Plan Review Details - Permit 10110400
Plan Review Stops For Permit 10110400
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-20 Cont ID  
Sent By jwitmer Date 2010-12-20 Time 16:29 Rev Time 0.77
Received By jwitmer Date 2010-12-20 Time 16:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-29 Cont ID  
Sent By jwitmer Date 2010-11-29 Time 10:40 Rev Time 0.77
Received By jwitmer Date 2010-11-29 Time 10:40 Sent To  
Notes
2010-11-29 11:02:12BUILDING PLAN REVIEW
 PERMIT: 10110400
 ADD: 2505-C OKEECHOBEE BLVD
 CONT: ALL FLORIDA CONSTRUCTION
 TEL: (305)300-4026
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 THE PLANS INDICATE A NEW DOUBLE DOOR OPENING IN THE
 REAR OF THE BUILDING:
 1) PLEASE PROVIDE THE WIND DESIGN CRITERIA PER 1609.6.2
 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) NOTE THIS
 IS AN EXPOSURE"C".
  
 1.5 PRESSURES FOR COMPONENTS & CLADDING.
  
 2) THE NEW OPENING WILL REQUIRE PRODUCT APPROVALS,
 STATE OR MIAMI-DADE NOA ARE ACCEPTABLE.
 2A) DOUBLE DOORS RULE 9B-72/ RULE 9N-3 (31)(A)
 2B) STORM SHUTTERS IF THE DOUBLE DOORS ARE NOT LARGE
 MISSILE IMPACT TESTED.
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) SHEET A-1 DETAIL # 1 INDICATES THE USE OF A NEW
 COLUMN AND LINTEL. PLEASE REVIEW FBC-B 2104.1, ACI
 530.9.9.2. LINTELS
 MINIMUM END BEARING SHALL BE 4 INCHES.
  
 5) PLEASE CORRECT THE COVER SHEET AND A-2. THE PLANS
 INDICATE 3 EXITS ARE PROVIDED, WHILE SHEET A-2
 INDICATES ONE TO BE LOCKED AT ALL TIMES AND NOT TO BE
 PART OF THE MEANS OF EGRESS.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-11-18 Cont ID  
Sent By jdickins Date 2010-11-18 Time 18:32 Rev Time 0.00
Received By jdickins Date 2010-11-18 Time 18:32 Sent To  
Notes
2010-11-18 18:33:09OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER,LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-20 Cont ID  
Sent By wjolin Date 2010-12-20 Time 14:00 Rev Time 0.00
Received By wjolin Date 2010-12-20 Time 13:40 Sent To  
Notes
2010-12-20 14:00:322505 OKEECHOBEE BOULEVARD
 PERMIT #10110400
 REVIEW COMMENTS - FIRE
  
  
 A 36-INCH (MINIMUM) AISLE SHALL BE PROVIDED BETWEEN
 DISPLAY AREAS DESIGNATED IN FLOOR PADS.
  
 THE SCOPE OF WORK SHOWN ON DRAWING FS-1 SHOULD INCLUDE
 ALL OF SUITE C. THE EXISTING SPRINKLER LOCATIONS SHOWN
 ON THE PLAN RESULT IN SPRINKLER COVERAGES GREATER THAN
 130 SQUARE FEET. SEPARATE PLANS AND PERMIT REQUIRED FOR
 FIRE SPRINKLER MODIFICATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-08 Cont ID  
Sent By wjolin Date 2010-12-08 Time 13:20 Rev Time 0.00
Received By wjolin Date 2010-12-08 Time 11:25 Sent To  
Notes
2010-12-08 13:20:472505 OKEECHOBEE BOULEVARD, SUITE C
 PERMIT #10110400
 REVIEW COMMENTS - FIRE
  
 IN ADDTION TO THE FLORIDA BUILDING CODE, DESIGN SHALL
 CONFORM TO THE REQUIREMENTS OF THE FLORIDA FIRE
 PREVENTION CODE 2007 EDITION.
  
 ALL DEMOLITION WORK TO CONFORM TO THE REQUIREMENTS OF
 NFPA 241.
  
 PROVIDE TACTILE SIGNAGE AT EXITS.
  
 LABEL PERMANENTLY LOCKED DOORS AS "NOT AN EXIT".
  
 PROVIDE SCOPE OF WORK AFFECTING EXISTING FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEM. PROVIDE NEW/EXISTING DESIGN
 INFORMATION FOR THE FIRE SPRINKLER SYSTEM.
  
 PROVIDE ADDITIONAL INFORMATION FOR THE PADS REFERENCED
 ON SHEET A-1.
  
 COVER SHEET SHOWS AND OCCUPANT LOAD OF 235 PERSONS AND
 19 PERSONS. PLEASE EXPLAIN THE DISCREPANCY.
  
 THE PRINCIPLE EXIT IS DESCRIBED AS HAVING A THUMB TURN
 LOCK. DESCRIBE THE MECHANISM BEING USED TO OPEN THE
 DOOR (NONE, PANIC BAR, LEVER, ETC.)
  
 PROVIDE MAXIMUM STORAGE HEIGHT THAT IS INTENDED FOR
 THIS SPACE.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE ALARM/FIRE
 SPRINKLER SHOP DRAWINGS.
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-09 Cont ID  
Sent By hmoser Date 2010-12-09 Time 11:10 Rev Time 0.00
Received By hmoser Date 2010-11-17 Time 09:41 Sent To  
Notes
2010-11-17 11:51:42B--18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-12-09 Cont ID  
Sent By hmoser Date 2010-12-09 Time 11:02 Rev Time 0.00
Received By hmoser Date 2010-12-09 Time 08:40 Sent To  
Notes
2010-12-09 11:09:04IN REGARDS TO MECHANICAL PLANS PAGE M-1 MECHANICAL
 PERMITS ARE NOT REQUIRED . MECHANICAL IS EXISTING
 EXCEPT FOR REMOVAL OF TWO EXHAUST FANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-10 Cont ID  
Sent By lfranco Date 2010-12-10 Time 13:26 Rev Time 0.00
Received By lfranco Date 2010-12-10 Time 13:26 Sent To  
Notes
2010-12-10 13:30:00PLANNING AND ZONING: *** *ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****