Plan Review Details - Permit 10090778
Plan Review Stops For Permit 10090778
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-01 Cont ID  
Sent By jleahy Date 2010-10-01 Time 14:33 Rev Time 0.00
Received By jleahy Date 2010-10-01 Time 14:33 Sent To  
Notes
2010-10-01 14:34:06PASSED BASED ON PLAN WILL CHECK NEW WHEN RESUBED JL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-22 Cont ID  
Sent By wjolin Date 2010-11-22 Time 14:19 Rev Time 0.00
Received By wjolin Date 2010-11-22 Time 12:42 Sent To  
Notes
2010-11-22 14:19:044295 45TH STREET
 SAM'S CLUB (CLASS A - MERCANTILE)
 PERMIT #10090778
 MASTER #09070775
  
  
 SHEET EFP2: REVISE BOTH MATRICIES (SEQUENCE OF
 OPERATIONS & POINT TYPE) TO HAVE THE DUCT SMOKE
 DETECTORS ACTIVATE THE GENERAL FIRE ALARM SYSTEM AND
 TRANSMIT AN ALARM SIGNAL TO THE MONITORING COMPANY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By mcarsill Date 2010-10-01 Time 13:54 Rev Time 0.00
Received By mcarsill Date 2010-10-01 Time 13:33 Sent To  
Notes
2010-10-01 13:54:034295-45TH STREET
 PERMIT NUMBER 10090778
 " PROVIDE A NEW FIRE ALARM SYSTEM WITH FULL
 NOTIFICATION THROUGHOUT BUILDING"
  
 1. THE ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, 2002 EDITION.
  
 2. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
 OPERATIONAL UNTIL SUCH TIME AS THE NEW FIRE ALARM
 SYSTEM IS INSTALLED, INSPECTED, TESTED, AND APPROVED BY
 CITY OFFICIALS.
  
 3. ANY TIME THE REQUIRED FIRE ALARM SYSTEM IS OUT OF
 SERVICE FOR MORE THAN 4 HOURS IN A TWENTY FOUR HOUR
 PERIOD, A FIRE WATCH IS REQUIRED. ALL FIRE WATCH
 ACTIVITIES SHALL BE IN WRITING TO THE BATTALION CHIEF
 OF FIRE PREVENTION OR HIS DESIGNEE. FIRE WATCH
 PERSONNEL SHALL HAVE NO OTHER DUTIES EXCEPT TO REPORT
 EMERGENCIES. THEY SHALL BE RADIO OR CELLULAR TELEPHONE
 EQUIPPED AND A LOG MAINTAINED.
  
 4. ACCORDING TO LOCAL POLICY, DUCT DETECTORS WHEN
 ACTIVATED SHALL ACTIVATE THE FIRE ALARM SYSTEM NOT A
 SUPERVISORY SIGNAL.
  
 5. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 6. PLEASE INDICATE CIRCUITS FOR SIGNALING AND
 INITIATING APPLIANCES ON THE FLOOR PLAN.
  
 7. IS THERE ANY FIRE ALARM DEVICES PLANNED FOR THE
 REMODELED TIRE AND BATTERY STORAGE AREA AND THE
 REFRIGERATION MECHANICAL CENTER OR THE EXISTING
 DEHUMIDIFIER AREAS.
  
 8. NOTE # 12 AND 13 ARE CROPPED OFF ON SHEET EFP2.
  
 9. THE FIRE ALARM SYSTEM WHEN ACTIVATED SHALL PROVIDE
 FOR ADEQUATE AUDIBILITY THROUGHOUT THE STORE. ENOUGH
 VISUAL DEVICES SHALL BE PROVIDED THROUGHOUT THE STORE.
  
 10. SIGNALS TO BE PROVIDED TO THE CENTRAL STATION
 INCLUDE WATERFLOW, GENERAL ALARM, SUPERVISORY, AND
 TROUBLE SIGNALS.
  
 11. PLEASE ADD NOTES TO THE PLANS TO REFLECT THE ABOVE
 INFORMATION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-04 Cont ID  
Sent By lmartine Date 2010-11-04 Time 13:53 Rev Time 0.00
Received By lmartine Date 2010-11-04 Time 13:53 Sent To  
Notes
2010-11-04 14:13:44IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-29 Cont ID  
Sent By jwitmer Date 2010-09-29 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2010-09-29 Time 10:18 Sent To  
Notes
2010-09-29 10:19:04INCOMING SENT TO FIRE BOX