Plan Review Details - Permit 10100200
Plan Review Stops For Permit 10100200
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-02 Cont ID  
Sent By rmcdouga Date 2010-12-01 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2010-12-01 Time 15:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-19 Cont ID  
Sent By rmcdouga Date 2010-10-19 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2010-10-19 Time 10:28 Sent To Z
Notes
2010-10-19 11:18:182007 FBC W/2009 REVISIONS
 STORAGE ROOM ADDITION
  
 DENIED BY BUILDING
  
 1) INDICATE THE LOCATION OF THE ADDITION ON THE SURVEY
 OR PROVIDE SITE PLANS. SPECIFY THE DISTANCES TO
 PROPERTY LINES.
  
 2) SPECIFY THE ANCHORS THAT WILL BE USED TO STRAP THE 2
 X 6 RAFTERS TO THE TIE BEAM. THE PLANS SPECIFY A
 SIMPSON HS10 MASONRY CONNECTOR, HOWEVER I COULD NOT
 LOCATE THIS CONNECTOR IN THE SIMPSON CATALOG. PLEASE
 CLARIFY AND SUBMIT TWO CURRENT COPIES OF THE PRODUCT
 APPROVALS FOR ALL CONNECTORS SPECIFIED ON THE PLANS AS
 REQUIRED BY DCA RULE 9B-72.
  
 3) THE CONCRETE FOUNDATION IS REQUIRED TO BE A MINIMUM
 OF 4 INCHES ABOVE THE ADJACENT GRADE PER FBC R404.1.6
 AND EXTERIOR FOOTINGS SHALL BE AT LEAST 12" BELOW GRADE
 PER FBC R403.1.4. THIS REQUIRES A MINIMUM 16" THICK
 FOOTING. PLEASE REVISE PLANS.
  
 4) SHOW COMPLIANCE WITH FBC R320 FOR TERMITE
 PROTECTION.
  
 5) THE PLANS DO NOT INDICATE ANY ROOF OVERHANG. FBC
 R320.7 REQUIRES GUTTERS WITH DOWNSPOUTS ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6 INCHES HORIZONTAL
 PROJECTION.
  
 6) FBC R803.2.3.1 REQUIRES ROOF SHEATHING TO BE
 FASTENED WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER. SPECIFY THIS ON PLANS.
  
 7) SPECIFY THE SPACING OF THE ROOF RAFTERS ON THE
 PLANS. THEY APPEAR TO BE 2 FEET ON CENTER.
  
 8) SUBMIT TWO CURRENT COPIES OF THE MIAMI-DADE NOAS OR
 STATE OF FLORIDA PRODUCT APPROVALS FOR THE EXTERIOR
 DOOR AND THE ROOF COVERING MATERIAL AS REQUIRED BY DCA
 RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By rmcdouga Date 2010-10-19 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2010-10-19 Time 10:25 Sent To  
Notes
2010-10-19 10:26:10OK PER J. LEAHY 10/13/10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-01 Cont ID  
Sent By rmcdouga Date 2010-12-01 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2010-11-02 Time 15:24 Sent To  
Notes
2010-11-02 15:24:51R5
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-29 Cont ID  
Sent By shill Date 2010-10-29 Time 12:43 Rev Time 0.00
Received By shill Date 2010-10-13 Time 08:34 Sent To  
Notes
2010-10-13 08:37:17R2

Review Stop Z ZONING
Rev No 2 Status P Date 2010-11-10 Cont ID  
Sent By astelly Date 2010-11-10 Time 11:53 Rev Time 0.00
Received By astelly Date 2010-11-10 Time 11:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-10-29 Cont ID  
Sent By astelly Date 2010-10-29 Time 11:22 Rev Time 0.00
Received By astelly Date 2010-10-29 Time 11:22 Sent To  
Notes
2010-10-29 11:26:50AMY STELLY
 PLANNING AND ZONING
 822-1442
  
 PLEASE INDICATE THE LOCATION OF THE ADDITION WITH SIDE
 AND REAR SETBACKS ON THE SURVEY. SEE REQUIREMENTS
 BELOW.
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
  
 A.FRONT: 25 FEET;
  
 B.CORNER: 12.5 FEET;
  
 C.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
  