Plan Review Details - Permit 10110462
Plan Review Stops For Permit 10110462
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 09:25 Rev Time 0.00
Received By shill Date 2011-08-02 Time 09:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-07-18 Cont ID  
Sent By shill Date 2011-07-18 Time 15:12 Rev Time 0.00
Received By shill Date 2011-07-18 Time 15:12 Sent To  
Notes
2011-07-18 15:12:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE PLAN PROVIDED SHOWS THE UNIT LOCATED IN ZONE 1
 (FIELD). SEE BELOW DESIGN PRESSURES FROM FIRST
 CORRECTION LIST.
  
 FIELD 49.2PSF
 PERIMETER 82.6PSF
 CORNER 124.3 PSF
  
 2. COMMENT FROM PREVIOUS LIST: ON THE PRODUCT APPROVAL,
 INDICATE WHICH OPTION WILL BE USED ON THIS PROJECT TO
 SHOW COMPLIANCE WITH DESIGN PRESSURE REQUIREMENTS,
 FBC1609. SEE SHEET 2 OF PRODUCT APPROVAL.
  
 2ND REVIEW, RESPONSE IS THAT ALL UNITS ARE STAND DESIGN
 SCHEDULE 1. NOT ALL OF THE OPTIONS COMPLY WITH THE
 REQUIRED DESIGN PRESSURE OF 49.2 PSF. AS REQUESTED,
 PLEASE INDICATE WHICH OPTION IS PROPOSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-18 Cont ID  
Sent By shill Date 2010-11-18 Time 12:17 Rev Time 0.00
Received By shill Date 2010-11-18 Time 12:17 Sent To  
Notes
2010-11-18 12:17:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A PLAN SHOWING PROPOSED LOCATION ON ROOF,
 FBC1609. SHOW DISTANCE FROM ROOF EDGES. THIS IS
 REQUIRED TO DETERMINE ZONE LOCATION AND DESIGN PRESSURE
 REQUIRED WHICH THE ENGINEER HAS SPECIFIED AS:
  
 FIELD 49.2PSF
 PERIMETER 82.6PSF
 CORNER 124.3 PSF
  
 2. ON THE PRODUCT APPROVAL, INDICATE WHICH OPTION WILL
 BE USED ON THIS PROJECT TO SHOW COMPLIANCE WITH DESIGN
 PRESSURE REQUIREMENTS, FBC1609. SEE SHEET 2 OF PRODUCT
 APPROVAL.
  
 3. PLEASE CLARIFY, ARE THE EXISTING UNITS CURRENTLY
 INSTALLED ON THE ROOF? ADDITIONAL ENGINEERING TO VERIFY
 ABILITY OF EXISTING STRUCTURE TO ACCOMODATE THE
 ADDITIONAL LOADS, IF APPLICABLE, MAY BE REQUIRED.
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-06-24 Cont ID  
Sent By fmittner Date 2011-06-24 Time 16:40 Rev Time 0.00
Received By fmittner Date 2011-06-24 Time 16:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2010-11-17 Cont ID  
Sent By fmittner Date 2010-11-17 Time 13:06 Rev Time 0.00
Received By fmittner Date 2010-11-17 Time 11:32 Sent To  
Notes
2010-11-17 13:07:29FAILED DUE TO LACK OF SCREENING OF EQUIPTMENT. FHM
 11-17-10 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 09:25 Rev Time 0.00
Received By shill Date 2011-07-26 Time 16:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-18 Cont ID  
Sent By shill Date 2010-11-18 Time 12:19 Rev Time 0.00
Received By shill Date 2010-11-18 Time 12:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-11-17 Cont ID  
Sent By fmittner Date 2010-11-17 Time 13:08 Rev Time 0.00
Received By fmittner Date 2010-11-17 Time 13:08 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved