| 2010-10-22 12:24:24 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. THE LETTER REQUESTING A FEE REDUCTION AND THE |
| | ESTIMATE PROVIDED MAKE REFERENCE TO AWNINGS INSTALLED |
| | AT 368 CRANESNEST. PROVIDE A COST BREAKDOWN AND THE |
| | PERMIT NUMBER FOR THE PERMITTED AWNINGS REFERRED TO IN |
| | THE LETTER. I WAS UNABLE TO LOCATE AN AWNING PERMIT FOR |
| | 368 CRANESNEST. VALUE OF IMPROVEMENT IS NEEDED TO |
| | DETERMINE PERMIT FEES. |
| | |
| | 2. PROVIDE AN ELEVATION WHICH SHOWS HEIGHT OF |
| | INSTALLATION AND HEIGHT AT LOWEST PART OF AWNING, |
| | FBC3105.1. |
| | |
| | 3. PROVIDE DOCUMENTATION TO SHOW THAT THE FABRIC |
| | PROPOSED COMPLIES WITH FBC3105.3, NFPA701. |
| | |
| | 4. PROVIDE A STRUCTURAL DETAIL WHICH SHOWS COMPLIANCE |
| | WITH FBC3105.4, WIND RESISTANCE. |
| | |
| | 5. IF FABRIC IS TO BE RETRACTED IN THE ANTICIPATION OF |
| | HIGH WINDS, PROVIDE A LETTER, OR CONTRACTORS FORM, |
| | SIGNED BY THE OWNER (NOT THE TENANT) TO ACKNOWLEDGE |
| | THEIR RESPONSIBILITY TO HAVE THE AWNING COVER |
| | REMOVED/RETRACTED PRIOR TO ANY WIND EVENT WITH |
| | PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE |
| | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT |
| | BE NOTARIZED. |
| | |
| | 6. REVISE THE SITE PLAN TO SHOW PROPOSED AWNING SIZES. |
| | |
| | 7. REGARDING THE LETTER REQUESTING A FEE REDUCTION, |
| | THIS HAS BEEN DENIED BY THE BUILDING OFFICIAL DUE TO |
| | THE REQUIREMENT OF FBC 108.4, CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC AS A LICENSED CONTRACTOR |
| | PERFORMED THE WORK. |
| | |
| | |