Plan Review Details - Permit 10110225
Plan Review Stops For Permit 10110225
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-15 Cont ID  
Sent By rmcdouga Date 2011-02-15 Time 12:31 Rev Time 0.00
Received By rmcdouga Date 2011-02-15 Time 12:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-02 Cont ID  
Sent By rmcdouga Date 2010-12-02 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2010-12-02 Time 08:42 Sent To  
Notes
2010-12-02 10:17:51DENIED BY BUILDING
  
 1) THE 8-1/2" X 11" SPA DRAWINGS FROM DOUGLAS W. BAUMAN
 P.E. ARE REQUIRED TO BE SIGNED AND SEALED PER FS 471.
  
 2) SHOW COMPLIANCE WITH FBC R301.2.1 THE POOL EQUIPMENT
 IS REQUIRED TO BE ANCHORED TO UPLIFT AND OVERTURNING IN
 A 140 MPH WIND SPEED.
  
 3) SHOW COMPLIANCE WITH FBC R4101.17 FOR SWIMMING POOL
 BARRIER REQUIREMENTS.
  
 4) THE VALVE FOR THE POOL AND SPA SPECIFIED ON THE
 APPLICATION IS TOO LOW. THE PERMIT VALUE IS BASED ON
 THE TOTAL COSTS INCLUDING ALL DESIGN COSTS, MATERIALS,
 LABOR, OVERHEAD AND PROFIT AS A CONTRACTOR WOULD CHARGE
 PER FBC 108.3. THE VALUE HAS BEEN CONSERVATIVELY
 INCREASED TO $ 15,000.00 BASED ON MARSHALL AND SWIFT
 PUBLISHED DATA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-15 Cont ID  
Sent By rmcdouga Date 2011-02-15 Time 12:32 Rev Time 0.00
Received By rmcdouga Date 2011-02-15 Time 12:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-12-01 Cont ID  
Sent By rmcdouga Date 2010-12-01 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2010-12-01 Time 15:39 Sent To  
Notes
2010-12-01 16:00:43DENIED BY ELECTRICAL
  
 1) THE ELECTRICAL DIAGRAM SHOWS TWO PUMP MOTORS AND THE
 PIPING DIAGRAM ONLY HAS ONE PUMP. PLEASE CLARIFY.
  
 2) THE ELECTRICAL DIAGRAM SHOWS AN ELECTRIC HEAT PUMP
 POOL HEATER. SUBMIT 2 COPIES OF THE SPECIFICATIONS FOR
 THIS HEATER.
  
 3) SPECIFY ON THE PLANS THAT A THERMAL COVER IS
 REQUIRED FOR HEATED SWIMMING POOLS AND SPAS PER
 13-612.AB.2.3.2 OF THE 2007 FLORIDA ENERGY CODE.
  
 4) SHOW COMPLIANCE WITH 13-612.AB.2.3.3 WHICH REQUIRES
 TIME CLOCKS ON PRIVATE POOL PUMPS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-15 Cont ID  
Sent By rmcdouga Date 2011-02-15 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2011-02-11 Time 16:30 Sent To  
Notes
2011-02-11 16:30:28TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-02 Cont ID  
Sent By rmcdouga Date 2010-12-02 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2010-11-05 Time 16:11 Sent To  
Notes
2010-11-05 16:12:37IN ZONING BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-15 Cont ID  
Sent By rmcdouga Date 2011-02-15 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2011-02-15 Time 12:40 Sent To  
Notes
2011-02-15 14:13:04THE BRANCH PIPING AT THE SPA MAIN DRAINS ARE REQUIRED
 TO BE 4 INCH.

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-02 Cont ID  
Sent By rmcdouga Date 2010-12-02 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2010-12-02 Time 06:39 Sent To  
Notes
2010-12-02 08:42:23DENIED BY PLUMBING
  
 1) THE PLUMBING PIPING SCHEMATIC DOES NOT SPECIFY THE
 SIZES OF ALL OF THE PIPING.
  
 2) THE PIPING SCHEMATIC SPECIFIES A 32" CHANNEL DRAIN
 FOR THE POOL AND THE LONGITUDINAL POOL SECTION
 SPECIFIES 2 MAIN DRAINS 3 FEET APART. PLEASE CLARIFY.
  
 3) THE PLANS SPECIFY A VARIABLE SPEED PUMP WHICH
 REQUIRES THE MAXIMUM FLOW RATE OF THE PUMP TO BE USED
 IN CALCULATIONS. THE PUMP CURVE ON THE PLAN SHOWS THIS
 AS 140 GPM. THE PIPING SCHEMATIC SHOWS 3" PIPE ON THE
 SPA SUCTION LINES AND THE 8-1/2" X 11" SPA PLANS
 ATTACHED TO THE LARGE PLANS SPECIFIES 2" PIPING. PLEASE
 CLARIFY. THE SPA MAIN DRAIN BRANCH PIPING BETWEEN THE
 TWO MAIN DRAINS IS LIMITED TO A MAXIMUM OF 6 FEET PER
 SECOND WHEN ONE OF THE PAIR IS BLOCKED PER ANSI/APSP-7.
 AT A 140 GPM FLOW RATE THE VELOCITY IN 3" PIPE IS 6.35
 FEET PER SECOND. MAXIMUM OUTLET SIZE ON THE
 MANUFACTURED MAIN DRAIN SUMP LITERATURE THAT WAS
 SUBMITTED IS 2-1/2" AND IS CONSIDERED PART OF THE MAIN
 DRAIN BRANCH PIPING PER DEFINITION 3.5 OF ANSI/APSP-7
 2006. THEREFORE, THE MAXIMUM BRANCH PIPING SIZE IS
 2-1/2". AT 140 GPM THE WATER VELOCITY IN 2-1/2" PIPE
 9.15 FEET PER SECOND. UNLESS TDH CALCULATIONS ARE
 SUBMITTED THE MAXIMUM FLOW RATE OF THE PUMP WILL BE
 USED TO DETERMINE THE WATER VELOCITY. PLEASE SHOW HOW
 THE POOL PIPING WILL COMPLY WITH ANSI/APSP-7 SECTION
 4.4 AND FBC R4101.6.3.
  
 4) SPECIFY THE TURNOVER RATE FOR THE POOL ON THE PLANS
 AS REQUIRED BY FBC R4101.20.
  
 5) SPECIFY THE TOTAL WATER CAPACITY OF THE POOL AND SPA
 IN GALLONS ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-02-14 Cont ID  
Sent By jroach Date 2011-02-14 Time 16:21 Rev Time 0.00
Received By jroach Date 2011-02-14 Time 15:45 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-11-19 Cont ID  
Sent By jroach Date 2010-11-19 Time 14:38 Rev Time 0.00
Received By jroach Date 2010-11-10 Time 16:08 Sent To E
Notes
2010-11-19 14:38:14ZONING PLAN REVIEW
  
 DATE OF REVIEW: 11/19/10
 PERMIT NO.: 10110225
 ADDRESS: 415 AVENIDA ALEGRE
 CONTRACTOR/CONTACT: MARIO CASTANO
 TELEPHONE NO.: 561.633.2475
 SCOPE OF REVIEW: SWIMMING POOL AND FIBER GLASS SPA
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) SITE PLAN AND SURVEY SHALL PROVIDE THE PROPOSED
 DIMENSIONS FROM THE WATER'S EDGE TO ALL ADJACENT
 PROPERTY LINES.
  
 2) SITE PLAN AND SURVEY SHALL PROVIDE THE PROPOSED
 DIMENSIONS FROM THE POOL EQUIPMENT TO ALL ADJACENT
 PROPERTY LINES.
  
 3) PURSUANT TO SECTION 94-304(D)(2)(1)(B) OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS, EVERY SWIMMING
 POOL SHALL BE ENCLOSED BY A PERMANENT FENCE WHICH IS
 INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN THE
 OWNERS OR OCCUPANTS OF THE RESIDENCE. SUCH FENCE SHALL
 BE A MINIMUM OF FOUR (4) FEET IN HEIGHT ABOVE GRADE.
 THE SURVEY PROVIDED DOES NOT INDICATE ANY EXISTING
 FENCE. IF AN EXISTING FENCE IS PRESENT, THEN THE SURVEY
 SHALL INDICATE SUCH...IF NO FENCE EXISTS, THEN A
 PERMANENT FENCE THAT IS IN COMPLIANCE WITH THE
 REQUIREMENTS PROVIDED ABOVE SHALL BE PROVIDED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved