Plan Review Details - Permit 10090836
| Plan Review Stops For Permit 10090836 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-10-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-10-04 |
Time |
12:00 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
2010-10-04 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2010-10-04 12:47:52 | BUILDING PROVISO: | | | CONTRACTOR IS TO SUBMIT TO THE INSPECTOR INSTALATION | | | INSSTRUCTIONS FOR ONE HOUR RATED FRAME AND FIRE | | | CAULKING DETAILS OF FRAME TO CONCRETE WALL. 106.1.2 | | | ADDITIONAL INFORMATION REQUIRED. 715.4 FIRE DOOR AND | | | SHUTTER ASSEMBLIES. APPROVED FIRE DOOR AND FIRE SHUTTER | | | ASSEMBLIES SHALL BE CONSTRUCTED OF ANY MATERIAL OR | | | ASSEMBLY OF COMPONENT MATERIALS THAT CONFORMS TO THE | | | TEST REQUIREMENTS OF SECTION 715.4.1, 715.4.2 OR | | | 715.4.3 AND THE FIRE-PROTECTION RATING INDICATED IN | | | TABLE 715.4. FIRE DOOR ASSEMBLIES AND SHUTTERS SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS | | | SECTION AND NFPA 80. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-10-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-10-04 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-10-04 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2010-10-04 17:06:46 | OK PER JOHN DICKINSON CONTRACT PLAN REVIEWE LICENSE | | | NUMBER PX3182 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-10-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-10-07 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-10-07 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2010-10-07 15:26:41 | 215 NORTH OLIVE AVENUE | | | PERMIT NUMBER 10090836 | | | "PROVIDE NEW DOOR FOR SECURITY ACCESS FOR EVIDENCE | | | STORAGE ROOM" | | | | | | | | | 1. THE INSTALLATION OF THE CARD READER SHALL NOT | | | INTERFERE WITH ANY EXITING. | | | | | | 2. NEW FIRE RATED DOOR AND FRAME TO BE INSTALLED IN | | | ACCORDANCE WITH NFPA 80, THE STANDARD FOR FIRE DOORS | | | AND WINDOWS. | | | | | | 3. PLANS DO NOT INDICATE IF ANY EXIT SIGNS OR EMERGENCY | | | LIGHT FIXTURES EXIST WITHIN CLOSE PROXIMITY OF THE NEW | | | DOOR. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-10-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-10-07 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-10-01 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
|