By wjolin Date 2011-03-07 Time 10:03 Rev Time 0.00
Received By wjolin Date 2011-03-07 Time 09:15 Sent To  
Notes
2011-03-07 10:03:48411 7TH STREET
 PERMIT #10110508
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A KNOXBOX KEY SWITCH TO ALLOW EMERGENCY
 RESPONDERS ACCESS THROUGH THE SECURITY FENCE/GATE. KEY
 SWITCH CAN BE ORDERED FROM WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-06 Cont ID  
Sent By mcarsill Date 2010-12-06 Time 11:47 Rev Time 0.00
Received By mcarsill Date 2010-12-06 Time 11:21 Sent To  
Notes
2010-12-06 11:47:10411-7TH STREET
 PERMIT NUMBER 10110508
 "ADDITION OF BUILDING TO EXISTING STORAGE FACILITY"
  
  
 1. THE BUILDING ADDRESS IS REQUIRED. THE MINIMUM OF 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED ON THE
 PROPER ELEVATION.
  
 2. THE PORTABLE FIRE EXTINGUISHERS ARE TO BE PROPERLY
 SERVICE TAGGED.
  
 3. A MALTESE CROSS IS REQUIRED TO BE PLACED ON THE
 BUILDING WITH THE LETTER R SIGNIFYING THAT A ROOF TRUSS
 EXISTS ON THE BUILDING. THIS IS FOR FIREFIGHTER SAFETY
 AND NEEDS TO BE CALLED OUT ON THE PLANS.
  
 4. PLEASE ENSURE THAT AN EXISTING KNOX-BOX IS PRESENT
 FOR ENTRY THROUGH THE EXISTING GATES SHOWN ON THE
 PLANS.
  
 5. PLEASE INDICATE ON THE PLANS THE TYPES OF MATERIALS
 THAT WILL BE STORED AT THE LOCATION. NO STORAGE OF ANY
 EXPLOSIVES OR HAZARDOUS MATERIALS, FLAMMABLE GASES OR
 LIQUIDS SHALL OCCUR AT THE LOCATION.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT LOCATIONS.
  
 7. PLEASE INDICATE HOURS OF OPERATION. NO EXIT SIGNAGE
 OR EMERGENCY LIGHTING SHOWN ON THE PLANS. PLEASE REVIEW
 CHAPTER 42 OF THE LIFE SAFETY CODE (101) FOR STORAGE
 OCCUPANCIES
  
 8. PLEASE INDICATE IF LOW, ORDINARY OR HIGH HAZARD
 MATERIALS WILL BE STORED AT THE LOCATION.
  
 9. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 10. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 11. SUITABLE ACCESS SHALL BE PROVIDED FOR FIRE AND
 PARAMEDICAL EQUIPMENT DURING CONSTRUCTION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-16 Cont ID  
Sent By lmartine Date 2011-03-16 Time 14:47 Rev Time 0.00
Received By lmartine Date 2011-02-25 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-09 Cont ID  
Sent By rmcdouga Date 2010-12-16 Time 13:48 Rev Time 0.00
Received By lmartine Date 2010-11-18 Time 09:34 Sent To  
Notes
2010-11-19 09:34:52C3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-03-16 Cont ID  
Sent By lmartine Date 2011-03-16 Time 14:47 Rev Time 0.00
Received By lmartine Date 2010-11-23 Time 14:58 Sent To  
Notes
2011-03-16 14:49:29RECEIPT PROVIDED FROM FOUNDATION PERMIT #11010631
2010-11-23 14:58:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-03-03 Cont ID  
Sent By rkussner Date 2011-03-03 Time 14:13 Rev Time 0.00
Received By rkussner Date 2011-03-03 Time 14:13 Sent To  
Notes
2011-03-03 14:14:51***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #11030015 FOR LANDSCAPE PERMIT
 AND PLANS---RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-12-16 Cont ID  
Sent By rkussner Date 2010-12-16 Time 16:37 Rev Time 0.00
Received By rkussner Date 2010-12-16 Time 16:37 Sent To  
Notes
2010-12-16 16:42:38***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT.
 PROVIDE TWO COPIES OF THE LANDSCAPE PLAN AND CERTIFIED
 COST ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO UNIT
 COXT.
  
 2. PLEASE APPLY FOR A SEPARATE IRRIGATION PERMIT. TWO
 COPIES OF AN IRRIGATION PLAN THAT PROVIDES 120%
 COVERAGE TO ALL LANDSCAPED AREAS WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-06 Cont ID  
Sent By hmoser Date 2010-12-06 Time 13:38 Rev Time 0.00
Received By hmoser Date 2010-12-06 Time 13:27 Sent To  
Notes
2010-12-06 13:47:12 
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-12-01 Cont ID  
Sent By lwagner Date 2010-12-01 Time 14:42 Rev Time 0.00
Received By lwagner Date 2010-12-01 Time 14:08 Sent To  
Notes
2010-12-01 14:33:59UPDATE:
 2/24/11 PLUMBING FIXTURES ARE WITHIN DISTANCE PER
 PLUMBING CODE 403.4.1. SEE SEALED LETTER FOR EXISTING
 FACILITIES.
  
  
 FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 NO PLUMBING FACILITIES WERE SHOWN ON PLANS.
 PLUMBING 403.1 MINIMUM NUMBER OF FIXTURES #8 STORAGE:
 WATER CLOSETS = 1 PER 100
 LAVATORIES = 1 PER 100
 DRINKING FOUNTAIN = 1 PER 1,000
 SERVICE SINK = 1
  
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
  
 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN
 COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET
 FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY
 ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH
 TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH
 FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-03-16 Cont ID  
Sent By aaponte Date 2011-03-16 Time 11:57 Rev Time 0.00
Received By aaponte Date 2011-03-16 Time 11:57 Sent To  
Notes
2011-03-16 11:58:38PROVISO: 1. WESTERN DRIVEWAY SHALL BE MARKED AS ONE-WAY
 ONLY.
 2. BIKE RACKS SHALL COMPLY IWHT CITY'S DESIGN
 STANDARDS.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-15 Cont ID  
Sent By aaponte Date 2010-12-15 Time 15:44 Rev Time 0.00
Received By aaponte Date 2010-12-15 Time 15:11 Sent To  
Notes
2011-01-10 15:47:371. LOADING AREA CAN NOT BLOCK ACCESS DRIVE. TWO-WAY
 ACCESS DRIVE SHALL BE A MINIMUM OF 24 FEET IN CLEAR
 WIDTH.
 2. NORTH FACADE SHALL PROVIDE ARCHITECTURAL
 ARTICULATION AS REQUIRED BY TABLE IV-4 OF THE ZLDR.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 822-1439
  
 NOTE: THE COMMENTS FROM REVIEW WHERE NOT SAVED IN THE
 SYSTEM. THESE ARE WHAT I REMEMBER. CONFIRMATION WILL BE
 PROVIDED DURING SECOND REVIEW.