Plan Review Details - Permit 10100153
Plan Review Stops For Permit 10100153
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-01 Cont ID  
Sent By jwitmer Date 2010-12-01 Time 12:03 Rev Time 1.20
Received By jwitmer Date 2010-12-01 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-25 Cont ID  
Sent By jwitmer Date 2010-10-25 Time 13:34 Rev Time 2.00
Received By jwitmer Date 2010-10-22 Time 15:51 Sent To  
Notes
2010-10-25 13:35:29BUILDING PLAN REVIEW
 PERMIT: 10100153
 ADD: 321 8TH ST
 CONT: BELLA CONSTRUCTION
 TEL: (561)722-6402
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW: DENIED
  
 1) SITE PLAN REVIEW:
  
 1A) THE FRONT ENTRY IS NOT THE ACCESSIBLE ENTRY,
 11-4.1.8(3) DOES ALLOW FOR ALTERNATE ENTRY PLEASE
 INDICATE HOW COMPLIANCE WITH THE ARCHITECTURAL BARRIER
 REMOVAL ACT WOULD NOT BE READILY ACHIEVABLE. IN BOTH
 CASES FRONT OR REAR ENTRY THE ENTRANCE WOULD NEED TO BE
 MODIFIED BY CHANGE OF ELEVATION.
  
 1B) FOR ENTRANCES THAT ARE NOT ACCESSIBLE PLEASE REVIEW
 REQUIRED SIGNAGE 11-4.1.8(3) , 11-4.30.1. & 11-4.30.7.
  
 1C) THE REAR OF THE BUILDING INDICATES THE ACCESSIBLE
 PATH WITH THE USE OF A RAMP FOR CHANGE IN ELEVATION.
 PLEASE REVIEW SECTION 11-4.8.4(2) FOR THE REQUIRED
 LENGTH OF THE BOTTOM LANDING. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE.
  
 1D) THE OTHER ISSUE WITH THE RAMP IS THE MID LANDING
 AND CHANGE OF DIRECTION. 11-4.8.4(3) IF RAMPS CHANGE
 DIRECTION AT LANDINGS, THE MINIMUM LANDING SIZE SHALL
 BE 60" X 60".
  
 1E) PLANS INDICATE THIS TO BE A LEVEL III ALTERATION
 BUT IS IT A CHANGE OF OCCUPANCY FROMR-3 TO BUSINESS? IF
 SO PALM BEACH COUNTY IMPACT FEE OFFICE WILL NEED TO
 REVIEW PLANS FOR ASSESSMENT.
  
 2) THE FRONT ENTRY DOORS ARE LACKING PRODUCT APPROVALS
 AS PER RULE 9B-72(31)(A) FOR EXTERIOR DOORS. SHEET S-1
 INDICATES IN SECTION #1 INDICATES THE DOORS TO BE
 WITHIN A DOOR FRAME AND TRANSOM TO BE IMPOSED UPON THE
 BEAM MORE OF A MOCK TRANSOM?
  
 3) ADDITIONAL INFORMATION REQUIRED 106.1.2 SHEET A-300
 INDICATES THE USE OF CAST STONE TRIM PLEASE PROVIDE
 COMPLIANCE WITH EITHER FBC-B 1405.6, 1405.7 OR 1405.9.
  
 4) A-3 AND STRUCTURAL SHEETS ALSO INDICATE A NEW
 CRICKET BUT THE PLANS INDICATE THE TYPE OF ROOF
 COVERING TO BE SHINGLES. NO ROOFING PRODUCT APPROVALS
 SUBMITTED, RULE 9B-72(31)(D) WILL REQUIRE PRODUCT
 APPROVALS AT TIME OF THE ROOFING PERMIT IS APPLIED FOR.
  
 5) SHEET M-1 IT APPEARS THAT THE A/C CONDENSERS ARE TO
 BE ROOF MOUNTED, IF THIS IS THE CASE RULE 9-B-72(31)(G)
 REQUIRES PRODUCT APPROVALS FOR PRE-ENGINEERED AIR
 CONDITIONING STANDS. THE SITE PLANS DO INDICATE
 EXISTING CONCRETE A/C PAD?
  
 6) A-400 INDICATES THE USE OF ICYNENE FOAM INSULATION
 PLEASE PROVIDE PRODUCT TESTING REPORTS AS TO
 LIMITATIONS. FBC-B 2603.4.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-12 Cont ID  
Sent By dwise Date 2010-10-12 Time 19:42 Rev Time 0.00
Received By dwise Date 2010-10-12 Time 19:42 Sent To  
Notes
2010-10-12 19:44:32OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-06 Cont ID  
Sent By mcarsill Date 2010-12-06 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2010-12-06 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-18 Cont ID  
Sent By mcarsill Date 2010-10-18 Time 13:19 Rev Time 0.00
Received By mcarsill Date 2010-10-18 Time 13:08 Sent To  
Notes
2010-10-18 13:19:02321-8TH STREET
 PERMIT NUMBER 10100153
 "ALTERATION/ REMODEL OF EXISTING 1 STORY STRUCTURE FOR
 DENTAL OFFICE"
  
  
 1. THE BUILDING ADDRESS DISPLAYED ON SHEET A-700 SHALL
 BE AT LEAST 6" HIGH AND AT LEAST 1" WIDE THAT CONTRASTS
 TO THE BACKGROUND THAT IT IS AFFIXED TO.
  
 2. NO EXIT SIGNS, EMERGENCY LIGHTS OF PORTABLE FIRE
 EXTINGUISHERS DISPLAYED ON THE PLANS.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 5. THE BUILDING IS TO BE PLACARDED WITH A MALTESE CROSS
 WITH THE LETTER "R" SIGNIFYING WOODEN ROOF TRUSSES.
  
 6. PLEASE INDICATE INFORMATION RELATED TO THE TYPES OF
 MEDICAL GASES, (OXYGEN, NITROUS OXIDE, ETC.) THAT MAY
 BE PLANNED FOR THE FACILITY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-15 Cont ID  
Sent By jwitmer Date 2010-11-15 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2010-11-15 Time 16:14 Sent To  
Notes
2010-11-15 16:18:24INCOMING SENT TO B-8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-06 Cont ID  
Sent By lmartine Date 2010-10-25 Time 14:41 Rev Time 0.00
Received By lmartine Date 2010-10-07 Time 16:40 Sent To  
Notes
2010-10-07 16:40:41B--8

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2010-12-07 Cont ID  
Sent By lmartine Date 2010-12-07 Time 14:22 Rev Time 0.00
Received By lmartine Date 2010-12-07 Time 14:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2010-12-01 Cont ID  
Sent By jwitmer Date 2010-12-01 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2010-12-01 Time 11:48 Sent To  
Notes
2010-12-01 11:49:23BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-10-25 Cont ID  
Sent By jwitmer Date 2010-10-25 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2010-10-25 Time 13:35 Sent To  
Notes
2010-10-25 13:36:29BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2010-12-06 Cont ID  
Sent By lmartine Date 2010-12-06 Time 14:38 Rev Time 0.00
Received By lmartine Date 2010-12-06 Time 14:38 Sent To  
Notes
2010-12-06 14:40:10SEPARATE PLANS AND PERMIT REQUIRED.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-10-25 Cont ID  
Sent By rkussner Date 2010-10-25 Time 09:49 Rev Time 0.00
Received By rkussner Date 2010-10-25 Time 09:49 Sent To  
Notes
2010-10-25 09:57:28***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE ADDRESS ZONING COMMENTS PRIOR TO SUBMITTING
 LANDSCAPE PLAN. THERE ARE PROBLEMS WITH THE PARKING LOT
 THAT MUST BE ADDRESSED PRIOR TO DESIGNING THE
 LANDSCAPE.
  
 2. APPLY FOR SEPARATE LANDSCAPE PERMIT ONCE ZONING
 ISSUES HAVE BEEN RESOLVED. SUBMIT TWO (2) COPIES OF A
 LANDSCAPE PLAN THAT HAS BEEN SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT. IN ADDITION, PLEASE
 PROVIDE A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FO THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-11-29 Cont ID  
Sent By hmoser Date 2010-11-29 Time 08:59 Rev Time 0.00
Received By hmoser Date   Time   Sent To  
Notes
2010-11-29 09:06:52PROVISO
 PLEASE PROVIDE A REVISED PLAN BE FOR FIRST MECHANICAL
 ROUGH INSPECTION. SHOWING FRESH AIR DUCT LOCATION AND
 DUCT SIZE .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-10-22 Cont ID  
Sent By hmoser Date 2010-10-22 Time 09:29 Rev Time 0.00
Received By hmoser Date 2010-10-21 Time 13:40 Sent To  
Notes
2010-10-22 09:46:19PLAN DENIED
 1) PLEASE REFER TO SECTION 601.4 2007 FMC BALANCED
 RETURN AIR EXCEPTION # 3 KITCHEN AND DENTAL EQUIPMENT
 ROOM .
 2) PLEASE REFER TO SECTION 606.2.1 2007 FMC SUPPLY AIR
 SYSTEM SEE EXCEPTION .
 3) REFER TO SECTION 606.3 INSTALLATION
 4) PLEASE REFER TO SECTION 602.2.1 MATERIALS EXPOSED
 WITHIN PLENUMS . CAN NOT USE WOOD DOORS ON THE A/C
 CLOSET
 5) PLEASE PROVIDE A DETAIL ON THE PLANS FROM THE
 ENGINEER ON THE A/C STAND TIE DOWN TO THE ROOF.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2010-11-29 Cont ID  
Sent By lwagner Date 2010-11-29 Time 15:23 Rev Time 0.00
Received By lwagner Date 2010-11-29 Time 15:23 Sent To  
Notes
2010-11-29 15:23:53MED GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-11-29 Cont ID  
Sent By lwagner Date 2010-11-29 Time 15:22 Rev Time 0.00
Received By lwagner Date 2010-11-29 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-21 Cont ID  
Sent By lwagner Date 2010-10-21 Time 10:27 Rev Time 0.00
Received By lwagner Date 2010-10-20 Time 14:37 Sent To  
Notes
2010-10-20 14:37:14FBC 2007 PLUMBING PLAN REVIEW #1
 DENIED:
  
 MED GAS
 1. NOT ENOUGH INFORMATION WAS FOUND FOR A REVIEW ON MED
 GAS. SHEETS P-2.0 & P-3.0 REFER TO SP PLANS- (WERE NOT
 FOUND)
  
 WATER HEATER
 1. SHEETS P-2.0 & P-3.0 SHOW RELIEF LINE FOR WATER
 HEATER TO OUTSIDE OF BLDG. 504.6 RELIEF DISCHARGE SHALL
 BE THROUGH AN AIR GAP IN THE SAME ROOM AS THE WATER
 HEATER (ALLOWED TO DISCHARGE INTO A HEATER PAN OR AIR
 GAP FITTING).
  
 SANITARY
 2. DENTAL EQUIPTMENT ROOM SHOWS NO DRAINAGE OR WATER
 FOR THE EQUIPTMENT.
  
 *****PROVISOS*****
  
 SHEET A-502
 FBC 11-4.24.2
 SINK COUNTER TOP TO BE A MAXIMUM OF 34" ABOVE FINISHED
 FLOOR.
 A CLEAR FLOOR SPACE OF 48" X 30" IS REQUIRED IN FRONT
 OF SINK.
  
 GRAB BARS ARE TO BE BETWEEN 33"- 36" A.F.F. TO CENTER.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status N Date 2010-12-01 Cont ID  
Sent By aaponte Date 2010-12-01 Time 14:09 Rev Time 0.00
Received By aaponte Date 2010-12-01 Time 14:09 Sent To  
Notes
2010-12-01 14:11:06INTERIOR REMODEL ONLY, INLCUDING FACADE CHANGES.
 LANDSCAPE AND SITE IMPROVEMENTS SHALL BE SUBMITTED
 UNDER SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-10-19 Cont ID  
Sent By aaponte Date 2010-10-19 Time 09:48 Rev Time 0.00
Received By aaponte Date 2010-10-19 Time 09:48 Sent To  
Notes
2010-10-19 09:53:291. A 5 FOOT LANDSCAPE BUFFER IS REQUIRED ALONG THE SIDE
 PROPERTY LINE. SUCH LANDSCAPE SHALL HAVE SHADE TREES
 EVERY 30 LINEAR FEET.
 2. PROPOSED PARKING AREA ON FRONT YARD DOES NOT MEET
 MINIMUM REQUIRED DIMENSIONS FOR 90 DEGREE PARKING OR
 LANDSCAPE BUFFER REQUIREMENTS FOR PARKING AREAS. AN
 ALTERNATIVE LAY OUT SHALL BE PROPOSED TO MEET REQUIRED
 DIMENSIONS AND LANDSCAPE.
 3. FRONT YARD SHALL HAVE A MINIMUM 50% OF VEGETATED
 AREA, AND 30% TREE CANOPY.
 4. A SEPARATE LANDSCAPE AND IRRIGATION PERMITS ARE
 REQUIRED.
 PLEASE CONTACT ANA MARIA APONTE FOR FURTHER DISCUSSION
 ON FAILED ITEMS - 561-822-1439.
  