Plan Review Details - Permit 10090847
Plan Review Stops For Permit 10090847
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-10-13 Cont ID  
Sent By mcarsill Date 2010-10-13 Time 12:27 Rev Time 0.00
Received By mcarsill Date 2010-10-13 Time 12:18 Sent To  
Notes
2010-10-13 12:26:581217 SOUTH FLAGLER DRIVE
 PERMIT NUMBER 10090847
 'REPLACEMENT OF SPRINKLER UNDER BUILDING - PARKING
 FACILITY"
  
  
 1. ON OCTOBER 13, 2010, THIS WRITER CONTACTED ROY ZIEK
 OF JOHN W. POLHEMUS BY TELEPHONE. WE DISCUSSED IF AN
 EXISTING FIRE DEPARTMENT CONNECTION (FDC) IS AVAILABLE.
 MR. ZIEK IS TO VERIFY EXISTING FIRE DEPARTMENT
 CONNECTION.
  
 2. THE EXISTING FIRE DEPARTMENT CONNECTION SHOULD
 INSPECTED TO DETERMINE IF IT IS OPERATIONAL, EQUIPPED
 WITH CAPS, AND DO THE HOSE CONNECTIONS SWIVEL.
  
 3. THE WORK DISPLAYED ON THE PLANS IS A LIKE FOR LIKE
 REPLACEMENT EXCEPT FOR CORROSION RESISTANT PIPING AND
 FIRE SPRINKLER HEADS.
  
 4. THE NEW FIRE SPRINKLER PIPING IS TO BE PRESSURE
 TESTED AT 200 PSI FOR 2 HOURS AND WITNESSED BY THIS
 OFFICE.
  
 5. INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13,
 2002 EDITION.
  
 6. THE FIRE SPRINKLER SYSTEM SHALL BE INSPECTED AND
 APPROVED BY THIS OFFICE AFTER INSTALLATION.
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-21 Cont ID  
Sent By hmoser Date 2010-10-21 Time 12:31 Rev Time 0.00
Received By hmoser Date 2010-09-30 Time 16:39 Sent To  
Notes
2010-09-30 16:40:06IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-10-21 Cont ID  
Sent By hmoser Date 2010-10-21 Time 12:31 Rev Time 0.00
Received By hmoser Date 2010-10-21 Time 12:31 Sent To  
Notes
***NONE***