Plan Review Details - Permit 10100695
Plan Review Stops For Permit 10100695
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By jdickins Date 2010-11-08 Time 14:07 Rev Time 0.00
Received By jdickins Date 2010-11-08 Time 14:07 Sent To  
Notes
2010-11-08 14:07:42OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-10-28 Cont ID  
Sent By jdickins Date 2010-10-28 Time 18:47 Rev Time 0.00
Received By jdickins Date 2010-10-28 Time 18:47 Sent To  
Notes
2010-10-28 18:53:51ELECT PLAN REVIEWE FAIL
 1)RISER DIAGRAM REQUIRED TO BE SIGNED BY DESIGNER
 2) SUMMIT ELECT SITE PLAN SHOWING MAIN SERVICE LOCATION
 AND A/C COMPRESSOR LOCATION
 3) SHOW WHERE SERVICE FEED FROM FPL IS RUNNING ON SITE
 SURVEY
 JOHN DICKINSON CELL 561-718-3230

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-01 Cont ID  
Sent By shill Date 2010-11-01 Time 08:27 Rev Time 0.00
Received By shill Date 2010-10-28 Time 16:29 Sent To  
Notes
2010-10-28 16:29:38UNDER 5 K ELECTRIC