Plan Review Details - Permit 10110479
Plan Review Stops For Permit 10110479
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-11-30 Cont ID  
Sent By jwitmer Date 2010-11-30 Time 12:25 Rev Time 0.33
Received By jwitmer Date 2010-11-30 Time 12:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-11-30 Cont ID  
Sent By jdickins Date 2010-11-30 Time 19:40 Rev Time 0.00
Received By jdickins Date 2010-11-30 Time 19:40 Sent To  
Notes
2010-11-30 19:40:36OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-17 Cont ID  
Sent By mcarsill Date 2010-12-17 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2010-12-17 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-09 Cont ID  
Sent By wjolin Date 2010-12-09 Time 11:23 Rev Time 0.00
Received By wjolin Date 2010-12-09 Time 11:23 Sent To  
Notes
2010-12-09 11:23:44777 SOUTH FLAGLER DRIVE, SUITE #136 (EAST TOWER)
 PERMIT #10110479
 REVIEW COMMENTS - FIRE
  
 SHEET A1.1
 PROVIDE LIFE SAFETY DATA ENTAILING OCCUPANCY TYPE,
 OCCUPANT LOAD, NUMBER OF EXITS, TRAVEL DISTANCES, DOOR
 HARDWARE ETC.
  
 PROVIDE A FURNITURE LAYOUT.
  
 THE SWING OF RESTROOM DOOR NO.10 OBSTRUCTS MORE THAN 50
 PERCENT OF THE HALLWAY.
  
 SLIDING POCKET DOOR NO. 11 DOES NOT MEET THE EGRESS
 REQUIREMENTS OF CHAPTER 7 OF NFPA 101 - LIFE SAFETY
 CODE.
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION.
  
 PORTABLE FIRE EXTINGUISHERS (2A:10BC) SHALL BE LOCATED
 IN ALONG THE PATH OF EGRESS.
  
  
 SHEET FS0.1
 SPRINKLER DESIGN SHALL CONFORM TO THE 2003 EDITION OF
 NFPA 13 AS IS REFERENCED IN THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION.
  
 PROVIDE WATER SUPPLY DATA (FLOW TEST OR FIRE PUMP TEST
 RESULTS).
  
  
 SHEET FS2.1
 ALL SPRINKLERS INSTALLED ARE REQUIRED TO BE NEW. REUSE
 OF SPRINKLERS IS PROHIBITED. REVISE KEY NOTE NUMBER 1.
  
 PROTECT STORAGE SPACES AS ORDINARY HAZARD. REVISE KEY
 NOTE NUMBER 3 LABELING ALL SPACES AS LIGHT HAZARD.
  
 THIS SPRINKLER SYSTEM IS SUBJECT TO PRESSURES IN EXCESS
 OF 100 PSI. REVISE HANGER LOCATION SCHEDULE AND HANGER
 TYPES TO MEET THE REQUIREMENTS OF NFPA 13 FOR SYSTEM
 PRESSURES GREATER THAN 100 PSI.
  
  
 SHEET E-1
 SHOW THE SCOPE OF THE FIRE ALARM WORK.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR CONTRACTOR'S
 FIRE ALARM SHOP DRAWINGS.
  
  
 SHEET E-2
 PROVIDE ADDITIONAL EXIT SIGNAGE FOR WEST AREA OF OPEN
 OFFICE NO. 106.
  
 THERE DOES NOT APPEAR TO BE EMERGENCY LIGHTING PROVIDED
 FOR CONFERENCE ROOM 102.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-15 Cont ID  
Sent By lmartine Date 2010-12-15 Time 16:54 Rev Time 0.00
Received By lmartine Date 2010-12-15 Time 16:54 Sent To  
Notes
2010-12-15 16:55:21IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-09 Cont ID  
Sent By shill Date 2010-12-09 Time 15:18 Rev Time 0.00
Received By shill Date 2010-11-18 Time 16:30 Sent To  
Notes
2010-11-18 16:30:23B20
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-03 Cont ID  
Sent By hmoser Date 2010-12-03 Time 10:30 Rev Time 0.00
Received By hmoser Date 2010-12-03 Time 09:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-11-30 Cont ID  
Sent By lwagner Date 2010-11-30 Time 14:44 Rev Time 0.00
Received By lwagner Date 2010-11-30 Time 14:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-01 Cont ID  
Sent By aaponte Date 2010-12-01 Time 15:58 Rev Time 0.00
Received By aaponte Date 2010-12-01 Time 15:58 Sent To  
Notes
***NONE***