| Plan Review Stops For Permit 10100399 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2010-11-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-11-10 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-11-10 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2010-11-10 13:08:44 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | | | | | | | 1. DESIGN PRESSURES TO BE SPECIFIED BY A DESIGN | | | PROFESSIONAL, FS471, FBC1609, ASCE7-05. | | | | | | A LETTER WAS SUBMITTED WHICH STATED THAT THE ATTACHED | | | DOORS MEET OR EXCEED PRESSURES FOR ZONE 5. PLEASE | | | REVISE THE LETTER TO SPECIFY THE PRODUCT REVIEWED BY | | | THE ENGINEER AS NOTHING WAS ATTACHED TO THE LETTER. IF | | | ENGINEER PRFERS TO SPECIFY PRODUCTS IN LIEU OF | | | SPECIFYING DESIGN PRESSURES, A REFERENCE TO PRODUCT | | | APPROVAL NUMBER (AND SPECIFIC PRODUCT WITHIN THE | | | PRODUCT APPROVAL) IS REQUIRED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2010-11-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-11-04 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-11-04 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2010-11-04 08:17:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | | | 1. DESIGN PRESSURES TO BE SPECIFIED BY A DESIGN | | | PROFESSIONAL, FS471, FBC1609, ASCE7-05. | | | | | | A LETTER WAS SUBMITTED WHICH STATED THAT THE ATTACHED | | | DOORS MEET OR EXCEED PRESSURES FOR ZONE 5. PLEASE | | | REVISE THE LETTER TO SPECIFY THE PRODUCT REVIEWED BY | | | THE ENGINEER AS NOTHING WAS ATTACHED TO THE LETTER. IF | | | ENGINEER PRFERS TO SPECIFY PRODUCTS IN LIEU OF | | | SPECIFYING DESIGN PRESSURES, A REFERENCE TO PRODUCT | | | APPROVAL NUMBER (AND SPECIFIC PRODUCT WITHIN THE | | | PRODUCT APPROVAL) IS REQUIRED. | | | | | | 2. PROVIDE A PLAN SHOWING DOOR LOCATION. THE DESIGN | | | PROFESSIONAL IS TO DETERMINE WHETHER DOORS ARE LOCATED | | | IN ZONE 4 OR ZONE 5. | | | | | | NO PLAN PROVIDED. SEE ALSO FIRE COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-10-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-10-20 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-10-20 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2010-10-20 07:33:57 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. DESIGN PRESSURES TO BE SPECIFIED BY A DESIGN | | | PROFESSIONAL, FS471, FBC1609, ASCE7-05. | | | | | | 2. PROVIDE A PLAN SHOWING DOOR LOCATION. THE DESIGN | | | PROFESSIONAL IS TO DETERMINE WHETHER DOORS ARE LOCATED | | | IN ZONE 4 OR ZONE 5. | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-11-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-11-10 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-11-10 |
Time |
12:32 |
Sent To |
B |
|
| Notes |
| 2010-11-10 12:33:30 | 525 SOUTH FLAGLER DRIVE | | | PERMIT #10100399 | | | | | | PER CONVERSATION WITH CHRIS OF CAMBRIDGE CONSTRUCTION, | | | FIRE DOORS WILL HAVE A UL LISTED 2-HOUR FIRE RATING. WJ |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-11-04 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-11-04 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-11-04 |
Time |
10:15 |
Sent To |
B |
|
| Notes |
| 2010-11-04 10:29:42 | 525 SOUTH FLAGLER DRIVE | | | PERMIT #10100399 | | | | | | REVIEW COMMENTS: FIRE | | | | | | 1) PROVIDE FLOOR PLAN INDICATING WHICH DOORS WILL BE | | | REPLACED. | | | | | | 2) PROVIDE DOOR CLOSERS AND LISTED FIRE EXIT HARDWARE | | | FOR RATED DOORS. | | | | | | 3) PROVIDE DIRECTION OF DOOR SWING OF ALL EXIT DOORS. | | | | | | 4) PROVIDE UL FIRE RESISTANCE RATING OF PROPOSED DOORS. | | | APPLICATION STATES DOORS BE RATED AT 90- MINUTES. | | | | | | 5) TRANSOM OR WINDOWS ARE REQUIRED TO BE FIRE RATED ON | | | FIRE RATED DOORS. | | | | | | 6) IF ELECTRIC HARDWARE OR CONTROLED ACCESS IS INTENDED | | | TO BE USED PLEASE PROVIDE THIS INFORMATION. | | | | | | WJOLIN, DDANIELS | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | 561 805-6730 | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-11-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-11-05 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-11-05 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2010-11-05 15:42:02 | IN FIRE BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-11-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-11-04 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-11-03 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2010-11-03 08:51:08 | TO SH DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-10-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-10-20 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-10-18 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2010-10-18 15:06:06 | *******************EXPEDITED****************** | | | GAVE TO SAMANTHA |
|
|