Plan Review Details - Permit 10100266
Plan Review Stops For Permit 10100266
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-10 Cont ID  
Sent By jwitmer Date 2011-02-10 Time 11:33 Rev Time 0.22
Received By jwitmer Date 2011-02-10 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-10-29 Cont ID  
Sent By jwitmer Date 2010-10-29 Time 08:54 Rev Time 1.00
Received By jwitmer Date 2010-10-29 Time 08:54 Sent To  
Notes
2010-10-29 08:58:12 
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) EQUIPMENT MOUNTING 3.6. FAILS TO PROVIDE TYPE OF
 ANCHOR FOR INSTALATION.
  
 2) 2000 GALLON FUEL TANK IS THIS EXISTING OR NEW? IF
 NEW PROVIDE MANUFACTURERS SPECIFICATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-11 Cont ID  
Sent By rlecky Date 2011-02-11 Time 14:46 Rev Time 0.00
Received By rlecky Date 2011-02-11 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-12-08 Cont ID  
Sent By rmcdouga Date 2010-12-08 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2010-10-21 Time 18:28 Sent To  
Notes
2010-10-21 19:11:15ELECTRICAL PLAN REVIEW FAIL
 1) SUBMIT LOAD CALCUATIONS FOR EM PANEL BEING SERVED BY
 NEW GENERATOR REPLACEMENT
  
 JOHN DICKINSON CONTRACT PLAN REVIEWER
 CELL NUMBER 561-718-3230

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-02-07 Cont ID  
Sent By ddaniels Date 2011-02-07 Time 12:35 Rev Time 0.00
Received By ddaniels Date 2011-02-07 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-21 Cont ID  
Sent By mcarsill Date 2010-10-21 Time 13:09 Rev Time 0.00
Received By mcarsill Date 2010-10-21 Time 12:49 Sent To  
Notes
2010-10-21 13:09:431200-45TH STREET
 PERMIT NUMBER 10100266
 "PROVIDE AND INSTALL REPLACEMENT GENERATOR PER THE
 ATTACHED PLANS AND SPECS"
  
  
 1. PLEASE PROVIDE CUT SHEETS AND PRODUCT APPROVALS FOR
 THE NEW PERMANENT GENERATOR.
  
 2. PLEASE PROVIDE A CODE DATA TABLE REFERENCING THE
 APPROPRIATE CODES. (FLORIDA FIRE PREVENTION CODE, 2006
 EDITION, NFPA 37, NFPA 30, NFPA 110, NFPA 70)
  
 3. PLEASE DECLARE WHAT EQUIPMENT THE NEW EMERGENCY
 GENERATOR IS EXPECTED TO SUPPLY. IS IT ONLY LIFE SAFETY
 SYSTEMS AND DEVICES OR EMERGENCY SYSTEMS AND NON
 EMERGENCY SYSTEMS.
  
 4. PLEASE SUPPLY A SURVEY TO ENSURE THAT THE ORIGINAL
 INSTALLATION LOCATION IS NOT IN ANY RECORDED EASEMENTS,
 ON PROPERTY LINES, AND IT ALLOWS SETBACKS TO BE
 EXAMINED.
  
 5. PLEASE INDICATE ANY WARNING LABELS ON THE DIESEL
 FUEL STORAGE TANK.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-16 Cont ID  
Sent By lmartine Date 2011-03-14 Time 11:40 Rev Time 0.00
Received By lmartine Date 2011-02-03 Time 11:13 Sent To  
Notes
2011-02-03 11:13:33C19
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-08 Cont ID  
Sent By rmcdouga Date 2010-12-08 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2010-10-13 Time 08:59 Sent To  
Notes
2010-10-14 09:00:00C24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-02-15 Cont ID  
Sent By hmoser Date 2011-02-15 Time 09:38 Rev Time 0.00
Received By hmoser Date 2011-02-15 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-11-02 Cont ID  
Sent By hmoser Date 2010-11-02 Time 11:03 Rev Time 0.00
Received By hmoser Date 2010-11-02 Time 10:36 Sent To  
Notes
2010-11-02 11:10:01PLAN DENIED
 PROVIDE A PIPING DIAGRAM FROM DAY TANK TO THE GENERATOR
 . DO NOT FILL FUEL LINES UNTIL PRESSURE TEST IS
 COMPLETED
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 3 Status P Date 2011-03-14 Cont ID  
Sent By ajones Date 2011-03-14 Time 16:10 Rev Time 0.00
Received By ajones Date 2011-03-14 Time 16:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-02-09 Cont ID  
Sent By astelly Date 2011-02-09 Time 16:08 Rev Time 0.00
Received By astelly Date 2011-02-09 Time 16:08 Sent To  
Notes
2011-02-09 16:12:22AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 REPEAT COMMENT
  
 PLEASE PROVIDE PLANS AND ELEVATIONS FOR THE SCREENING
 OF THE 2000 GALLON FUEL TANK IN ACCORDANCE WITH THE
 FOLLOWING FROM SEC 94-444:
  
 (B) OUTDOOR STORAGE FOR NONRESIDENTIAL AND MULTIFAMILY
 USES; STORAGE AND DISPOSAL FACILITIES.
  
 OUTDOOR INCINERATORS, GARBAGE OR TRASH RECEPTACLES,
 FUEL OIL OR PROPANE TANKS, AND STORAGE RACKS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS. A
 FOUR-SIDED ENCLOSURE WITH AN OBSCURING GATE MAY BE
 REQUIRED AS A CONDITION FOR SITE PLAN APPROVAL....
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-11-10 Cont ID  
Sent By astelly Date 2010-11-10 Time 11:39 Rev Time 0.00
Received By astelly Date 2010-11-10 Time 11:39 Sent To  
Notes
2010-11-10 11:50:14AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE PLANS AND ELEVATIONS FOR THE SCREENING
 OF THE GENERATOR AND ASSOCAITED FUEL TANK IN ACCORDANCE
 WITH THE FOLLOWING FROM SEC 94-444:
  
 (B) OUTDOOR STORAGE FOR NONRESIDENTIAL AND MULTIFAMILY
 USES; STORAGE AND DISPOSAL FACILITIES.
  
 OUTDOOR INCINERATORS, GARBAGE OR TRASH RECEPTACLES,
 FUEL OIL OR PROPANE TANKS, AND STORAGE RACKS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS. A
 FOUR-SIDED ENCLOSURE WITH AN OBSCURING GATE MAY BE
 REQUIRED AS A CONDITION FOR SITE PLAN APPROVAL....
  
  