| 2010-10-01 13:03:27 | 6001 VILLAGE BOULEVARD |
| | PERMIT NUMBER 10090773 |
| | "REPLACE EXISTING FIRE ALARM SYSTEM" |
| | |
| | 1. THE EXISTING FIRE ALARM SYSTEM IS TO REMAIN |
| | OPERATIONAL UNTIL SUCH TIME AS THE NEW FIRE ALARM |
| | SYSTEM HAS BEEN INSTALLED, INSPECTED, TESTED, AND |
| | APPROVED BY THE CITY. |
| | |
| | 2. SHOULD THE EXISTING FIRE ALARM SYSTEM BE OUT OF |
| | SERVICE FOR MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR |
| | PERIOD, A FIRE WATCH IS REQUIRED FOR THE BUILDING. ALL |
| | FIRE WATCHES MUST BE APPROVED BY THE BATTALION CHIEF OF |
| | THE FIRE PREVENTION BUREAU OR HIS DESIGNEE AND SHALL BE |
| | REQUESTED IN WRITING. |
| | |
| | 3. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION TO COMPLY |
| | WITH NFPA 72, THE NATIONAL FIRE ALARM CODE, 2002 |
| | EDITION. |
| | |
| | 4. NOTE 17 ON SHEET FA0.1 IS INCORRECT. WHEN ACTIVATED |
| | DUCT SMOKE DETECTORS SHALL INITIATE A FIRE ALARM |
| | SIGNAL. |
| | |
| | 5. THE PLANS DO NOT ILLUSTRATE ANY EXISTING FIRE ALARM |
| | EQUIPMENT IN THE CHILLER, COOLING TOWER OR GENERATOR |
| | AREAS. DOES ANY EXIST OR ARE ANY PLANNED. |
| | |
| | 6. THERE APPEARS TO BE NO EQUIPMENT LOCATED ON WHAT |
| | APPEARS TO BE THE LOADING DOCK AREA. DOES ANY EXIST OR |
| | ARE ANY PLANNED. |
| | |
| | 7. THE CONFERENCE ROOM NEAR THE COPY/FAX ROOM ON SHEET |
| | FA2.1 DOES DISPLAY A SIGNALING APPLIANCE. |
| | |
| | 8. NO FIRE ALARM EQUIPMENT DISPLAYED IN CAFETERIA ON |
| | PAGE FA2.2. |
| | |
| | 9. NOTE 25 ON SHEET FA0.1 DESCRIBES THAT PENETRATIONS |
| | ARE TO BE REPAIRED TO MATCH EXISTING. PENETRATIONS IN |
| | RATED FIRE WALLS AND TO BE SEALED IN AN APPROVED MANNER |
| | WITH APPROVED MATERIALS. PLEASE PROVIDE A DETAIL. |
| | |
| | 10. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A |
| | LICENSED THIRD PARTY MONITORING COMPANY APPROVED TO |
| | MONITOR FOR CENTRAL STATION SERVICE. |
| | |
| | 11. ALL FLOW AND TAMPER SWITCHES INCLUDING THE BACKFLOW |
| | DEVICE ARE TO BE MONITORED. |
| | |
| | 12. SOME MECHANICAL AND TELEPHONE ROOMS APPEAR TO |
| | CONTAIN NO FIRE ALARM EQUIPMENT. DOES EQUIPMENT EXIST |
| | OR ARE SOME PLANNED. |
| | |
| | 13. PLEASE DISPLAY CIRCUITING OF INITIATING AND |
| | SIGNALING APPLIANCES CONTAINED ON THE FLOOR PLANS. |
| | |
| | 14. WHEN ACTIVATED, THE FIRE ALARM SYSTEM SHALL PROVIDE |
| | THE REQUIRED AUDIBILITY THROUGHOUT THE BUILDING. PROPER |
| | COVERAGE OF STROBE DEVICES SHALL BE PROVIDED. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |