Plan Review Details - Permit 10100243
Plan Review Stops For Permit 10100243
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-01-04 Cont ID  
Sent By rmcdouga Date 2011-01-04 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2011-01-03 Time 14:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-12-10 Cont ID  
Sent By rmcdouga Date 2010-12-10 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2010-12-10 Time 07:48 Sent To  
Notes
2010-12-10 13:24:16DENIED BY BUILDING
  
 1) THE REVISED PLANS INCORRECTLY SPECIFY THE WIND-SPEED
 AS 120 MPH. THE CORRECT WIND-SPEED FOR WEST PALM BEACH
 IS 140 MPH AND THE EXPOSURE CATEGORY FOR THIS BUILDING
 IS C. PLEASE CORRECT.
  
 2) THE COMPONENT AND CLADDING PRESSURES ARE TOO LOW FOR
 THE ADDITIONS TO THE MAIN HOUSE. THE PRESSURES NEED TO
 REFLECT THE 140 MPH WIND-SPEED, THE EXPOSURE CATEGORY C
 AND THE MEAN ROOF HEIGHT OF 26 FEET.
  
 3) THE COMPONENT AND CLADDING PRESSURES ARE TOO LOW FOR
 THE ADDITIONS TO THE CABANA. THE PRESSURES NEED TO
 REFLECT THE 140 MPH WIND-SPEED, THE EXPOSURE CATEGORY C
 AND THE MEAN ROOF HEIGHT OF 26 FEET.
  
 4) THE ELEVATIONS FOR THE CABANA ON A-02 SPECIFIES THE
 TOP OF THE PARAPET WALL AT THE ADDITION AS 34'-10".
 PLEASE CORRECT.
  
 5) THE COMPONENT AND CLADDING PRESSURES FOR THE
 ADDITION ROOFS ARE INCORRECT. THE ADDITIONS ALL HAVE
 FLAT ROOFS AND THE EFFECTIVE WIND AREA IS 10 SQFT. IF
 USING TABLES R301.2(2) AND R301.2(3).
  
 6) THE ENERGY CALCULATION FORMS ARE NOT SIGNED BY THE
 OWNER AGENT. THE FORMS HAVE THE EXTERIOR WALLS AS R-6
 AND THE PLANS HAVE R-4. THE CEILING INSULATION ON THE
 FORMS IS R-30 AND THE PLANS HAVE R-19. PLEASE CORRECT.
  
 7) THE ROOFING PRODUCT APPROVAL FOR THE JOHNS MANVILLE
 TORCH DOWN MODIFIED ROOF REQUIRES SIGNED AND SEALED
 CALCULATIONS FOR ENHANCED FASTENING FOR THE HIGHER
 UPLIFTS AT THE CORNER AND PERIMETER AREAS. SPECIFY THE
 APPROVED ASSEMBLY AND FASTENING OPTION FROM THE PRODUCT
 APPROVAL FOR A NON-INSULATED WOOD DECK THAT WILL BE
 INSTALLED AND SUBMIT THE ENHANCED FASTENING
 CALCULATIONS.
  
 8) THE PLANS SPECIFY AN 1/8" PER FOOT SLOPE ON THE FLAT
 ROOFS. THE MINIMUM SLOPE ALLOWED BY THE CODE IS 1/4"
 PER FOOT PER FBC R905.11.1. PLEASE CORRECT.
  
 9) SHOW COMPLIANCE WITH FBC R903.4.1 AND FBC PLUMBING
 1107.1 - 1107.3 FOR SECONDARY (EMERGENCY) ROOF DRAINS.
 THESE ARE REQUIRED IN ADDITION TO THE PRIMARY DRAINS
 SHOWN ON THE REVISED DRAWINGS.
  
 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. FBC 106.3.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-28 Cont ID  
Sent By rmcdouga Date 2010-10-28 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2010-10-27 Time 07:26 Sent To Z
Notes
2010-10-27 07:54:552007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PLANS SPECIFY EXPOSURE CATEGORY B AND THE
 STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C PER FBC
 R301.2.1.4.3. PLEASE REVISE PLANS. ALSO REVISE THE
 COMPONENT AND CLADDING PRESSURES TO COMPLY WITH
 EXPOSURE C.
  
 2) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY FOR IMPACT FEES. THIS CAN BE DONE AFTER
 ALL OF THE REVIEWS HAVE BEEN COMPLETED.
  
 3) SUBMIT 2 COPIES OF ENERGY CALCULATIONS FOR THE NEW
 ADDITION AS REQUIRED BY 2007 FBC ENERGY GLITCH
 AMENDMENTS CHAPTER 11. THE FORM IS REQUIRED TO BE
 SIGNED BY THE PREPARER AND THE OWNER/AGENT. THE
 R-VALUES SPECIFIED ON THE PLANS ARE REQUIRED TO
 CORRESPOND WITH THE ENERGY CALC. FORM.
  
 4) SECTION AA ON SHEET S-01 SPECIFIES 4" INSULATION ON
 1/2" PT FURRING. PLEASE CLARIFY. DID YOU MEAN R-4
 INSULATION ON 1 X 2 FURRING?
  
 5) SHOW COMPLIANCE WITH FBC R806.1 FOR ROOF VENTILATION
 OR R806.4 FOR UNVENTED ATTIC ASSEMBLIES.
  
 6) SHEET S-01 SPECIFIES A MODIFY STARCH DOWN BUILT-UP
 ROOF MEMBRANE. PLEASE CLARIFY. DID YOU MEAN A MODIFIED
 TORCH DOWN MEMBRANE. SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR THE ROOF COVERING MATERIAL THAT WILL BE
 INSTALLED AS REQUIRED BY DCA RULE 9B-72. SPECIFY THE
 APPROVED ASSEMBLY AND FASTENING OPTION THAT WILL BE
 USED. IF THE DESIGN PRESSURES REQUIRE ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER AREAS, SUBMIT
 ENHANCED FASTENING CALCULATIONS.
  
 7) SHOW COMPLIANCE WITH FBC R903.4 AND R903.4.1 FOR
 ROOF SCUPPERS AND OVERFLOW SCUPPERS. SPECIFY THE SIZE
 OF THE ROOF AND OVERFLOW SCUPPERS AND PROVIDE SIZING
 CALCULATIONS. INCLUDE THE AREA OF THE ROOF ABOVE THAT
 WILL EMPTY ONTO THE FLAT ROOF BELOW. SEE FBC PLUMBING
 1106.7 AND 1107.3.
  
 8) DOWN SPOUTS ARE REQUIRED ON THE PRIMARY SCUPPERS AND
 SHALL DISCHARGE AT LEAST ONE FOOT AWAY FROM THE
 STRUCTURE SIDEWALL PER FBC R320.7.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-01-04 Cont ID  
Sent By rmcdouga Date 2011-01-04 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2011-01-04 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-23 Cont ID  
Sent By jdickins Date 2010-11-23 Time 18:26 Rev Time 0.00
Received By jdickins Date 2010-11-23 Time 18:26 Sent To  
Notes
2010-11-23 18:26:27OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-25 Cont ID  
Sent By rmcdouga Date 2010-10-25 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2010-10-25 Time 14:47 Sent To  
Notes
2010-10-25 14:49:41PASSED WITH PROVISO
  
 CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PER FBC R313.4.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-01-04 Cont ID  
Sent By rmcdouga Date 2011-01-04 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2010-12-21 Time 07:59 Sent To  
Notes
2010-12-21 07:59:30R21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-10 Cont ID  
Sent By rmcdouga Date 2010-12-10 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2010-11-19 Time 09:40 Sent To  
Notes
2010-11-19 09:41:00R6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-19 Cont ID  
Sent By rmcdouga Date 2010-11-19 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2010-10-14 Time 14:55 Sent To  
Notes
2010-10-14 15:00:05R20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-01-04 Cont ID  
Sent By rmcdouga Date 2011-01-04 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2011-01-04 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-12-10 Cont ID  
Sent By rmcdouga Date 2010-12-10 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2010-12-10 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-10-26 Cont ID  
Sent By rmcdouga Date 2010-10-26 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2010-10-26 Time 15:43 Sent To  
Notes
2010-10-26 15:45:54DENIED BY MECHANICAL
  
 1) SPECIFY THE SIZE OF THE NEW SUPPLY AND RETURN DUCTS
 ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-10-26 Cont ID  
Sent By rmcdouga Date 2010-10-26 Time 15:46 Rev Time 0.00
Received By rmcdouga Date 2010-10-26 Time 15:46 Sent To  
Notes
2010-10-26 15:54:23NO PLUMBING PLANS SUBMITTED AND NO PLUMBING PERMIT WAS
 APPLIED FOR.

Review Stop Z ZONING
Rev No 3 Status P Date 2010-12-30 Cont ID  
Sent By jroach Date 2010-12-30 Time 11:34 Rev Time 0.00
Received By jroach Date 2010-12-30 Time 11:34 Sent To  
Notes
2010-12-30 11:35:08ZONING PLAN REVIEW
  
 DATE OF REVIEW: 11/29/10
 PERMIT NO.: 10100243
 ADDRESS: 236 BLOOMFIELD DRIVE
 CONTRACTOR/CONTACT: JUAN
 TELEPHONE NO.: 305.778.2082
 SCOPE OF REVIEW: ENCLOSURE OF EAST AND WEST TERRACES ON
 SECOND FLOOR OF PRIMARY STRUCTURE, AND BUILD OUT OF
 PORCH AREA ON EAST AND WEST SIDES AT REAR CABANA.
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1) THAT AREA IDENTIFIED AS ???OUTDOOR PORCH??? ON THE
 REAR CABANA SHALL NOT BE ENCLOSED!
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-11-29 Cont ID  
Sent By jroach Date 2010-11-29 Time 16:42 Rev Time 0.00
Received By jroach Date 2010-11-29 Time 16:42 Sent To  
Notes
2010-11-29 16:42:14ZONING PLAN REVIEW
  
 DATE OF REVIEW: 11/29/10
 PERMIT NO.: 10100243
 ADDRESS: 236 BLOOMFIELD DRIVE
 CONTRACTOR/CONTACT: JUAN
 TELEPHONE NO.: 305.778.2082
 SCOPE OF REVIEW: ENCLOSURE OF EAST AND WEST TERRACES ON
 SECOND FLOOR OF PRIMARY STRUCTURE, AND BUILD OUT OF
 PORCH AREA ON EAST AND WEST SIDES AT REAR CABANA.
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1) THAT AREA IDENTIFIED AS ???OUTDOOR PORCH??? ON THE
 REAR CABANA SHALL NOT BE ENCLOSED!
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-11-08 Cont ID  
Sent By jroach Date 2010-11-08 Time 17:09 Rev Time 0.00
Received By jroach Date 2010-11-08 Time 17:09 Sent To  
Notes
2010-11-08 17:10:07ZONING PLAN REVIEW
  
 DATE OF REVIEW: 11/08/2010
 PERMIT NO.: 10100243
 ADDRESS: 236 BLOOMFIELD DRIVE
 CONTRACTOR/CONTACT: MANUAL SANCHEZ
 TELEPHONE NO.: 561.688.2295
 SCOPE OF REVIEW: ENCLOSE EAST AND WEST TERRACES ON
 SECOND FLOOR. BUILD OUT PORCH AREA ON EAST AND WEST
 SIDES AT BACK CABANA.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) COPIES OF CURRENT AND ACCURATE SURVEY SHALL
 BE PROVIDED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved