Plan Review Details - Permit 10110256
Plan Review Stops For Permit 10110256
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-13 Cont ID  
Sent By jwitmer Date 2010-12-13 Time 14:55 Rev Time 0.45
Received By jwitmer Date 2010-12-13 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-23 Cont ID  
Sent By jwitmer Date 2010-11-23 Time 17:03 Rev Time 0.00
Received By jwitmer Date 2010-11-23 Time 17:03 Sent To  
Notes
2010-11-23 17:21:24BUILDING PLAN REVIEW
 PERMIT: 10110256
 ADD: 550 OKEECHOBEE BLVD SUITE: UPH23
 CONT: FORTUNE CONSTRUCTION CO.
 TEL: (786)457-1171
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE THEY ARE DRAWN TO 1/4" =1'-0" BUT ARE
 ALOT SMALLER THAN THAT. THE PLANS NEED TO BE LARGE
 ENOUGH SO THEY
 CAN BE SCANNED INTO OUR RECORD RETENTION PROGRAM. SHEET
 ID-2 THE DETAILS AT THE BOTTOM OF THE PAGE ARE
 ILLEGIBLE.
 106.1.3 * QUALITY OF PLANS.
  
 2) ID DRAWINGS ARE MISSING STATEMENT REQUIRED BY
 481.2131(1) 481.203 INTERIOR DESIGN DOCUMENTS PREPARED
 BY A REGISTERED INTERIOR DESIGNER SHALL CONTAIN A
 STATEMENT THAT THE DOCUMENT IS NOT AN ARCHITECTURAL OR
 ENGINEERING STUDY, DRAWING, SPECIFICATION, OR DESIGN
 AND IS NOT TO BE USED FOR CONSTRUCTION OF ANY
 LOAD-BEARING COLUMNS, LOAD-BEARING FRAMING OR WALLS OF
 STRUCTURES, OR ISSUANCE OF ANY BUILDING PERMIT, EXCEPT
 AS OTHERWISE PROVIDED BY LAW.
  
 3) ID-2.1 SOFFIT DETAILS ARE MISSING SIZE OF FRAMING
 MEMBERS, SPACING OF FRAMING MEMBERS AND TYPE OF
 ATTACHMENT SIZE OF PIN AND SPACING OF PINS TO THE
 CONCRETE DECK ABOVE. IT WOULD APPEAR THIS WOULD BE
 BEYOND THE SCOPE OF YOUR LICENSE SINCE THE SOFFIT
 WOULD BE CONSIDERED LOAD BEARING HAVING TO BE ATTACHED
 TO THE DECK ABOVE.
  
 4) SHEET ID-1 ALSO INDICATES NEW DOORS BUT NO MENTION
 OF DOOR SIZE IS PROVIDED NOR IS THE SIZE OF THE NEW
 CLOSET PROVIDED.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-12-13 Cont ID  
Sent By rlecky Date 2010-12-13 Time 08:04 Rev Time 0.00
Received By rlecky Date 2010-12-13 Time 07:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-02 Cont ID  
Sent By rlecky Date 2010-12-02 Time 14:45 Rev Time 0.00
Received By rlecky Date 2010-12-02 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 14:26 Rev Time 0.00
Received By wjolin Date 2010-12-16 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-23 Cont ID  
Sent By wjolin Date 2010-11-23 Time 12:15 Rev Time 0.00
Received By wjolin Date 2010-11-23 Time 10:51 Sent To  
Notes
2010-11-23 12:15:14550 OKEECHOBEE BOULEVARD, SUITE UP#23
 PERMIT #10110256
 REVIEW COMMENTS - FIRE
  
 DRAWINGS ID-1 AND ID-2 ARE NOT SCALABLE AT ONE-QUARTER
 INCH EQUALS ONE-FOOT.
  
 PLEASE CLARIFY THE TWO LOWER CEILING ARROWS POINTING TO
 DIFFERENT AREAS IN THE SAME ROOM ON DRAWING ID-2.
  
 PLEASE PROVIDE CEILING HEIGHTS, SOFFIT ELEVATIONS, AND
 LIGHT COVE DIMENSIONS.
  
 THE RELOCATION OF FIRE SPRINKLERS ON DRAWING ID-3
 RESULTS IN INADEQUATE COVERAGE PER NFPA 13.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR AUTOMATIC
 SPRINKLER SYSTEM MODIFICATIONS.
  
 NOTE: THE CURRENT DIMENSIONS AND LAYOUT OF THE NEW
 SOFFITS MAY PREVENT CODE COMPLIANT SPRINKLER COVERAGE.
 THE USE OF SIDEWALL SPRINKLERS IS GENERALLY LIMITED TO
 FLAT CEILINGS WITH LITTLE OR NO OBSTRUCTIONS (SOFFITS).
 THE SPRINKLERS NEED TO BE INSTALLED ACCORDING TO THEIR
 LISTING CRITERIA AND THE REQUIREMENTS OF NFPA 13.
 INSTALLATION EXAMPLES INCLUDE: SIDEWALL SPRINKLERS
 SHALL NOT PROJECT MORE THAN 6-INCHES FROM THE WALL ON
 WHICH THEY ARE MOUNTED; SIDEWALL SPRINKLERS SHALL BE
 INSTALLED NO CLOSER THAN 8-FEET FROM LIGHT FIXTURES OR
 SIMILAR OBSTRUCTIONS; WHERE SOFFITS EXCEED 8-INCHES IN
 WIDTH, PENDENT SPRINKLERS SHALL BE INSTALLED UNDER THE
 SOFFIT.
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 14:26 Rev Time 0.00
Received By wjolin Date 2010-12-10 Time 19:23 Sent To  
Notes
2010-12-10 19:23:54B12
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-02 Cont ID  
Sent By rlecky Date 2010-12-02 Time 14:57 Rev Time 0.00
Received By rlecky Date 2010-11-08 Time 14:22 Sent To  
Notes
2010-11-08 14:22:47SENT TO B12.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-12-10 Cont ID  
Sent By hmoser Date 2010-12-15 Time 09:11 Rev Time 0.00
Received By hmoser Date 2010-11-15 Time 13:51 Sent To  
Notes
2010-11-15 14:00:00NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 1 Status N Date 2010-11-22 Cont ID  
Sent By eschneid Date 2010-11-22 Time 11:41 Rev Time 0.25
Received By eschneid Date 2010-11-22 Time 11:41 Sent To  
Notes
2010-11-22 11:41:53INTERIOR WORK ONLY.