Plan Review Details - Permit 10110375
Plan Review Stops For Permit 10110375
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-12-03 Cont ID  
Sent By rmcdouga Date 2010-12-03 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2010-12-03 Time 08:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-03 Cont ID  
Sent By rmcdouga Date 2010-12-03 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2010-12-03 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-15 Cont ID  
Sent By jwitmer Date 2010-11-15 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2010-11-15 Time 15:12 Sent To  
Notes
2010-11-15 15:13:07INCOMING SENT TO ZONING BOX. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-12-21 Cont ID  
Sent By rmcdouga Date 2010-12-21 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2010-12-21 Time 11:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-03 Cont ID  
Sent By rmcdouga Date 2010-12-03 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2010-12-03 Time 08:13 Sent To  
Notes
2010-12-03 08:28:25DENIED BY PLUMBING
  
 1) THE PLANS SPECIFY A 2 HP INTELLIFLO VARIABLE SPEED
 PUMP WHICH REQUIRES THE MAXIMUM FLOW RATE OF THE PUMP
 TO BE USED IN CALCULATIONS. THE PIPING SCHEMATIC SHOWS
 3" PIPE ON THE SPA SUCTION LINES AND THE MAIN DRAIN
 DETAIL SPECIFIES 2" BRANCH PIPING BETWEEN THE TWO MAIN
 DRAINS. PLEASE CLARIFY. THE SPA MAIN DRAIN BRANCH
 PIPING BETWEEN THE TWO MAIN DRAINS IS LIMITED TO A
 MAXIMUM OF 6 FEET PER SECOND WHEN ONE OF THE PAIR IS
 BLOCKED PER ANSI/APSP-7. MAXIMUM OUTLET SIZE ON THE
 MANUFACTURED MAIN DRAIN SUMPS IS TYPICALLY 2-1/2" AND
 IS CONSIDERED PART OF THE MAIN DRAIN BRANCH PIPING PER
 DEFINITION 3.5 OF ANSI/APSP-7 2006. THEREFORE, THE
 MAXIMUM BRANCH PIPING SIZE IS 2-1/2". UNLESS TDH
 CALCULATIONS ARE SUBMITTED THE MAXIMUM FLOW RATE OF THE
 PUMP WILL BE USED TO DETERMINE THE WATER VELOCITY.
 PLEASE SHOW HOW THE POOL PIPING WILL COMPLY WITH
 ANSI/APSP-7 SECTION 4.4 AND FBC R4101.6.3.
  
 2) SUBMIT 2 COPIES OF THE SPECIFICATIONS FOR THE POOL
 PUMP INCLUDING THE PUMP CURVE.
  
 3) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR THE SYSTEM OR DESIGN THE SYSTEM FOR
 THE MAXIMUM FLOW RATE OF THE PUMP.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2010-12-21 Cont ID  
Sent By rmcdouga Date 2010-12-21 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2010-12-14 Time 09:03 Sent To  
Notes
2010-12-21 11:54:06PASSED BY L FRANKO AT FIRST REVIEW. NO CHANGES IN
 LOCATIONS OF SPA OR EQUIPMENT FROM ORIGINAL REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2010-11-18 Cont ID  
Sent By lfranco Date 2010-11-18 Time 17:09 Rev Time 0.00
Received By lfranco Date 2010-11-16 Time 17:49 Sent To B
Notes
***NONE***