Plan Review Details - Permit 10110288
Plan Review Stops For Permit 10110288
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-01-14 Cont ID  
Sent By rbrown Date 2011-01-14 Time 12:00 Rev Time 0.00
Received By rbrown Date 2011-01-14 Time 12:00 Sent To  
Notes
2011-01-14 12:01:28INITIAL PERMIT APPLICATION WAS SUBMITTED AS CONTRACTOR
 "TBD". PREVIOUS REVIEW WAS DEEMED CODE COMPLIANT AND
 JUST AWAITING A CONTRACTOR TO SUBMIT A PERMIT
 APPLICATION FORM. A LICENSED CONTRACTOR HAS NOW
 SUBMITTED A SIGNED PERMIT APPLICATION FORM FOR THIS
 SCOPE OF WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-01-11 Cont ID  
Sent By jwitmer Date 2011-01-11 Time 11:28 Rev Time 1.00
Received By jwitmer Date 2011-01-11 Time 11:28 Sent To  
Notes
2011-01-11 11:29:01PLANS ARE CODE COMPLIANT AND STAMPED , REQUIRES A
 PROPERLY LICENSED CONTRACTOR TO BE SIGNED ON NEED TO
 VERIFY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-23 Cont ID  
Sent By jwitmer Date 2010-11-23 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2010-11-23 Time 08:45 Sent To  
Notes
2010-11-23 08:46:32PLANS ARE CODE COMPLIANT AND STAMPED , REQUIRES A
 PROPERLY LICENSED CONTRACTOR TO BE SIGNED ON NEED TO
 VERIFY.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-08 Cont ID  
Sent By rlecky Date 2010-12-08 Time 11:29 Rev Time 0.00
Received By rlecky Date 2010-12-08 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-01-12 Cont ID  
Sent By wjolin Date 2011-01-12 Time 13:14 Rev Time 0.00
Received By wjolin Date 2011-01-12 Time 12:14 Sent To  
Notes
2011-01-12 13:05:28525 OKEECHOBEE BOULEVARD, SUITE #750
 PERMIT #10110288
 REVIEW COMMENTS - FIRE
  
 *****APPROVED WITH PROVISIOINS*****
  
 PROVIDE 90-MINUTE FIRE-RATED DOORS FOR OPENING
 PROTECTION IN NEW 2-HOUR FIRE-RATED WALL ASSEMBLY. THE
 DOORS AFFECTED ARE 701 AND 714. THE PROPOSED SPRINKLER
 WATER CURTAIN AT THE MAIN ENTRY PROVIDES ONLY A 1-HOUR
 SEPARATION EQUIVALENT AND IS ONLY APPLICABLE TO ATRIUM
 GLAZING CURTAIN WALLS. TYCO MODEL WS WINDOW SPRINKLERS
 ARE THE ONLY UL-LISTED SPRINKLERS THAT CAN PROVIDE AN
 EQUIVALENT TWO-HOUR FIRE SEPARATION; HOWEVER,THESE
 SPRINKLERS ARE ONLY LISTED TO PROTECT WINDOWS, NOT
 DOORS.
  
 THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 USES THE 2006 EDITION OF THE LIFE SAFETY CODE - NFPA
 101 WITH FLORIDA AMENDMENTS. THE COVER SHEET REFERENCES
 THE 2003 EDITION OF NFPA 101.
  
 CONSTRUCTION DOCUMENTS ARE NEEDED FOR THE MODIFICATION
 OF THE FIRE ALARM AND AUTOMATIC SPRINKLER SYSTEMS.
 ADDITIONALLY, SEPARATE PLANS AND PERMITS WILL BE NEEDED
 FOR THE FIRE ALARM AND SPRINKLER SYSTEM SHOP DRAWINGS.
  
 THE ACCESS-CONTROLLED EGRESS SYSTEM SHALL BE INTEGRATED
 WITH THE BUILDING FIRE ALARM SYSTEM AND FIRE SPRINKLER
 SYSTEM.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-01-06 Cont ID  
Sent By wjolin Date 2011-01-06 Time 10:49 Rev Time 0.00
Received By wjolin Date 2011-01-06 Time 09:36 Sent To  
Notes
2011-01-06 10:33:36525 OKEECHOBEE BOULEVARD, SUITE #750
 PERMIT #10110288
 REVIEW COMMENTS - FIRE
  
 REPEAT COMMENT: THE 2007 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE USES THE 2006 EDITION OF THE LIFE
 SAFETY CODE - NFPA 101 WITH FLORIDA AMENDMENTS. THE
 COVER SHEET REFERENCES THE 2003 EDITION OF NFPA 101.
  
 REPEAT COMMENT: TO OBTAIN A BUILDING PERMIT,
 CONSTRUCTION DOCUMENTS ARE NEEDED FOR THE MODIFICATION
 OF THE FIRE ALARM AND AUTOMATIC SPRINKLER SYSTEMS.
 ADDITIONALLY, SEPARATE PLANS AND PERMITS WILL BE NEEDED
 FOR THE FIRE ALARM AND SPRINKLER SYSTEM SHOP DRAWINGS.
  
 REPEAT COMMENT: THE ACCESS-CONTROLLED EGRESS SYSTEM
 SHALL BE INTEGRATED WITH THE BUILDING FIRE ALARM SYSTEM
 AND FIRE SPRINKLER SYSTEM.
  
 NEW COMMENT: PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 NOTE: THE CURRENT EXIT ACCESS CONFIGURATION CREATES A
 COMMON PATH OF TRAVEL GREATER THAN 100 FEET. THE TWO
 DOORS (701 & 714) FROM THE TENANT SUITE ARE STILL
 CONSIDERED EXIT ACCESS AND NOT EXIT.
  
 THE DESIGN TEAM HAS PROPOSED THE INSTALLATION OF A
 TWO-HOUR FIRE-RATED WALL SEPARATION BETWEEN TENANT
 SUITE #750 AND THE EXIT ACCESS CORRIDOR. THIS
 ALTERNATIVE METHOD IS SUBMITTED AS A REQUEST FOR
 EQUIVALENCY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-30 Cont ID  
Sent By wjolin Date 2010-11-30 Time 17:04 Rev Time 0.00
Received By wjolin Date 2010-11-30 Time 15:15 Sent To  
Notes
2010-11-30 17:04:14525 OKEECHOBEE BOULEVARD, SUITE #750
 PERMIT #10110288
 REVIEW COMMENTS - FIRE
  
 THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 USES THE 2006 EDITION OF THE LIFE SAFETY CODE - NFPA
 101 WITH FLORIDA AMENDMENTS. THE COVER SHEET REFERENCES
 THE 2003 EDITION OF NFPA 101.
  
 THE CURRENT EXIT ACCESS CONFIGURATION CREATES A COMMON
 PATH OF TRAVEL GREATER THAN 100 FEET. THE TWO DOORS
 (701 & 714) FROM THE TENANT SUITE ARE STILL CONSIDERED
 EXIT ACCESS AND NOT EXITS. OCCUPANTS EXITING THROUGH
 DOOR 714 WILL CONVERGE WITH THE OCCUPANTS EXITING
 THROUGH DOOR 701.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER LOCATIONS ON THE
 FLOOR PLAN.
  
 TO OBTAIN A BUILDING PERMIT, CONSTRUCTION DOCUMENTS ARE
 NEEDED FOR THE MODIFICATION OF THE FIRE ALARM AND
 AUTOMATIC SPRINKLER SYSTEMS. ADDITIONALLY, SEPARATE
 PLANS AND PERMITS WILL BE NEEDED FOR THE FIRE ALARM AND
 SPRINKLER SYSTEM SHOP DRAWINGS.
  
 THE COLUMNS AND FURNITURE LAYOUT CREATE AN AISLE THAT
 IS LESS THAN 36 INCHES IN WIDTH ON SHEET A-1.1.
  
 THE ACCESS-CONTROLLED EGRESS SYSTEM SHALL BE INTEGRATED
 WITH THE BUILDING FIRE ALARM AND FIRE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-01-12 Cont ID  
Sent By wjolin Date 2011-01-12 Time 12:14 Rev Time 0.00
Received By wjolin Date 2011-01-12 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-03 Cont ID  
Sent By lmartine Date 2011-01-03 Time 13:16 Rev Time 0.00
Received By lmartine Date 2011-01-03 Time 13:16 Sent To  
Notes
2011-01-03 13:17:01C--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-08 Cont ID  
Sent By rlecky Date 2010-12-08 Time 13:43 Rev Time 0.00
Received By rlecky Date 2010-11-10 Time 16:23 Sent To  
Notes
2010-11-10 16:23:31C16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-11-16 Cont ID  
Sent By hmoser Date 2010-11-16 Time 13:10 Rev Time 0.00
Received By hmoser Date 2010-11-16 Time 13:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-01-07 Cont ID  
Sent By lwagner Date 2011-01-07 Time 10:43 Rev Time 0.00
Received By lwagner Date 2011-01-06 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-11-16 Cont ID  
Sent By lwagner Date 2010-11-16 Time 08:52 Rev Time 0.00
Received By lwagner Date 2010-11-15 Time 13:23 Sent To  
Notes
2010-11-16 08:52:09FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. AAV SHOWN IS NOT WITHIN THE TOP 4 FLOOR BRANCH
 INTERVALS.
 917.3.1 LOCATION OF BRANCH. THE HORIZONTAL BRANCH DRAIN
 SHALL CONNECT TO THE DRAINAGE STACK OR BUILDING DRAIN A
 MAXIMUM OF FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK.
  
 2. DISH WASHER WILL REQUIRE A SHOCK ARRESTOR.
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-11-30 Cont ID  
Sent By eschneid Date 2010-11-30 Time 13:41 Rev Time 0.25
Received By eschneid Date 2010-11-30 Time 13:41 Sent To  
Notes
2010-11-30 13:42:08INTERIOR ONLY