Plan Review Details - Permit 10110108
Plan Review Stops For Permit 10110108
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-11-18 Cont ID  
Sent By shill Date 2010-11-18 Time 08:41 Rev Time 0.00
Received By shill Date 2010-11-17 Time 16:15 Sent To  
Notes
2010-11-18 08:41:58PROVISO
 (PLAN REVIEW IN PROCESS)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-09 Cont ID  
Sent By shill Date 2010-11-09 Time 18:04 Rev Time 0.00
Received By shill Date 2010-11-09 Time 18:04 Sent To  
Notes
2010-11-09 18:14:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE REVISE PLAN TO STATE BUILDING TYPE, FBC
 CHAPTER 6. SHEET A1 SHOWS A WOOD NAILER ABOVE THE
 CEILING; ARE COMBUSTIBLES PERMITTED IN THIS MANNER?
  
 2. FBC 435.5.1, ROOM 103, NO SHIELDING SHOWN ON
 CORRIDOR OR TENANT SEPARATION WALLS OR THE DOOR BETWEEN
 THE CORRIDOR AND X-RAY ROOM. THIS METHOD OF RADIATION
 PROTECTION IS TO BE APPROVED WITH THE FLORIDA
 DEPARTMENT OF HEALTH (BASED ON DISTANCE, RADIATION
 PRODUCED, ETC.) PRIOR TO PERMIT ISSUANCE. WILL FILM
 ALSO BE PROCESSED IN THIS ROOM? SEE FBC435.5.2.
  
 3. FBC 435.5.3, REVISE PLAN TO INCLUDE ALL REQUIRED
 INFORMATION AND SUBMIT TO DOH. PLEASE CONTACT THOMAS H.
 TOMCZAK, 904-278-5730, [email protected]
 FOR MORE INFORMATION.
  
 4. PROVIDE INFORMATION REGARDING EXISTING OR PROPOSED
 NEW ACCESSIBLE ELEMENTS PER FBC11-4.1.6(2) SUCH AS:
 ACCESSIBLE ENTRANCE
 ROOM 103, SHOW MANEUVERING CLEARANCE FOR DOOR, PULL
 SIDE FBC 11 FIGURE 25
 ACCESSIBLE DRINKING FOUNTAIN
  
 PROVIDE COST BREAKDOWN IF NECESSARY.
  
 5. PROVIDE INFORMATION REGARDING PROPOSED NEW HARDWARE,
 FBC11-4.13.9.
  
 6. PROVIDE MORE INFORMATION REGARDING PROPOSED USE OF
 CONFERENCE ROOM AND SINK. EITHER REVISE PLAN TO SHOW
 USE AS A WORK AREA OR PROVIDE A DETAIL TO COMPLY WITH
 FBC11-4.24.
  
 7. AFTER DOH APPROVAL, AND DISCUSSION WITH DESIGNER OF
 RECORD, THIS REVIEW CAN BE ISSUED WITH PROVISO.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-11-08 Cont ID  
Sent By jdickins Date 2010-11-08 Time 18:09 Rev Time 0.00
Received By jdickins Date 2010-11-08 Time 18:09 Sent To  
Notes
2010-11-08 18:10:18OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-17 Cont ID  
Sent By mcarsill Date 2010-11-17 Time 11:05 Rev Time 0.00
Received By mcarsill Date 2010-11-17 Time 11:03 Sent To  
Notes
2010-11-17 11:05:26ON NOVEMBER 17, 2010, THIS WRITER RECEIVED ELECTRONIC
 MAIL PLAN REVIEW COMMENTS ADDRESSING THE FIRE RESCUE
 COMMENTS.
  
 THE PLAN WILL BE APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-17 Cont ID  
Sent By mcarsill Date 2010-11-17 Time 07:40 Rev Time 0.00
Received By mcarsill Date 2010-11-17 Time 07:31 Sent To  
Notes
2010-11-17 07:40:094700 NORTH CONGRESS AVENUE, SUITE 100
 PERMIT NUMBER 10110108
  
 1. WRONG CODES LISTED ON SHEET E-1. WRONG EDITIONS OF
 THE FLORIDA BUILDING CODE AND THE FLORIDA FIRE
 PREVENTION CODE. SHOULD READ 2007 EDITIONS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 4. DOORS LOCATED IN EXISTING FIRE WALLS ARE TO BE FIRE
 RATED. NO DOOR SCHEDULE PROVIDED.
  
 5. EXITING APPEARS TO BE OCCURING THROUGH THE CONFERNCE
 ROOM. THERE DOES NOT APPEAR TO BE ENOUGH WIDTH AFTER
 SCALING THE AREA BETWEEN THE TABLE AND OTHER FURNITURE.
  
 6. ON SHEET A-2 SOME AREAS ARE NOT COVERED BY FIRE
 SPRINKLERS. THEY INCLUDE HALL 120, EXISTING TOILET 106,
 UTILITY 109, CLOSET 110, AND EXISTING TOLIET 118.
 PLEASE REVIEW THESE AREAS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-18 Cont ID  
Sent By shill Date 2010-11-18 Time 08:44 Rev Time 0.00
Received By shill Date 2010-11-05 Time 08:29 Sent To  
Notes
2010-11-05 09:21:24***************EXPEDITED****************
 B--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-11-09 Cont ID  
Sent By shill Date 2010-11-09 Time 18:04 Rev Time 0.00
Received By shill Date 2010-11-09 Time 18:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2010-11-18 Cont ID  
Sent By shill Date 2010-11-18 Time 08:41 Rev Time 0.00
Received By shill Date 2010-11-18 Time 08:41 Sent To  
Notes
2010-11-18 08:41:32VOIDED MECHANICAL APPLICATION, NO MECH WORK IN SCOPE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-11-15 Cont ID  
Sent By hmoser Date 2010-11-15 Time 11:04 Rev Time 0.00
Received By hmoser Date 2010-11-15 Time 11:04 Sent To  
Notes
2010-11-15 11:07:49NO MECHANICAL PLANS SUBMITTED .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-11-15 Cont ID  
Sent By lwagner Date 2010-11-15 Time 09:16 Rev Time 0.00
Received By lwagner Date 2010-11-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-11-10 Cont ID  
Sent By astelly Date 2010-11-10 Time 12:05 Rev Time 0.00
Received By astelly Date 2010-11-10 Time 12:05 Sent To  
Notes
***NONE***