Plan Review Details - Permit 10110305
Plan Review Stops For Permit 10110305
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-10 Cont ID  
Sent By jwitmer Date 2011-02-10 Time 12:24 Rev Time 0.77
Received By jwitmer Date 2011-02-10 Time 12:24 Sent To  
Notes
2011-02-10 12:28:30BUILDING PLAN REVIEW
 PERMIT: 10110305
 ADD: 1009 BANYAN BLVD.
 CONT: TO BE DETERMINED
 TEL: (561)494-1046
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 FEB. 10/ 2011
 2ND REVIEW
  
 ACTION:PROVISO
 1-5) COMPLIED
  
 6) A PROPERLY LICENSED CONTRACTOR TO BE SIGNED ON
 BEFORE THE PERMIT ISSUANCE CAN TAKE PLACE, FL S 489.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-29 Cont ID  
Sent By jwitmer Date 2010-11-29 Time 13:33 Rev Time 1.55
Received By jwitmer Date 2010-11-29 Time 13:33 Sent To  
Notes
2010-11-29 13:46:27BUILDING PLAN REVIEW
 PERMIT: 10110305
 ADD: 1009 BANYAN BLVD.
 CONT: TO BE DETERMINED
 TEL: (561)494-1046
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
 1) PLANS INDICATE 3 NEW AQUA AMMONIA BULK STORAGE
 TANKS, PLEASE PROVIDE MANUFACTURERS SPEC SHEETS FOR
 THESE UNITS.
  
 2) AQUA AMMONIA IS CONSIDERED A H-4 OCCUPANCY,
 FBC-B415.7 PLEASE PROVIDE MSDS SHEETS.
  
 3) SHEET M-2 INDICATES THE USE OF NEW EXTERIOR WALL
 LOUVERS, PLEASE PROVIDE PRODUCT APPROVALS FOR LOUVERS.
 RULE 9B-72/
 RULE 9N-3 (31)(C)
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) THE PLANS DO NOT PROVIDE ANY WIND DESIGN CRITERIA
 FOR TTHE NEW EXTERIOR WALL LOUVERS:
 1609.6.2 WIND DESIGN PROCEDURES
 5.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 5.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 5.5 PROVIDE POSITIVE AND NEGATIVE PRESSURES FOR WALL
 LOUVERS.
  
 6) A PROPERLY LICENSED CONTRACTOR TO BE SIGNED ON
 BEFORE THE PERMIT ISSUANCE CAN TAKE PLACE, FL S 489.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-27 Cont ID  
Sent By rlecky Date 2010-12-27 Time 11:50 Rev Time 0.00
Received By rlecky Date 2010-12-27 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-02-15 Cont ID  
Sent By ddaniels Date 2011-02-15 Time 16:24 Rev Time 0.00
Received By ddaniels Date 2011-02-15 Time 16:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-13 Cont ID  
Sent By mcarsill Date 2010-12-13 Time 09:22 Rev Time 0.00
Received By mcarsill Date 2010-12-13 Time 09:09 Sent To  
Notes
2010-12-13 09:21:541009 BANYAN BOULEVARD
 PERMIT NUMBER 10110305
 AQUA AMMONIA CHEMICAL FEED AND STORAGE SYSTEM
  
  
 1. PLEASE PROVIDE MATERIAL SAFETY DATA SHEETS (MSDS)
 FOR THE TEMPORARY AND PERMANENT AQUA AMMONIA PRODUCT.
  
 2. PLEASE SUBMIT A HAZARDOUS MATERIALS MANAGEMENT PLAN
 (HMMP) TO THIS OFFICE FOR REVIEW.
  
 3. ALL DEMOLITION, RENOVATION, AND CONSTRUCTION SHALL
 COMPLY WITH NFPA 241.
  
 4. CARE IS TO BE TAKEN WHEN REMOVING THE AMMONIA TANKS
 AND ALL APPURTENANT EQUIPMENT AND ELECTRICAL SYSTEMS
 AND DEVICES DESCRIBED ON SHEET M-1.
  
 5. THE AQUA AMMONIA BULK AND DAY TANKS ARE TO BE
 PROPERLY LABELED WITH TANK CONTENTS AND QUANTITIES.
  
 6. IT WAS NOTED THAT CONTAINMENT CURBS ARE LOCATED
 DIRECTLY IN-FRONT OF DOORS USED FOR EXISTING.
  
 7. PLEASE INCLUDE "NO SMOKING SIGNS" FOR BUILDING.
  
 8. ALL AMMONIA IS TO BE STORED, HANDLED, AND USED IN
 ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL
 GUIDELINES.
  
 9. PLEASE INDICATE ALL SAFETY EQUIPMENT CONTAINED ON
 THE INSIDE AND OUTSIDE OF THE BUILDING.
  
 10. PLEASE INDICATE OCCUPANT LOADS FOR THE BUILDING.
  
 11. MORE DETAILS REQUIRED ON THE STORAGE VESSELS
 PLANNED FOR USE.
  
 12. PLEASE DESCRIBE EMERGENCY PROCEDURES.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-12-20 Cont ID  
Sent By fmittner Date 2010-12-20 Time 13:39 Rev Time 0.00
Received By fmittner Date 2010-12-20 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-04 Cont ID  
Sent By lmartine Date 2011-02-04 Time 08:51 Rev Time 0.00
Received By lmartine Date 2011-02-04 Time 08:51 Sent To  
Notes
2011-02-04 09:02:56C--8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-04 Cont ID  
Sent By lmartine Date 2010-12-27 Time 08:51 Rev Time 0.00
Received By lmartine Date 2010-11-10 Time 10:21 Sent To  
Notes
2010-11-10 10:21:50C22
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-11-22 Cont ID  
Sent By rregueir Date 2010-11-22 Time 15:28 Rev Time 0.00
Received By rregueir Date 2010-11-22 Time 15:26 Sent To  
Notes
2010-11-22 15:28:38PROCESS PIPING AND EQUIPMENT ON M PAGES NOT REVIEWED.
 PROPOSED LOUVERS SHALL BE INSTALLED PER PRODUCT
 APPROVAL DOCUMENTATION IN ACCORDANCE WITH FBC-M 1609
 AND FAC RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-02-09 Cont ID  
Sent By astelly Date 2011-02-09 Time 15:42 Rev Time 0.00
Received By astelly Date 2011-02-09 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By astelly Date 2010-12-17 Time 14:37 Rev Time 0.00
Received By astelly Date 2010-12-17 Time 14:37 Sent To HIST
Notes
2010-12-17 14:42:01AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SITE PLAN OR AERIAL SHOWING LOCATION
 OF PROPOSED WORK. ANY ALTERATIONS TO THE HISTORIC
 STRUCTURES ON THE SITE MUST BE APPROVED BY THE HISTORIC
 PRESERVATION DIVISION. ADDITIONALLY, ELEVATIONS SHOULD
 BE SUBMITTED THAT SHOW THE PROPOSED BUILDING
 ALTERATIONS.