| Plan Review Stops For Permit 10100008 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-12-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-12-15 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-12-10 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-10-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-22 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-10-21 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2010-10-21 15:55:09 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE PLANS SPECIFY EXPOSURE CATEGORY B. BASED ON FBC | | | R301.2.1.4.3 THE STRUCTURE IS LOCATED IN EXPOSURE | | | CATEGORY C. PLEASE REVISE THE PLANS. THIS WILL ALSO | | | RESULT IN AN INCREASE IN THE COMPONENT AND CLADDING | | | PRESSURES. PLEASE REVISE THESE ALSO. | | | | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND LISTING INFORMATION FOR THE PRE-FAB | | | FIREPLACE, CHIMNEY AND CHIMNEY CAP. | | | | | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND LISTING INFORMATION FOR THE GAS BBQ | | | GRILL AT THE COVERED PORCH. | | | | | | 4) PROVIDE DETAILS FOR THE 36" EXTERIOR FIREPLACE | | | LOCATED ON THE COVERED PORCH. IS THIS A MASONRY | | | FIREPLACE? PLEASE CLARIFY. | | | | | | 5) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED FOR | | | THE CONCRETE ROOF TILES BY CIRCLING THE METHOD AND | | | MOMENT OF RESISTANCE FROM THE TABLES LISTED IN THE | | | TILE'S PRODUCT APPROVAL. | | | | | | 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE TRUSS | | | CONNECTORS THAT WILL BE USED AS REQUIRED BY DCA RULE | | | 9B-72. | | | | | | 8) THE DESIGN PRESSURES FOR THE 2" X HEAVY WALL TUBE | | | MULLIONS IN THE PRODUCT APPROVALS SUBMITTED ARE TOO LOW | | | FOR USE BETWEEN THE 12 FT WIDE SLIDING GLASS DOORS AND | | | THE TRANSOM WINDOWS ABOVE THEM. PLEASE CORRECT. | | | | | | 9) THE PRODUCT APPROVALS FOR THE PGT FD-750 OUTSWING | | | ALUMINUM FRENCH DOOR IS EXPIRED. SUBMIT THE CURRENT | | | NOAS (09-1028.10). | | | | | | 10) THE PRODUCT APPROVALS FOR THE 9' WIDE AND 16' WIDE | | | AMARR GARAGE DOORS HAVE BEEN SUPERSEDED. SUBMIT THE | | | CURRENT NOAS (09-0604.03/09-0604.05). | | | | | | 11) THE PRODUCT APPROVALS FOR THE PGT PW-701 FIXED | | | WINDOW HAVE BEEN SUPERSEDED. SUBMIT THE CURRENT NOA | | | (10-0504.05) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-10-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-10-07 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-10-07 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2010-10-07 18:35:08 | OK PER JOHN DICKINSON LICENSE NUMBER PX 3182 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2010-10-27 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2010-10-27 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2010-10-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2010-10-27 13:40:15 | PASSED WITH PROVISO: | | | | | | #1 NO OBJECTION TO SFR. | | | #2 A SEPARATE DRIVEWAY PERMIT IS REQUIRED THRU | | | CONSTRUCTION SERVICES DEPARTMENT. | | | #3 EASEMENT CONSENT FORM MUST BE PRESENTED COVERING ALL | | | THE UTILITIES IN THE UTILITY EASEMENT | | | #4 DRIVEWAY AGREEMENT WILL NEED TO BE FILLED, RECORDED | | | AND 2 COPIES SUPPLIED WHEN APPLYING FOR PERMIT. | | | (I HAVE ATTACHED A COPY FOR YOUR CONVENIENCE) | | | #5 PERVIOUS AND IMPERVIOUS CALCULATIONS FOR DRIVEWAY | | | AND RESIDENCE WILL NEED TO BE INCLUDED ON PLANS. | | | | | | FEEL FREE TO CONTACT ME DIRECTLY IF ANY FURTHER | | | QUESTIONS. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2010-10-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-19 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-10-19 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-11-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-11-30 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-11-30 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2010-11-30 11:22:20 | 3RD RESUB INCOMING SENT TO R-19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-11-18 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-11-15 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-11-15 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-11-18 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-10-27 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-10-04 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2010-10-04 10:21:15 | SENT TO R3. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2010-10-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-19 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-10-19 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2010-12-08 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-12-08 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-12-08 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2010-12-08 17:37:52 | ****LANDSCAPE REVIEW PASSED WITH 'PROVISO'*** | | | | | | MUST APPLY FOR A LANDSCAPE PERMIT AND GET IT APPROVED | | | PRIOR TO FIRST INSPECTION.---RAK |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2010-10-25 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-10-25 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-10-25 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2010-10-25 12:06:35 | ***LANSDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT | | | AN APPLICATION, TWO (2) SETS OF LANDSCAPE PLANS AND A | | | CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF | | | ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO | | | UNIT COST. | | | | | | 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED. PLEASE | | | SUBMIT AN APPLICATION AND TWO (2) SETS OF IRRIGATION | | | PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-20 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-10-20 |
Time |
11:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-10-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-19 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-10-19 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2010-12-08 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2010-12-08 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2010-12-08 |
Time |
16:05 |
Sent To |
B |
|
| Notes |
| 2010-12-08 16:07:53 | PLANNING AND ZONING: **** PASSED WITH PROVISO - A | | | SEPARATE DRIVEWAY PERMIT IS REQUIRED PRIOR TO FINAL | | | INSPECTION OF THE HOME. COMPLIANCE WITH THE ITEMS BELOW | | | IS REQUIRED. ***** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. RESUBMITTAL MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | 2. PURSUANT TO SECTION 94-72(A)(3) ZLDR, THE MAXIMUM | | | BUILDING HEIGHT IS 30 FEET. SECTION 94-306, HEIGHT | | | EXCEPTIONS ALLOWS FOR DECORATIVE FEATURES (I.E. | | | PROPOSED TOWER-LIKE FEATURE), BUT MAY NOT EXCEED MORE | | | THAN TEN PERCENT (10%) OF THE ALLOWED MAXIMUM HEIGHT OF | | | 30 FEET. REVISE SHEET A-5, ELEVATIONS ACCORDINGLY. | | | | | | A SEPARATE DRIVEWAY PERMIT IS REQUIRED PRIOR TO FINAL | | | INSPECTION OF HOME. COMPLIANCE WITH THE ITEMS BELOW IS | | | REQUIRED. **** | | | | | | 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED | | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | | | | | INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES | | | (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD | | | (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING | | | FACADE). | | | | | | 4. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY | | | EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE | | | FOLLOWING UTILITY COMPANIES: | | | | | | WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT | | | 401 CLEMATIS STREET | | | CITY HALL, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (561)822-1300 | | | | | | FLORIDA POWER AND LIGHT | | | 810 CHARLOTTE AVE | | | WEST PALM BEACH, FL 33401 | | | (561)697-8000 | | | | | | FLORIDA PUBLIC UTILITIES | | | 401 SOUTH DIXIE HWY | | | WEST PALM BEACH, FL 33402 | | | (561)832-2461 | | | | | | BELL SOUTH | | | 2021 SOUTH MILITARY TRAIL | | | WEST PALM BEACH, FL 33415 | | | (561)439-9110 | | | | | | COMCAST | | | 1401 NORTHPOINT PKWY | | | WEST PALM BEACH, FL 33407 | | | (561)655-3842 - RESIDENTIAL | | | (561)227-4261 - COMMERCIAL | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2010-11-18 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2010-11-18 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2010-11-18 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2010-11-18 18:58:01 | PLANNING AND ZONING: **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. RESUBMITTAL MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | 2. PURSUANT TO SECTION 94-72(A)(3) ZLDR, THE MAXIMUM | | | BUILDING HEIGHT IS 30 FEET. SECTION 94-306, HEIGHT | | | EXCEPTIONS ALLOWS FOR DECORATIVE FEATURES (I.E. | | | PROPOSED TOWER-LIKE FEATURE), BUT MAY NOT EXCEED MORE | | | THAN TEN PERCENT (10%) OF THE ALLOWED MAXIMUM HEIGHT OF | | | 30 FEET. REVISE SHEET A-5, ELEVATIONS ACCORDINGLY. | | | | | | A SEPARATE DRIVEWAY PERMIT WILL BE REQUIRED PRIOR TO | | | FINAL INSPECTION OF HOME. COMPLIANCE WITH THE ITEMS | | | BELOW WILL BE REQUIRED. **** | | | | | | 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED | | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | | | | | INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES | | | (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD | | | (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING | | | FACADE). | | | | | | 4. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY | | | EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE | | | FOLLOWING UTILITY COMPANIES: | | | | | | WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT | | | 401 CLEMATIS STREET | | | CITY HALL, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (561)822-1300 | | | | | | FLORIDA POWER AND LIGHT | | | 810 CHARLOTTE AVE | | | WEST PALM BEACH, FL 33401 | | | (561)697-8000 | | | | | | FLORIDA PUBLIC UTILITIES | | | 401 SOUTH DIXIE HWY | | | WEST PALM BEACH, FL 33402 | | | (561)832-2461 | | | | | | BELL SOUTH | | | 2021 SOUTH MILITARY TRAIL | | | WEST PALM BEACH, FL 33415 | | | (561)439-9110 | | | | | | COMCAST | | | 1401 NORTHPOINT PKWY | | | WEST PALM BEACH, FL 33407 | | | (561)655-3842 - RESIDENTIAL | | | (561)227-4261 - COMMERCIAL | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-10-26 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2010-10-26 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2010-10-26 |
Time |
10:38 |
Sent To |
ENG |
|
| Notes |
| 2010-10-26 10:58:35 | PLANNING AND ZONING: **** FAILED **** | | | | | | | | | 1. PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 2. PROVIDE PROPOSED BUILDING (STRUCTURE) ON THE SURVEY | | | DEPICTING DIMENSIONS TO ALL PROPERTY LINES. ALL | | | SETBACKS SHALL MEET THE IBIS RESIDENTIAL PLANNED | | | DEVELOPMENT ("RPD") SETBACK REQUIREMENTS. | | | | | | 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED | | | A/C/MECHANICAL EQUIPMENT TO ALL PROPERTY LINES. | | | PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. | | | | | | 4. A SEPARATE PERMIT FOR THE PROPOSED DRIVEWAY WILL BE | | | REQUIRED. | | | | | | 5. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY | | | EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE | | | FOLLOWING UTILITY COMPANIES: | | | | | | WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT | | | 401 CLEMATIS STREET | | | CITY HALL, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (561)822-1300 | | | | | | FLORIDA POWER AND LIGHT | | | 810 CHARLOTTE AVE | | | WEST PALM BEACH, FL 33401 | | | (561)697-8000 | | | | | | FLORIDA PUBLIC UTILITIES | | | 401 SOUTH DIXIE HWY | | | WEST PALM BEACH, FL 33402 | | | (561)832-2461 | | | | | | BELL SOUTH | | | 2021 SOUTH MILITARY TRAIL | | | WEST PALM BEACH, FL 33415 | | | (561)439-9110 | | | | | | COMCAST | | | 1401 NORTHPOINT PKWY | | | WEST PALM BEACH, FL 33407 | | | (561)655-3842 - RESIDENTIAL | | | (561)227-4261 - COMMERCIAL | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | | | | | | | | | | |
|
|