Plan Review Details - Permit 10110436
Plan Review Stops For Permit 10110436
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-11-18 Cont ID  
Sent By jwitmer Date 2010-11-18 Time 10:40 Rev Time 0.55
Received By jwitmer Date 2010-11-18 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-11-18 Cont ID  
Sent By jdickins Date 2010-11-18 Time 16:27 Rev Time 0.00
Received By jdickins Date 2010-11-18 Time 16:27 Sent To  
Notes
2010-11-18 16:28:01OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER,LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-27 Cont ID  
Sent By wjolin Date 2010-12-27 Time 11:05 Rev Time 0.00
Received By wjolin Date 2010-12-27 Time 11:05 Sent To  
Notes
2010-12-27 11:09:20222 LAKEVIEW AVENUE, SUITE #1400
 TRACKING #10110436
 MASTER # 10080761
  
 THE SUBMITTED REVISED SECURITY PLAN ALLOWS UNRESTRICTED
 ACCESS TO BOTH EXIT STAIRS PER CHAPTER 7 OF THE LIFE
 SAFETY CODE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2010-12-06 Time   Rev Time  
Received By   Date 2010-12-06 Time   Sent To  
Notes
2010-12-07 09:50:10RESULTS AND NOTES TRANSFERRED FROM MASTER #10080761.
 RJR
  
 222 LAKEVIEW AVENUE, SUITE 1400
 MASTER PERMIT NUMBER 10080761
 REVISION TRACKING NUMBER 10110436
 "REVISED CEILING LAYOUT INCLUDING LIGHTING AND AC
 DIFFUSERS"
  
  
 1. CARD READERS ARE DISPLAYED IN BOTH STAIRWELLS. CARD
 READERS ARE NOT ALLOWED TO BE INSTALLED IN STAIRWELLS.
 PLEASE SEE NFPA 101 THE LIFE SAFETY CODE SECTION
 7.1.3.2.1 (6) OF WHAT EQUIPMENT IS ALLOWED TO BE
 CONTAINED WITHIN AN EXIT ENCLOSURE. IN ADDITION NFPA
 101 THE LIFE SAFETY CODE 7.2.1.5.7.1 SPEAKS TO STAIR
 ENCLOSURE DOORS. ALSO 7.2.1.5.7 DISCUSSES STAIR
 ENCLOSURES.
  
 2. IF CARD READERS ARE INSTALLED AT THE ELEVATOR
 LOBBIES HOW DOES A TRANSIENT VISITOR TO THE SPACE EXIT
 THIS AREA WITHOUT AN ACCESS CARD. ACCESS TO BOTH EXITS
 ARE MADE INACCESSIBLE AND WHEN THE FIRE ALARM SYSTEM
 ACTIVATES IS IT THE ENTIRE BUILDING OR THE FLOOR OF
 INCIDENT, FLOOR ABOVE AND FLOOR BELOW.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-27 Cont ID  
Sent By wjolin Date 2010-12-27 Time 11:09 Rev Time 0.00
Received By wjolin Date 2010-12-21 Time 09:21 Sent To  
Notes
2010-12-21 09:21:54SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-12-07 Time   Rev Time 0.00
Received By lmartine Date 2010-11-16 Time 15:42 Sent To  
Notes
2010-11-16 15:49:32************EXPEDITED************
 B--15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-07 Cont ID  
Sent By rregueir Date 2010-12-07 Time 09:52 Rev Time 0.00
Received By rregueir Date 2010-12-07 Time 09:50 Sent To  
Notes
2010-12-07 09:51:53**PROVISO**
  
 NEED REVISED PAGE A1.1 TO SHOW ELIMINATION OF RATED
 WALLS AT RESTROOM VESTIBULES WHERE FIRE DAMPERS HAVE
 BEEN ELIMINATED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]