| 2010-11-22 13:36:47 | RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- MISSING FLOOR PLAN SHOWING LOCATION OF SCREEN |
| | ENCLOSURE. SEC. 106.1.1 AND SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC. |
| | AND, CLEARLY IDENTIFY EACH POST. |
| | |
| | 2- PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR |
| | CONCRETE SLAB AND FOOTING SIZES. SEC. 106.1.1 AND SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC. |
| | AND, CLEARLY IDENTIFY EACH POST. |
| | |
| | 3- REVISE DESIGN PARAMETERS: |
| | A) ACCORDING TO 2009 REVISIONS SEC. 1609.4.3 (SEC. |
| | R301.2.1.4.3 2007 FLORIDA RESIDENTIAL CODE) THIS |
| | BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". NEED TO |
| | REVISE THE DESIGN PARAMETERS FROM TABLE 2002.4 FOR |
| | EXPOSURE C. |
| | |
| | B) UPDATE ASCE 7 SPECIFIED ON DESIGN PARAMETERS. ASCE |
| | 7-05 IS THE ONE THAT WAS ADOPTED BY THE FBC 2007. NOT |
| | ASCE 7-02. REVISE AS REQUIRED. |
| | |
| | 4- A) REVISE ALL THE BEAMS AND COLUMNS TABLES TO VALUES |
| | THAT CORRESPOND TO EXPOSURE "C". |
| | |
| | B) NEED TO USE TABLES FOR BEAMS AND COLUMNS THAT TAKE |
| | INTO CONSIDERATION THE SOLID ALUMINUM ROOF PANELS. |
| | TABLES PROVIDED ARE NOT ADEQUATE FOR ROOF WITH SOLID |
| | PANELS. |
| | |
| | C) SPECIFY WHERE ARE THE BEAMS AND COLUMNS TABLES TAKEN |
| | FROM. |
| | |
| | 5- CLARIFY IF THE ROOF PANELS ARE GOING TO HAVE |
| | OVERHANG OR NOT. DRAWINGS SUBMITTED DON'T SPECIFY ANY |
| | OVERHANG. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR THE ALUMINUM ROOF PANELS TO BE USED. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) THE ALUMINUM ROOF PANEL |
| | PRODUCT APPROVAL PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 8- PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT. |
| | SPECIFY LOCATION OF "K" BRACING ON ELEVATIONS. SEE |
| | DETAIL. AND, PROVIDE ONLY THE TABLES THAT APPLY TO THIS |
| | PROJECT. SEC. 106.1.1. |
| | |
| | 9- PROVIDE DETAIL CONNECTION TO THE EXISTING RESIDENCE. |
| | TOP VIEW FLOOR PLAN SPECIFIES 3" HEADER CHANNEL. THERE |
| | ARE NO DETAILS SHOWING THIS CONNECTION. SEC. 106.1.1. |
| | |
| | 10. FRONT ELEVATION SPECIFIES 2X6 CARRIER BEAM. THIS |
| | DOESN'T CORRESPOND TO CARRY BEAM TABLE PROVIDED. REVISE |
| | AS REQUIRED AND COORDINATE WITH ITEM #4B ABOVE. |
| | |
| | 11- PROVIDE TABLE THAT REFLECTS SIZE OF POSTS SPECIFIED |
| | ON ELEVATIONS TO VERIFY ALL LOADS AND SPACING. |
| | COORDINATE WITH ITEM #4B ABOVE. SEC. 106.1.1. |
| | |
| | 12- PROVIDE COMPLETE DOOR FRAMING DETAILS. SPECIFY ALL |
| | FRAMING MEMBERS. SEC. 106.1.1 |
| | |
| | 13- REVISE COLUMN ANCHORING DETAIL. REVISE SIZE OF |
| | COLUMN TO MATCH SIZE SHOWN ON ELEVATIONS. ALSO, PROVIDE |
| | DETAIL FOR CORNER POSTS. |
| | |
| | 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | ATTACHMENT OF ALUMINUM ROOF PANELS. DETAILS PROVIDED |
| | DON'T APPLY TO PROPOSED SCREEN ENCLOSURE. COORDINATE |
| | WITH PRODUCT APPROVAL SUBMITTED. |
| | |
| | 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | COLUMN TO CARRIER BEAM CONNECTION, INCLUDING |
| | CONNECTIONS AT THE ENDS OF THE BEAM. SEC. 106.1.1. |
| | |
| | 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION WAS UPDATED TO INCLUDE ALL LABOR, |
| | MATERIALS AND ENGINEERING FEES. OWES $208.34. |
| | |
| | 17- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |