Plan Review Details - Permit 10090780
Plan Review Stops For Permit 10090780
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-12-13 Cont ID  
Sent By jwitmer Date 2010-12-13 Time 11:57 Rev Time 0.35
Received By jwitmer Date 2010-12-13 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-12-03 Cont ID  
Sent By jwitmer Date 2010-12-03 Time 11:25 Rev Time 0.50
Received By jwitmer Date 2010-11-18 Time 09:53 Sent To  
Notes
2010-11-18 09:53:58CALLED CONTRACTOR TO SUPPLY UPDATE PAGES WILL KEEP
 PLANS AT MY DESK JW (11/18/2010)
  
 12/03/2010 FAILED MISSING IN ONE SET A-6.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-04 Cont ID  
Sent By jwitmer Date 2010-10-04 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2010-10-04 Time 11:07 Sent To  
Notes
2010-10-04 10:20:01BUILDING PLAN REVIEW
 PERMIT: 10090780
 ADD: 31111 45TH ST
 CONT: HARTZELL CONSTRUCTION
 TEL: (954)658-0570
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1.2 NOTE# 8 INDICATES THE USE OF A DOORBELL
 AT THE FRONT DOOR AND ANNUCIATOR IN THE STORAGE ROOM.
 IT APPEARS WITH THIS NOTE THE FRONT EGRESS DOOR IS TO
 BE LOCKED DURING OPERATING HOURS. PLEASE PROVIDE
 COMPLIANCE WITH THE 2007 FBC-B 1008.1.3.4
 ACCESS-CONTROLLED EGRESS DOORS. THE ENTRANCE DOORS IN A
 MEANS OF EGRESS IN BUILDINGS WITH AN OCCUPANCY IN GROUP
 A, B, D, E, M, R-1 OR R-2 AND ENTRANCE DOORS TO TENANT
 SPACES IN OCCUPANCIES IN GROUPS A, B, D, E, M, R-1 AND
 R-2 ARE PERMITTED TO BE EQUIPPED WITH AN APPROVED
 ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM WHICH SHALL
 BE INSTALLED IN ACCORDANCE WITH ALL OF THE FOLLOWING
 CRITERIA:
  
 1.1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE
 ARRANGED TO DETECT AN OCCUPANT APPROACHING THE DOORS.
 THE DOORS SHALL BE ARRANGED TO UNLOCK BY A SIGNAL FROM
 OR LOSS OF POWER TO THE SENSOR.
  
 1.2. LOSS OF POWER TO THAT PART OF THE ACCESS CONTROL
 SYSTEM WHICH LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS.
  
 1.3. THE DOORS SHALL BE ARRANGED TO UNLOCK FROM A
 MANUAL UNLOCKING DEVICE LOCATED 40 INCHES TO 48 INCHES
 (1016 MM TO 1219 MM) VERTICALLY ABOVE THE FLOOR AND
 WITHIN 5 FEET (1524 MM) OF THE SECURED DOORS. READY
 ACCESS SHALL BE PROVIDED TO THE MANUAL UNLOCKING DEVICE
 AND THE DEVICE SHALL BE CLEARLY IDENTIFIED BY A SIGN
 THAT READS "PUSH TO EXIT." WHEN OPERATED, THE MANUAL
 UNLOCKING DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF
 POWER TO THE LOCK???INDEPENDENT OF THE ACCESS CONTROL
 SYSTEM ELECTRONICS???AND THE DOORS SHALL REMAIN
 UNLOCKED FOR A MINIMUM OF 30 SECONDS.
  
 1.4. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOORS, AND THE
 DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RESET.
  
 1.5. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOORS. THE DOORS SHALL REMAIN UNLOCKED UNTIL
 THE FIRE ALARM SYSTEM HAS BEEN RESET.
  
 1.6. ENTRANCE DOORS IN BUILDINGS WITH AN OCCUPANCY IN
 GROUP A, B, E OR M SHALL NOT BE SECURED FROM THE EGRESS
 SIDE DURING PERIODS THAT THE BUILDING IS OPEN TO THE
 GENERAL PUBLIC.
  
 2) PLEASE CORRECT THE DISCREPANCY LOCATED WWITHIN THE
 PLANS. THE COVERSHEET UNDER THE HEADING BUILDING DATA
 INDICATES THE BUILDING IS NON-SPRINKLERED.
 WHEREAS SHEET A1.1 CEILING PLAN NOTE# 6 & 8 BOTH
 INDICATE THE USE OF A FULLY SPRINKLERED BUILDING.
 106.1.2 ADDITIONAL INFORMATION REQUIED.
  
 3) THE COVERSHEET INDICATES UNDER THE BUILDING DATA THE
 OCCUPANCY CLASSIFICATION AS BUSINESS/ MERCANTILE
 OCCUPANCY. PLEASE PROVIDE 508.3.1AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PER CENT OF
 THE AREA OF THE STORY IN WHICH THEY ARE LOCATED AND NOT
 EXCEED THE TABULAR VALUES IN TABLE 503, WITHOUT HEIGHT
 AND AREA INCREASES IN ACCORDANCE WITH 504 & 506 FOR
 SUCH OCCUPANCIES, EXCEPTIONS DO NOT APPLY. ALSO REVIEW
 2007 FBC-B 508.3. MIXED OCCUPANCIES .
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-04 Cont ID  
Sent By jwitmer Date 2010-10-04 Time 18:55 Rev Time 0.00
Received By jwitmer Date 2010-10-04 Time 18:55 Sent To  
Notes
2010-10-04 18:56:58OK PER JOHN DICKINSON CONTRACT PL;AN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 14:41 Rev Time 0.00
Received By wjolin Date 2010-12-16 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-11-12 Cont ID  
Sent By wjolin Date 2010-11-12 Time 12:14 Rev Time 0.00
Received By wjolin Date 2010-11-12 Time 12:05 Sent To  
Notes
2010-11-12 12:11:383111 45TH STREET
 PERMIT #10090780
  
 REVIEW COMMENTS - FIRE
  
 1) REPEAT COMMENT: SHEET M3 SECTION 2.04 REFERS TO A
 NEW FIRE SPRINKLER SYSTEM WHILE COVER SHEET SHOWS
 BUILDING AS NON-SPRINKLERED.
  
 2) REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT EXIT
 DOORS.
  
 3) REPEAT COMMENT: PROVIDE PORTABLE FIRE EXTINGUISHERS.
 SHOW LOCATION AND TYPE OF EXTINGUISHER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-18 Cont ID  
Sent By mcarsill Date 2010-10-18 Time 14:34 Rev Time 0.00
Received By mcarsill Date 2010-10-18 Time 14:18 Sent To  
Notes
2010-10-18 14:34:083111-45TH STREET
 PERMIT NUMBER 10090780
 "TENANT IMPROVEMENT"
  
  
 1. PLAN SHEETS CONFLICT IN SOME INSTANCES. ON ONE SHEET
 IT INDICATES THAT FIRE SPRINKLERS ARE PRESENT AND ON
 ANOTHER IT INDICATES THAT NO FIRE SPRINKLER EXIST.
 PLEASE CORRELATE INFORMATION.
  
 2. ANOTHER EXIT SIGN IS NEEDED NEAR ROW OF D20 LIGHT
 FIXTURES TO DIRECT PERSONS THROUGH DOORWAY.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PLANS DO NOT ILLUSTRATE PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 14:40 Rev Time 0.00
Received By wjolin Date 2010-12-07 Time 08:27 Sent To  
Notes
2010-12-07 08:27:30B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-28 Cont ID  
Sent By lmartine Date 2010-10-28 Time 16:04 Rev Time 0.00
Received By lmartine Date 2010-10-28 Time 16:04 Sent To  
Notes
2010-10-28 16:20:52B--2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-23 Cont ID  
Sent By lmartine Date 2010-10-18 Time 12:09 Rev Time 0.00
Received By lmartine Date 2010-09-30 Time 13:56 Sent To  
Notes
2010-09-30 13:56:58B--1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-12-13 Cont ID  
Sent By jwitmer Date 2010-12-13 Time 11:57 Rev Time 0.12
Received By jwitmer Date 2010-12-13 Time 11:57 Sent To  
Notes
2010-12-13 11:58:30NEW M-3 SHEET, JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-11-15 Cont ID  
Sent By hmoser Date 2010-11-15 Time 10:47 Rev Time 0.00
Received By hmoser Date 2010-11-15 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-10-06 Cont ID  
Sent By hmoser Date 2010-10-06 Time 11:09 Rev Time 0.00
Received By hmoser Date 2010-10-06 Time 10:18 Sent To P
Notes
2010-10-06 11:24:51PLANS DENIED
 1) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR
 EXCEPTION #3 FOR ROOM 104
 2) PLEASE PROVIDE RETURN AIR SIZE FOR ROOMS 102 ,103 ON
 THE PLANS.
 3) PLEASE INDICATE ON THE PLANS IF THE RETURN IS DUCTED
 OR CEILING PLENUM .
 4) PROVIDE FRESH AIR CALCULATIONS IN THE PLAN .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-11-09 Cont ID  
Sent By lwagner Date 2010-11-09 Time 12:58 Rev Time 0.00
Received By lwagner Date 2010-11-09 Time 10:59 Sent To  
Notes
2010-11-09 12:56:20****NOTE****
  
 SHEET A-1
 THE DOOR TO ROOM 107 LOOKS TO BE INTERFERING WITH THE
 USE OF THE DRINKING FOUNTAIN. THE DOOR COULD BE MOVED
 DOWN THE WALL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-07 Cont ID  
Sent By lwagner Date 2010-10-07 Time 08:20 Rev Time 0.00
Received By lwagner Date 2010-10-07 Time 07:38 Sent To  
Notes
2010-10-07 08:29:18FBC PLUMBING 2007 PLUMBING PLAN REVIEW
 DENIED:
  
 1. FBC PLUMBING 403.1 MINIMUN PLUMBING FACILITIES
 FBC PLUMBING 410.1 DRINKING FOUNTAINS
 A DRINKING FOUNTAIN IS REQUIRED IN BUSINESS &
 MERCANTILE OCCUPANCIES.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-10-15 Cont ID  
Sent By astelly Date 2010-10-15 Time 07:03 Rev Time 0.00
Received By astelly Date 2010-10-15 Time 07:03 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy