Plan Review Details - Permit 10110181
Plan Review Stops For Permit 10110181
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-08 Cont ID  
Sent By jwitmer Date 2011-06-08 Time 15:15 Rev Time 0.77
Received By jwitmer Date 2011-06-08 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-23 Cont ID  
Sent By jwitmer Date 2010-11-23 Time 07:38 Rev Time 0.77
Received By jwitmer Date 2010-11-23 Time 07:34 Sent To  
Notes
2010-11-23 07:52:53BUILDING PLAN REVIEW
 PERMIT: 10110181
 ADD: 1920 WEKIVA WAY
 CONT: J CROMPTON ELECTRIC, INC.
 TEL: (561)588-6559
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET T1 INDICATES THE WIND DESIGN CRITERIA AS A
 NORMAL DESIGN 3 SECOND GUST WIND VELOCITY 140 MPH. THE
 PLANS ARE LACKING THE WIND DESIGN CRITERIA AS TO:
  
 1609.6.2 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. PLEASE NOTE THIS IS A "C"
 EXPOSURE.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1.5) DESIGNED AS OPEN, SEMI- ENCLOSED OR ENCLOSED.
  
 1.6 PRESSURES FOR DOOR OPENINGS.
  
 2) PLEASE PROVIDE THE LOCATION AND TYPE OF ANCHORS TO
 BE INSTALLED TO COUNTER THE MOMENT OF OVERTURNING AND
 SLIPPAGE, FBC-B 1604.4.
  
 3) MISSING PRODUCT APPROVALS FOR DOOR OPENINGS,
 REQUIRED BY RULE 9B-72.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-24 Cont ID  
Sent By jleahy Date 2010-12-23 Time 19:05 Rev Time 0.00
Received By jleahy Date 2010-12-23 Time 19:05 Sent To  
Notes
2010-12-24 19:23:28PLAN PASSED
  
 NEEDED BEFORE FIRST ROUGH INSPECTION
  
 DETAIL OF THE GROUNDING AT THE GENERATOR AND TRANSFER
 SWITCH 250.32 B,D
  
 DETAIL OF THE GROUNDING AT THE EXISTING BUILDING 250.32
 B,D
  
 THIS IS NOT NEEDED FOR UNDERGROUND PIPE INSPECTIONS
  
 QUESTIONS 561-644-7291 JAKE LEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-05-27 Cont ID  
Sent By wjolin Date 2011-05-27 Time 12:45 Rev Time 0.00
Received By wjolin Date 2011-05-27 Time 11:16 Sent To  
Notes
2011-05-27 12:45:381920 WEKIVA WAY
 PERMIT #10110181
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 PER NFPA 1 (FLORIDA EDITION) CHAPTER 66 SECTION
 66.2.3.2.3: MEANS TO CONTROL SPILLS FROM ABOVEGROUND
 STORAGE TANKS SHALL BE PROVIDED IN ACCORDANCE NFPA 30.
 SUBMIT INFORMATION DETAILING HOW SPILL CONTROL WILL BE
 ACHIEVED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-17 Cont ID  
Sent By mcarsill Date 2010-11-17 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2010-11-17 Time 10:44 Sent To  
Notes
2010-11-17 10:49:501920 WEKIVA WAY
 PERMIT NUMBER 10110181
 GENERATOR INSTALLATION
  
 1. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 2. ENTIRE GENERATOR INSTALLATION TO COMPLY WITH NFPA
 110.
  
 3. PLANS DO NOT CONTAIN ANY STAMPS FROM THE DEPARTMENT
 OF ENVIRONMENTAL RESOURCE MANAGEMENT (DERM).
  
 4. PLEASE PROVIDE AN APPROVED SURVEY OF THE PROPOSED
 PROPERTY WHERE THE GENERATOR IS TO BE INSTALLED.
  
 5. APPROPRIATE SIGNAGE IS REQUIRED TO BE ON THE PLANS.
 THIS SIGNAGE SHALL INCLUDE THE NFPA 704 DIAMONDS, "NO
 SMOKING" SIGNS, PRODUCT NAME AND QUANTITY OF THE DIESEL
 FUEL.
  
 6. PLEASE INDICATE ON THE PLANS WHAT EQUIPMENT THE
 GENERATOR IS EXPECTED TO RUN. IS IT LIFE SAFETY
 EQUIPMENT ONLY OR GENERAL LOADS OR BOTH AND PLEASE
 INDICATE DURATION.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2011-06-21 Cont ID  
Sent By rregueir Date 2011-06-21 Time 11:07 Rev Time 0.00
Received By rregueir Date 2011-06-21 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2011-06-21 Time   Rev Time 0.00
Received By shill Date 2011-05-17 Time 12:24 Sent To  
Notes
2011-05-20 13:36:345/19/11 SUBMITTAL FOR IRRAGATION AND LANDSCAPING.
2011-05-17 12:30:58C14
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-27 Cont ID  
Sent By lmartine Date 2010-12-23 Time 16:38 Rev Time 0.00
Received By lmartine Date 2010-11-05 Time 14:17 Sent To  
Notes
2010-11-05 14:27:30C--14

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-05-20 Cont ID  
Sent By rkussner Date 2011-05-20 Time 16:03 Rev Time 0.00
Received By rkussner Date 2011-05-20 Time 16:03 Sent To  
Notes
2011-05-20 16:05:52***LANDSCAPE NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #11050583 FOR LANDSCAPE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-12-20 Cont ID  
Sent By rkussner Date 2010-12-20 Time 16:35 Rev Time 0.00
Received By rkussner Date 2010-12-20 Time 16:35 Sent To  
Notes
2010-12-20 16:46:53***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT FOR THE
 REQUIRED LANDSCAPING FOR THIS PROJECT. TWO (2) COPIES
 OF A LANDSCAPE PLAN WILL BE REQUIRED WITH THE
 APPLICATION.
  
 2. AN IRRIGATION PERMIT WILL BE REQUIRED.
  
 3 PURSUANT TO SECTION 94-444 (B), WALLS INSTALLED FOR
 SCREENING OF EQUIPMENT SHALL BE LANDSCAPED WITH SHRUBS
 AND HEDGES PLANTED AT TWO-FOOT INTERVALS. BECAUSE THIS
 WALL WILL BE NINE (9) FEET IN HEIGHT, THE PLANT
 MATERIAL SHALL BE TALL ENOUGH AT PLANTING TO ADEQUATELY
 SCREEN THE WALL. IF THE PLANT MATERIAL IS LARGER, THE
 SPACING BETWEEN PLANTS CAN BE EXPANDED BEYOND THE 24
 INCHES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-06-21 Cont ID  
Sent By rregueir Date 2011-06-21 Time 11:07 Rev Time 0.00
Received By rregueir Date 2011-06-21 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-11-17 Cont ID  
Sent By hmoser Date 2010-11-16 Time 12:13 Rev Time 0.00
Received By hmoser Date 2010-11-16 Time 10:49 Sent To  
Notes
2010-11-16 12:17:52PLANS MUST BE SUBMITTED TO DERM.
 PLANREVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 2 Status P Date 2011-06-08 Cont ID  
Sent By lfranco Date 2011-06-08 Time 18:45 Rev Time 0.00
Received By lfranco Date 2011-06-08 Time 18:30 Sent To  
Notes
2011-06-08 18:48:30PLANNING AND ZONING: ***** PASSED WITH PROVISO: COMPLY
 WITH LANDSCAPING PERMIT COMMENTS PRIOR TO FINAL
 APPROVAL BY ZONING. ****
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-21 Cont ID  
Sent By lfranco Date 2010-12-10 Time 18:42 Rev Time 0.00
Received By lfranco Date 2010-12-10 Time 13:48 Sent To  
Notes
2010-12-10 13:53:13PLANNING AND ZONING: ***** FAILED****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. A MINOR AMENDMENT TO THE INFORMAL SITE PLAN REVIEW
 APPROVAL ("ISPR 05-09") IS REQUIRED. AN APPLICATION
 WILL NEED TO BE FILED TO THE PLANNING AND ZONING
 DEPARTMENT AND APPROVED PRIOR TO SIGN-OFF OF BUILDING
 PERMIT. YOU CAN DOWNLOAD AN APPLICATION AT THE LINK
 BELOW:
  
 HTTP://WWW.WPB.ORG/PLAN/INDEX.PHP?PAGE=PB, SCROLL TO
 THE MIDDLE OF THE PAGE AND DOWNLOAD THE DEVELOPMENT
 APPLICATION (SEE PAGE 2, SITE PLAN AMENDMENT (MINOR -
 LEVEL 1) FOR APPLICATION REQUIREMENTS.
  
 THE COMMENTS BELOW REFLECT THE INFORMATION NEEDED ON
 SITE PLAN, PRIOR TO SUBMITTAL OF THE MINOR AMENDMENT TO
 THE ISPR 05-09.
  
 3. ON SHEET C4, "GENERATOR COMPOUND CROSS SECTION,"
 INCLUDE THE GENERATOR PROFILE WITHIN THE ENCLOSURE TO
 ASSURE THAT THE ENTIRE GENERATOR WILL BE SCREENED. ALSO
 SHOW DETAIL OF LANDSCAPING AND CURBING WITH THE CROSS
 SECTION.
  
 THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/HEDGES AROUND
 GENERATOR/ FUEL TANK, AND SETBACK DISTANCE FROM
 PROPERTY LINES.
  
 B. SHOW AMENDED SITE DATA TABLE THAT DEPICTS THE TOTAL
 PARKING SPACES THAT WERE REQUIRED/PROVIDED AND INCLUDE
 THE DELETION (MINUS) OF THE PARKING SPACES THAT WILL BE
 TAKEN UP BY THE NEW GENERATOR. A TERMINAL LANDSCAPE
 ISLAND WILL BE REQUIRED ON BOTH SIDES OF THE GENERATOR
 ENCLOSURE, SO ADDITIONAL PARKING WILL BE TAKEN UP.
 THERE SEEMS TO BE EXCESS PARKING FROM THE APPROVED
 PLANS, BUT THE REVISIONS SHOWING WHAT WAS REQUIRED AND
 PROVIDED NEED TO ALSO BE SHOWN. A COPY OF THE APPROVED
 PLANS CAN BE PROVIDED AT YOUR REQUEST FOR REFERENCE.
  
 NOTE: IS IT POSSIBLE TO MOVE THE GENERATOR OUT OF THE
 GENERAL PARKING AREA TO A MORE CONSPICUOUS AREA SUCH AS
 THE SOUTHEASTERN CORNER OF THE PROPERTY (WHERE THERE
 ARE SIX (6) PARKING SPACES)? THERE ARE TWO EXISTING
 LANDSCAPE TERMINAL ISLANDS IN PLACE THAT CAN
 ACCOMMODATE THE PROPOSED GENERATOR WITH LESS
 CURBING/LANDSCAPING ISLANDS REQUIRED.
  
 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL TANK AND ROOFTOP
 EXHAUST.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  