Plan Review Details - Permit 10110445
Plan Review Stops For Permit 10110445
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-03-16 Cont ID  
Sent By shill Date 2011-03-16 Time 11:07 Rev Time 0.00
Received By shill Date 2011-03-16 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-02 Cont ID  
Sent By shill Date 2011-03-02 Time 13:20 Rev Time 0.00
Received By shill Date 2011-03-02 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-02-02 Cont ID  
Sent By shill Date 2011-02-02 Time 15:27 Rev Time 0.00
Received By shill Date 2011-02-02 Time 15:27 Sent To  
Notes
2011-02-02 15:29:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THIS PARCEL IS TO BE DESIGNED TO EXPOSURE C
 PRESSURES OR AN ENGINEER MUST DETERMINE PRESSURES USING
 RATIONAL ANALYSIS. SEE FBC R301.2.1.4. NOTE THAT THE
 CODE CHANGED EFFECTIVE MARCH 1, 2009.
  
 R301.2.1.4 EXPOSURE CATEGORY. FOR EACH WIND DIRECTION
 CONSIDERED, AN EXPOSURE CATEGORY THAT ADEQUATELY
 REFLECTS THE CHARACTERISTICS OF GROUND SURFACE
 IRREGULARITIES SHALL BE DETERMINED FOR THE SITE AT
 WHICH THE BUILDING OR STRUCTURE IS TO BE CONSTRUCTED.
 FOR A SITE LOCATED IN THE TRANSITION ZONE BETWEEN
 CATEGORIES, THE CATEGORY RESULTING IN THE LARGEST WIND
 FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN OF
 VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE FROM
 NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM
 CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE
 EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER
 STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF
 THE FOLLOWING CATEGORIES:
  
 EXCEPTION: AN INTERMEDIATE EXPOSURE BETWEEN THE
 EXPOSURE CATEGORIES DEFINED IS PERMITTED IN A
 TRANSITION ZONE PROVIDED THAT IT IS DETERMINED BY A
 RATIONAL ANALYSIS METHOD.
  
 ROUGHNESS CATEGORY B MUST PREVAIL FOR 1500 FEET IN EACH
 UPWIND DIRECTION IN ORDER FOR EXPOSURE B PRESSURES TO
 BE USED.
  
 2. SHOW LOCATION FOR THE PROPOSED SKYLIGHT LOCATION,
 FBC R301 (DISTANCE TO EDGE).
  
 3. SPECIFY ROOF PITCH ON THE PLAN, FBC R301.
  
 4. REVISE PLAN TO SHOW SKYLIGHT SIZE. ITEMS 2, 3, AND 4
 ARE REQUIRED TO DETERMINE DESIGN PRESSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-21 Cont ID  
Sent By shill Date 2010-12-21 Time 15:22 Rev Time 0.00
Received By shill Date 2010-12-21 Time 15:22 Sent To  
Notes
2010-12-21 15:31:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. AAF GUIDE DOES NOT INCLUDE SKYLIGHTS IN THE
 GUIDELINES FOR INSTALLATION. PLEASE ADDRESS.
  
 2. THE SKYLIGHT PRODUCT APPROVAL REQUIRES FASTENING TO
 A ROOF DECK (WITH SHINGLES OR BUR INSTALLED). AN
 ENGINEERING ANALYSIS IS REQUIRED TO DETERMINE DESIGN
 PRESSURE LIMITATIONS FOR THE SKYLIGHT IN THE PROPOSED
 INSTALLATION METHOD. FBC R301, FBC 1609.
  
 3. PROVIDE A DETAIL FOR THE PROPOSED SKYLIGHT
 INSTALLATION (PREPARED BY AN ENGINEER) AS THE PROPOSED
 INSTALLATION IS NOT CONSISTENT WITH THE PRODUCT
 APPROVAL FAC9B72.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2011-03-16 Cont ID  
Sent By shill Date 2011-03-16 Time 11:07 Rev Time 0.00
Received By shill Date 2011-03-08 Time 08:54 Sent To  
Notes
2011-03-08 08:54:40SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-02-24 Cont ID  
Sent By rlecky Date 2011-02-24 Time 15:32 Rev Time 0.00
Received By rlecky Date 2011-02-24 Time 15:32 Sent To  
Notes
2011-02-24 15:33:26GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-01-13 Cont ID  
Sent By jwitmer Date 2011-01-13 Time 12:50 Rev Time 0.00
Received By jwitmer Date 2011-01-13 Time 12:50 Sent To  
Notes
2011-01-13 12:51:31INCOMING TO S. H.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-13 Cont ID  
Sent By jwitmer Date 2011-01-13 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2011-01-13 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-21 Cont ID  
Sent By shill Date 2010-12-21 Time 15:31 Rev Time 0.00
Received By shill Date 2010-11-18 Time 09:15 Sent To  
Notes
2010-11-18 09:15:43IN ZONING BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2010-11-22 Cont ID  
Sent By astelly Date 2010-11-22 Time 17:09 Rev Time 0.00
Received By astelly Date 2010-11-22 Time 17:09 Sent To  
Notes
***NONE***