Plan Review Details - Permit 10100008
Plan Review Stops For Permit 10100008
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-15 Cont ID  
Sent By rmcdouga Date 2010-12-15 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2010-12-10 Time 15:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-22 Cont ID  
Sent By rmcdouga Date 2010-10-22 Time 13:44 Rev Time 0.00
Received By rmcdouga Date 2010-10-21 Time 15:46 Sent To  
Notes
2010-10-21 15:55:092007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PLANS SPECIFY EXPOSURE CATEGORY B. BASED ON FBC
 R301.2.1.4.3 THE STRUCTURE IS LOCATED IN EXPOSURE
 CATEGORY C. PLEASE REVISE THE PLANS. THIS WILL ALSO
 RESULT IN AN INCREASE IN THE COMPONENT AND CLADDING
 PRESSURES. PLEASE REVISE THESE ALSO.
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION FOR THE PRE-FAB
 FIREPLACE, CHIMNEY AND CHIMNEY CAP.
  
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION FOR THE GAS BBQ
 GRILL AT THE COVERED PORCH.
  
 4) PROVIDE DETAILS FOR THE 36" EXTERIOR FIREPLACE
 LOCATED ON THE COVERED PORCH. IS THIS A MASONRY
 FIREPLACE? PLEASE CLARIFY.
  
 5) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED FOR
 THE CONCRETE ROOF TILES BY CIRCLING THE METHOD AND
 MOMENT OF RESISTANCE FROM THE TABLES LISTED IN THE
 TILE'S PRODUCT APPROVAL.
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE TRUSS
 CONNECTORS THAT WILL BE USED AS REQUIRED BY DCA RULE
 9B-72.
  
 8) THE DESIGN PRESSURES FOR THE 2" X HEAVY WALL TUBE
 MULLIONS IN THE PRODUCT APPROVALS SUBMITTED ARE TOO LOW
 FOR USE BETWEEN THE 12 FT WIDE SLIDING GLASS DOORS AND
 THE TRANSOM WINDOWS ABOVE THEM. PLEASE CORRECT.
  
 9) THE PRODUCT APPROVALS FOR THE PGT FD-750 OUTSWING
 ALUMINUM FRENCH DOOR IS EXPIRED. SUBMIT THE CURRENT
 NOAS (09-1028.10).
  
 10) THE PRODUCT APPROVALS FOR THE 9' WIDE AND 16' WIDE
 AMARR GARAGE DOORS HAVE BEEN SUPERSEDED. SUBMIT THE
 CURRENT NOAS (09-0604.03/09-0604.05).
  
 11) THE PRODUCT APPROVALS FOR THE PGT PW-701 FIXED
 WINDOW HAVE BEEN SUPERSEDED. SUBMIT THE CURRENT NOA
 (10-0504.05)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-07 Cont ID  
Sent By shill Date 2010-10-07 Time 18:34 Rev Time 0.00
Received By shill Date 2010-10-07 Time 18:34 Sent To  
Notes
2010-10-07 18:35:08OK PER JOHN DICKINSON LICENSE NUMBER PX 3182

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2010-10-27 Cont ID  
Sent By mgonzale Date 2010-10-27 Time   Rev Time 1.00
Received By mgonzale Date 2010-10-27 Time   Sent To  
Notes
2010-10-27 13:40:15PASSED WITH PROVISO:
  
 #1 NO OBJECTION TO SFR.
 #2 A SEPARATE DRIVEWAY PERMIT IS REQUIRED THRU
 CONSTRUCTION SERVICES DEPARTMENT.
 #3 EASEMENT CONSENT FORM MUST BE PRESENTED COVERING ALL
 THE UTILITIES IN THE UTILITY EASEMENT
 #4 DRIVEWAY AGREEMENT WILL NEED TO BE FILLED, RECORDED
 AND 2 COPIES SUPPLIED WHEN APPLYING FOR PERMIT.
 (I HAVE ATTACHED A COPY FOR YOUR CONVENIENCE)
 #5 PERVIOUS AND IMPERVIOUS CALCULATIONS FOR DRIVEWAY
 AND RESIDENCE WILL NEED TO BE INCLUDED ON PLANS.
  
 FEEL FREE TO CONTACT ME DIRECTLY IF ANY FURTHER
 QUESTIONS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By rmcdouga Date 2010-10-19 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2010-10-19 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-11-30 Cont ID  
Sent By jwitmer Date 2010-11-30 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2010-11-30 Time 11:21 Sent To  
Notes
2010-11-30 11:22:203RD RESUB INCOMING SENT TO R-19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-18 Cont ID  
Sent By lmartine Date 2010-11-15 Time 08:32 Rev Time 0.00
Received By lmartine Date 2010-11-15 Time 08:32 Sent To  
Notes
2010-11-18 08:48:51R--19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-18 Cont ID  
Sent By lmartine Date 2010-10-27 Time 08:31 Rev Time 0.00
Received By lmartine Date 2010-10-04 Time 10:21 Sent To  
Notes
2010-10-04 10:21:15SENT TO R3.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By rmcdouga Date 2010-10-19 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2010-10-19 Time 15:10 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-12-08 Cont ID  
Sent By rkussner Date 2010-12-08 Time 17:35 Rev Time 0.00
Received By rkussner Date 2010-12-08 Time 17:35 Sent To  
Notes
2010-12-08 17:37:52****LANDSCAPE REVIEW PASSED WITH 'PROVISO'***
  
 MUST APPLY FOR A LANDSCAPE PERMIT AND GET IT APPROVED
 PRIOR TO FIRST INSPECTION.---RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-10-25 Cont ID  
Sent By rkussner Date 2010-10-25 Time 12:01 Rev Time 0.00
Received By rkussner Date 2010-10-25 Time 12:01 Sent To  
Notes
2010-10-25 12:06:35***LANSDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT
 AN APPLICATION, TWO (2) SETS OF LANDSCAPE PLANS AND A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED. PLEASE
 SUBMIT AN APPLICATION AND TWO (2) SETS OF IRRIGATION
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-10-20 Cont ID  
Sent By rmcdouga Date 2010-10-20 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2010-10-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By rmcdouga Date 2010-10-19 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2010-10-19 Time 15:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-12-08 Cont ID  
Sent By lfranco Date 2010-12-08 Time 16:05 Rev Time 0.00
Received By lfranco Date 2010-12-08 Time 16:05 Sent To B
Notes
2010-12-08 16:07:53PLANNING AND ZONING: **** PASSED WITH PROVISO - A
 SEPARATE DRIVEWAY PERMIT IS REQUIRED PRIOR TO FINAL
 INSPECTION OF THE HOME. COMPLIANCE WITH THE ITEMS BELOW
 IS REQUIRED. *****
  
 1. RESPOND TO COMMENTS IN WRITING. RESUBMITTAL MAY
 GENERATE ADDITIONAL COMMENTS.
  
 2. PURSUANT TO SECTION 94-72(A)(3) ZLDR, THE MAXIMUM
 BUILDING HEIGHT IS 30 FEET. SECTION 94-306, HEIGHT
 EXCEPTIONS ALLOWS FOR DECORATIVE FEATURES (I.E.
 PROPOSED TOWER-LIKE FEATURE), BUT MAY NOT EXCEED MORE
 THAN TEN PERCENT (10%) OF THE ALLOWED MAXIMUM HEIGHT OF
 30 FEET. REVISE SHEET A-5, ELEVATIONS ACCORDINGLY.
  
 A SEPARATE DRIVEWAY PERMIT IS REQUIRED PRIOR TO FINAL
 INSPECTION OF HOME. COMPLIANCE WITH THE ITEMS BELOW IS
 REQUIRED. ****
  
 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES
 (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD
 (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING
 FACADE).
  
 4. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY
 EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE
 FOLLOWING UTILITY COMPANIES:
  
 WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT
 401 CLEMATIS STREET
 CITY HALL, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (561)822-1300
  
 FLORIDA POWER AND LIGHT
 810 CHARLOTTE AVE
 WEST PALM BEACH, FL 33401
 (561)697-8000
  
 FLORIDA PUBLIC UTILITIES
 401 SOUTH DIXIE HWY
 WEST PALM BEACH, FL 33402
 (561)832-2461
  
 BELL SOUTH
 2021 SOUTH MILITARY TRAIL
 WEST PALM BEACH, FL 33415
 (561)439-9110
  
 COMCAST
 1401 NORTHPOINT PKWY
 WEST PALM BEACH, FL 33407
 (561)655-3842 - RESIDENTIAL
 (561)227-4261 - COMMERCIAL
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2010-11-18 Cont ID  
Sent By lfranco Date 2010-11-18 Time 18:48 Rev Time 0.00
Received By lfranco Date 2010-11-18 Time 18:48 Sent To  
Notes
2010-11-18 18:58:01PLANNING AND ZONING: ****
  
 1. RESPOND TO COMMENTS IN WRITING. RESUBMITTAL MAY
 GENERATE ADDITIONAL COMMENTS.
  
 2. PURSUANT TO SECTION 94-72(A)(3) ZLDR, THE MAXIMUM
 BUILDING HEIGHT IS 30 FEET. SECTION 94-306, HEIGHT
 EXCEPTIONS ALLOWS FOR DECORATIVE FEATURES (I.E.
 PROPOSED TOWER-LIKE FEATURE), BUT MAY NOT EXCEED MORE
 THAN TEN PERCENT (10%) OF THE ALLOWED MAXIMUM HEIGHT OF
 30 FEET. REVISE SHEET A-5, ELEVATIONS ACCORDINGLY.
  
 A SEPARATE DRIVEWAY PERMIT WILL BE REQUIRED PRIOR TO
 FINAL INSPECTION OF HOME. COMPLIANCE WITH THE ITEMS
 BELOW WILL BE REQUIRED. ****
  
 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES
 (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD
 (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING
 FACADE).
  
 4. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY
 EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE
 FOLLOWING UTILITY COMPANIES:
  
 WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT
 401 CLEMATIS STREET
 CITY HALL, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (561)822-1300
  
 FLORIDA POWER AND LIGHT
 810 CHARLOTTE AVE
 WEST PALM BEACH, FL 33401
 (561)697-8000
  
 FLORIDA PUBLIC UTILITIES
 401 SOUTH DIXIE HWY
 WEST PALM BEACH, FL 33402
 (561)832-2461
  
 BELL SOUTH
 2021 SOUTH MILITARY TRAIL
 WEST PALM BEACH, FL 33415
 (561)439-9110
  
 COMCAST
 1401 NORTHPOINT PKWY
 WEST PALM BEACH, FL 33407
 (561)655-3842 - RESIDENTIAL
 (561)227-4261 - COMMERCIAL
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-10-26 Cont ID  
Sent By lfranco Date 2010-10-26 Time 10:38 Rev Time 0.00
Received By lfranco Date 2010-10-26 Time 10:38 Sent To ENG
Notes
2010-10-26 10:58:35PLANNING AND ZONING: **** FAILED ****
  
  
 1. PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE PROPOSED BUILDING (STRUCTURE) ON THE SURVEY
 DEPICTING DIMENSIONS TO ALL PROPERTY LINES. ALL
 SETBACKS SHALL MEET THE IBIS RESIDENTIAL PLANNED
 DEVELOPMENT ("RPD") SETBACK REQUIREMENTS.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED
 A/C/MECHANICAL EQUIPMENT TO ALL PROPERTY LINES.
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 4. A SEPARATE PERMIT FOR THE PROPOSED DRIVEWAY WILL BE
 REQUIRED.
  
 5. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY
 EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE
 FOLLOWING UTILITY COMPANIES:
  
 WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT
 401 CLEMATIS STREET
 CITY HALL, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (561)822-1300
  
 FLORIDA POWER AND LIGHT
 810 CHARLOTTE AVE
 WEST PALM BEACH, FL 33401
 (561)697-8000
  
 FLORIDA PUBLIC UTILITIES
 401 SOUTH DIXIE HWY
 WEST PALM BEACH, FL 33402
 (561)832-2461
  
 BELL SOUTH
 2021 SOUTH MILITARY TRAIL
 WEST PALM BEACH, FL 33415
 (561)439-9110
  
 COMCAST
 1401 NORTHPOINT PKWY
 WEST PALM BEACH, FL 33407
 (561)655-3842 - RESIDENTIAL
 (561)227-4261 - COMMERCIAL
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  
  