Plan Review Details - Permit 10100173
Plan Review Stops For Permit 10100173
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-10-22 Cont ID  
Sent By jwitmer Date 2010-10-22 Time 15:41 Rev Time 0.50
Received By jwitmer Date 2010-10-22 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By jdickins Date 2010-11-08 Time 16:00 Rev Time 0.00
Received By jdickins Date 2010-11-08 Time 16:00 Sent To  
Notes
2010-11-08 16:00:38OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-12 Cont ID  
Sent By dwise Date 2010-10-12 Time 18:39 Rev Time 0.00
Received By dwise Date 2010-10-12 Time 18:39 Sent To  
Notes
2010-10-12 18:41:12OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-17 Cont ID  
Sent By mcarsill Date 2010-11-17 Time 08:25 Rev Time 0.00
Received By mcarsill Date 2010-11-17 Time 08:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-18 Cont ID  
Sent By mcarsill Date 2010-10-18 Time 15:05 Rev Time 0.00
Received By mcarsill Date 2010-10-18 Time 14:57 Sent To  
Notes
2010-10-18 15:05:304001 BROADWAY AVENUE
 PERMIT NUMBER 10100173
 "ALTERATION CHINESE TAKE-OUT RESTAURANT"
  
  
 1. THE GAS FIRED RICE COOKER APPEARS TO BE PARTIALLY
 LOCATED OUTSIDE THE PROTECTION OF THE HOOD AND FIRE
 SUPPRESSION SYSTEM.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 HOODS,DUCTS, AND FIRE SUPPRESSION SYSTEM INSTALLATIONS.
  
 3. ON SHEET E-1 IT APPEARS THAN AN EXIT SIGN LEADS
 PERSONS TO THE EXISTING LAUNDRY STORE. ARE BOTH THESE
 BUSINESSES OPERATED BY THE SAME GROUP OR BY OTHERS. IF
 BY OTHERS HOW IS EXIT ACCESS PROVIDED AND MAINTAINED.
  
 4. NO EXISTING EXIT SIGNS OR EMERGENCY LIGHTS SHOWN IN
 THE EXISTING LAUNDRY STORE WHERE PERSONS ARE BEING
 DIRECTED TO.
  
 5. THE PLANS CALL OUT THE THREE DIFFERENT INTERIOR
 FINISH CLASSIFICATIONS BUT ONE SPECIFIC ONE IS NOT
 IDENTIFIED.
  
 6. GAS INSTALLATION TO COMPLY WITH THE NATIONAL FUEL
 GAS CODE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By lwagner Date 2010-10-19 Time 10:53 Rev Time 0.00
Received By lwagner Date 2010-10-19 Time 10:33 Sent To  
Notes
2010-10-19 10:53:01BEFORE PERMIT IS ISSUED SUBMIT MANUFACTURE SHEETS FOR
 ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND FBC-2007 FUEL GAS SEC. 402.2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-12-15 Cont ID  
Sent By lmartine Date 2010-12-15 Time 16:34 Rev Time 0.00
Received By lmartine Date 2010-12-15 Time 16:26 Sent To  
Notes
2010-12-15 16:34:58*******************EXPEDITED********************
 IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-04 Cont ID  
Sent By rmcdouga Date 2010-11-04 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2010-11-04 Time 12:47 Sent To  
Notes
2010-11-04 12:47:56B9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-04 Cont ID  
Sent By rmcdouga Date 2010-11-04 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2010-10-08 Time 14:20 Sent To  
Notes
2010-10-08 14:20:43SENT TO B1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-12-17 Cont ID  
Sent By hmoser Date 2010-12-17 Time 13:48 Rev Time 0.00
Received By hmoser Date 2010-12-17 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-12-08 Cont ID  
Sent By hmoser Date 2010-12-08 Time 14:13 Rev Time 0.00
Received By hmoser Date 2010-12-08 Time 14:13 Sent To  
Notes
2010-12-08 14:17:29PLAN DENIED
 PROVIDE FRESH AIR CALCULATIONS ON THE PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-11-02 Cont ID  
Sent By hmoser Date 2010-11-02 Time 09:22 Rev Time 0.00
Received By hmoser Date 2010-11-01 Time 14:04 Sent To  
Notes
2010-11-02 09:37:58PLAN DENIED
 1) PLEAS REFER TO SECTION 402 2007 FMC NATURAL
 VENTILATION ( WINDOWS ON THE BUILBING ARE FIXED THEY DO
 NOT OPEN ) PLEASE PROVIDE FRESH AIR CALCULATIONS ON THE
 PLANS.
 2) REFER TO SECTION 606.3 2007 FMC INSTALLATION .
 3) WALK IN COOLERS AND KITCHEN HOOD REQUIRE THERE OWN
 PLANS AND PERMITS.
 4) PLEASE PROVIDE A DETAIL ON THE PLAN FOR A/C CURB TO
 ROOF TIE DOWN .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By lwagner Date 2010-10-19 Time 10:53 Rev Time 0.00
Received By lwagner Date 2010-10-19 Time 10:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-12-17 Cont ID  
Sent By lfranco Date 2010-12-17 Time 10:50 Rev Time 0.00
Received By lfranco Date 2010-12-17 Time 10:50 Sent To M
Notes
2010-12-17 11:12:57PLANNING AND ZONING: **** ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2010-12-02 Cont ID  
Sent By lfranco Date 2010-12-01 Time 09:50 Rev Time 0.00
Received By lfranco Date 2010-12-01 Time 09:50 Sent To  
Notes
2010-12-01 09:51:05PLANNING AND ZONING: **** FAILED - RE-SUBMITTAL OF
 11/4/10 DID NOT ADDRESS ANY OF THE COMMENTS. *****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. THE PARTIAL FLOOR PLAN DOES NOT CORRELATE WITH THE
 BUILDING FOOTPRINT IN THE AERIAL. WHERE EXACTLY IS THIS
 BUILDING AREA FROM THE ADDRESS PROVIDED OF 4001
 BROADWAY? PROVIDE INFORMATION ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-10-26 Cont ID  
Sent By lfranco Date 2010-10-26 Time 19:14 Rev Time 0.00
Received By lfranco Date 2010-10-26 Time 19:14 Sent To  
Notes
2010-10-26 19:17:40PLANNING AND ZONING: **** FAILED *****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. THE PARTIAL FLOOR PLAN DOES NOT CORRELATE WITH THE
 BUILDING FOOTPRINT IN THE AERIAL. WHERE EXACTLY IS THIS
 BUILDING AREA FROM THE ADDRESS PROVIDED OF 4001
 BROADWAY? PROVIDE INFORMATION ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy