Plan Review Details - Permit 10110420
Plan Review Stops For Permit 10110420
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-14 Cont ID  
Sent By rlecky Date 2011-01-14 Time 12:34 Rev Time 0.00
Received By rlecky Date 2011-01-14 Time 12:34 Sent To  
Notes
2011-01-14 12:36:03LOW VOLTAGE SECURITY CAMERA SUBMITTAL STAMPED AND
 RELEASED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-11-22 Cont ID  
Sent By jdickins Date 2010-11-22 Time 18:21 Rev Time 0.00
Received By jdickins Date 2010-11-22 Time 18:21 Sent To  
Notes
2010-11-22 18:22:41OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182
 NOTE:
 SEPERATE ELECTRICAL PERMIT REQUIRED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-17 Cont ID  
Sent By wjolin Date 2010-12-14 Time 15:18 Rev Time 0.00
Received By wjolin Date 2010-12-14 Time 14:59 Sent To  
Notes
2010-12-14 15:18:151920 WEKIVA WAY
 PERMIT #10110420
 REVIEW COMMENTS - FIRE
 APPROVED PROVISO
  
 SECOND FLOOR ACCESS CONTROL:
  
 NO LOCKS (MAG LOCKS, KEYED LOCKS ETC.) PERMITTED ON
 CORRIDOR DOORS #225A OR #247A. EGRESS SHALL BE FREE AT
 ALL TIMES.
  
 SECTION 7.4.1.6 OF THE FLORIDA FIRE PREVENTION CODE
 (NFPA 101 - 2006 EDITION WITH FLORIDA AMENDMENTS)
 REQUIRES ELEVATOR LOBBIES TO HAVE UNRESTRICTED ACCESS
 TO EXTIS. EXIT ACCESS SHALL NOT REQUIRE THE USE OF A
 KEY, TOOL, SPECIAL KNOWLEDGE OR SPECIAL EFFORT.
  
 UNRESTRICTED ACCESS TO TWO EXITS SHALL BE AVAILABLE TO
 ALL OCCUPANTS AT ALL TIMES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-19 Cont ID  
Sent By wjolin Date 2010-11-19 Time 16:21 Rev Time 0.00
Received By wjolin Date 2010-11-19 Time 16:00 Sent To E
Notes
2010-11-19 16:21:121920 WEKIVA WAY
 PERMIT #10110420
 MASTER #10070788
 REVIEW COMMENTS - FIRE
  
 NO MANUAL RELEASE BUTTON HAS BEEN PROVIDED INSIDE
 STORAGE ROOM 121.
  
 THE ACCESS CONTROL SYSTEM DEVICES ARE NOT PERMITTED
 INSIDE THE STAIRS.
  
 UPON EXITING THE ELEVATORS ON THE SECOND FLOOR, THE
 DOORS ARE LOCKED IN THE PATH OF EGRESS TO STAIR 1 AND
 STAIR 2. THIS IS NOT PERMITTED PER THE REQUIRMENTS OF
 ACCESS-CONTROLLED EGRESS DOORS.
  
 NO MANUAL RELEASE BUTTONS HAVE BEEN PROVIDED ON THE
 SECOND FLOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-01-14 Cont ID  
Sent By rlecky Date 2011-01-14 Time 12:36 Rev Time 0.00
Received By rlecky Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-14 Cont ID  
Sent By wjolin Date 2010-12-14 Time 15:18 Rev Time 0.00
Received By wjolin Date 2010-12-13 Time 14:22 Sent To  
Notes
2010-12-13 14:22:47TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-29 Cont ID  
Sent By shill Date 2010-11-29 Time 11:32 Rev Time 0.00
Received By shill Date 2010-11-18 Time 15:14 Sent To  
Notes
2010-11-18 15:15:07IN FIRE BOX