Plan Review Details - Permit 10100160
Plan Review Stops For Permit 10100160
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-10-21 Cont ID  
Sent By shill Date 2010-10-20 Time 14:27 Rev Time 0.00
Received By shill Date 2010-10-20 Time 08:59 Sent To  
Notes
2010-10-20 14:27:28****PROVISO****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DETAIL 2/A3.1 REMOVED FROM PLAN. A REVISED DETAIL IS
 TO BE SUBMITTED IF REQUIRED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-21 Cont ID  
Sent By shill Date 2010-10-21 Time 14:04 Rev Time 0.00
Received By shill Date 2010-10-21 Time 14:04 Sent To  
Notes
2010-10-21 14:12:01OK PER JOHN DICKINSON PX3182
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-10-26 Cont ID  
Sent By mcarsill Date 2010-10-26 Time 09:08 Rev Time 0.00
Received By mcarsill Date 2010-10-26 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-10-29 Time   Rev Time 0.00
Received By rregueir Date 2010-10-08 Time 17:21 Sent To  
Notes
2010-10-08 17:22:19**DIGITAL PLANS** SEE PROJECTDOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-10-21 Cont ID  
Sent By shill Date 2010-10-21 Time 14:12 Rev Time 0.00
Received By shill Date 2010-10-21 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-10-12 Cont ID  
Sent By rregueir Date 2010-10-12 Time 14:33 Rev Time 0.00
Received By rregueir Date 2010-10-08 Time 17:22 Sent To  
Notes
2010-10-08 17:22:59**PROVISO**
  
 1. PG M0.1: CORRECT MATHEMATICAL ERROR IN VENTILATION
 CALCULATIONS. SEE DRAWING MARK-UP.
  
 2. PG M0.1: CALCULATE CONFERENCE ROOMS, LOBBIES AND
 BREAKROOMS SEPARATELY FROM GENERAL OFFICE SPACE PER
 AHSRAE 62.1-2004 TABLE 6-1.
  
 3. PG M0.2: FIRE DAMPER INSTALLATION SHALL BE IN
 ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS PER FBC-M
 607.2.
  
 4. PG M2.2: ARCHITECTURAL PLANS SHOW FULL HEIGHT
 PARTITIONS SEPARATING LOBBY 200, CONFERENCE 201 AND
 CONFERENCE 202 FROM THE REMAINDER OF THE CONDITIONED
 SPACES. SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN
 THIS AREA PER FBC-M 601.4.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By lwagner Date 2010-10-19 Time 08:22 Rev Time 0.00
Received By lwagner Date 2010-10-19 Time 08:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2010-10-27 Cont ID  
Sent By rregueir Date 2010-10-27 Time 09:27 Rev Time 0.00
Received By rregueir Date 2010-10-27 Time 09:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-10-14 Cont ID  
Sent By jroach Date 2010-10-14 Time 09:37 Rev Time 0.00
Received By jroach Date 2010-10-14 Time 09:37 Sent To  
Notes
***NONE***