Plan Review Details - Permit 10100582
Plan Review Stops For Permit 10100582
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-11-01 Cont ID  
Sent By jwitmer Date 2010-11-01 Time 14:16 Rev Time 1.33
Received By jwitmer Date 2010-11-01 Time 14:16 Sent To FIRE
Notes
2010-11-01 14:18:17PLANS APPEAR TO BE CODE COMPLIANT, A LICENSED
 CONTRACTOR TO BE SIGNED ON BEFORE A PASSED CAN OCCUR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-11-09 Cont ID  
Sent By mcarsill Date 2010-11-09 Time 07:34 Rev Time 0.00
Received By mcarsill Date 2010-11-09 Time 07:25 Sent To  
Notes
2010-11-09 07:34:476600-45TH STREET
 PERMIT NUMBER 10100582
 NEW BULK STORAGE TANK FOR SULFURIC ACID
  
  
 1. THE INSTALLATION FOR THE STORAGE, HANDLING, AND USE
 SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE
 (NFPA 1) CHAPTER 60 HAZARDOUS MATERIALS.
  
 2. NO SMOKING IS PERMITTED WITHIN 25 FEET OF THE
 OUTDOOR STORAGE AREA. APPROPRIATE SIGNAGE IS TO BE
 PROVIDED REGARDING THE NO SMOKING REQUIREMENTS OF
 CHAPTER 60.
  
 3. HAZARD IDENTIFICATION SIGNAGE (NFPA 704) SHALL BE
 PROVIDED FOR THE BULK STORAGE SULFURIC ACID STORAGE
 TANK.
  
 4. INCOMPATIBLE MATERIALS ARE TO BE KEPT AWAY FROM THE
 SULFURIC ACID PRODUCT.
  
 5. ALL UNNECESSARY COMBUSTIBLE MATERIALS ARE TO BE KEPT
 AWAY FROM THE BULK STORAGE AREA OF THE SULFURIC ACID.
  
 6. THE HAZARDOUS MATERIALS MANAGEMENT PLAN (HMMP) SHALL
 BE REVIEWED PERIODICALLY TO ENSURE CORRECTNESS.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-09 Cont ID  
Sent By mcarsill Date 2010-11-09 Time 07:38 Rev Time 0.00
Received By mcarsill Date 2010-10-22 Time 16:58 Sent To  
Notes
2010-10-22 16:58:20GAVE TO JIM