Plan Review Details - Permit 10090773
Plan Review Stops For Permit 10090773
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-05 Cont ID  
Sent By jleahy Date 2010-10-05 Time 13:15 Rev Time 0.00
Received By jleahy Date 2010-10-05 Time 13:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-04 Cont ID  
Sent By mcarsill Date 2010-11-04 Time 10:12 Rev Time 0.00
Received By mcarsill Date 2010-11-04 Time 10:12 Sent To  
Notes
2010-11-04 16:44:41PERMIT #10090773
  
 SPOKE WITH MR. HART STATED THAT HE WOULD PROVIDE LETTER
 CLARIFING THAT THE ENGINEER OF RECODS FOR THE FIRE
 ALARM SYSTEM IS MR. BROWN.
 BOTH THE CONSTRUCTION DOCUMENTS AND SHOP DRAWINGS HAVE
 BEEN SIGNED AND SEALED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By mcarsill Date 2010-10-01 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2010-10-01 Time 12:38 Sent To  
Notes
2010-10-01 13:03:276001 VILLAGE BOULEVARD
 PERMIT NUMBER 10090773
 "REPLACE EXISTING FIRE ALARM SYSTEM"
  
 1. THE EXISTING FIRE ALARM SYSTEM IS TO REMAIN
 OPERATIONAL UNTIL SUCH TIME AS THE NEW FIRE ALARM
 SYSTEM HAS BEEN INSTALLED, INSPECTED, TESTED, AND
 APPROVED BY THE CITY.
  
 2. SHOULD THE EXISTING FIRE ALARM SYSTEM BE OUT OF
 SERVICE FOR MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR
 PERIOD, A FIRE WATCH IS REQUIRED FOR THE BUILDING. ALL
 FIRE WATCHES MUST BE APPROVED BY THE BATTALION CHIEF OF
 THE FIRE PREVENTION BUREAU OR HIS DESIGNEE AND SHALL BE
 REQUESTED IN WRITING.
  
 3. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION TO COMPLY
 WITH NFPA 72, THE NATIONAL FIRE ALARM CODE, 2002
 EDITION.
  
 4. NOTE 17 ON SHEET FA0.1 IS INCORRECT. WHEN ACTIVATED
 DUCT SMOKE DETECTORS SHALL INITIATE A FIRE ALARM
 SIGNAL.
  
 5. THE PLANS DO NOT ILLUSTRATE ANY EXISTING FIRE ALARM
 EQUIPMENT IN THE CHILLER, COOLING TOWER OR GENERATOR
 AREAS. DOES ANY EXIST OR ARE ANY PLANNED.
  
 6. THERE APPEARS TO BE NO EQUIPMENT LOCATED ON WHAT
 APPEARS TO BE THE LOADING DOCK AREA. DOES ANY EXIST OR
 ARE ANY PLANNED.
  
 7. THE CONFERENCE ROOM NEAR THE COPY/FAX ROOM ON SHEET
 FA2.1 DOES DISPLAY A SIGNALING APPLIANCE.
  
 8. NO FIRE ALARM EQUIPMENT DISPLAYED IN CAFETERIA ON
 PAGE FA2.2.
  
 9. NOTE 25 ON SHEET FA0.1 DESCRIBES THAT PENETRATIONS
 ARE TO BE REPAIRED TO MATCH EXISTING. PENETRATIONS IN
 RATED FIRE WALLS AND TO BE SEALED IN AN APPROVED MANNER
 WITH APPROVED MATERIALS. PLEASE PROVIDE A DETAIL.
  
 10. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A
 LICENSED THIRD PARTY MONITORING COMPANY APPROVED TO
 MONITOR FOR CENTRAL STATION SERVICE.
  
 11. ALL FLOW AND TAMPER SWITCHES INCLUDING THE BACKFLOW
 DEVICE ARE TO BE MONITORED.
  
 12. SOME MECHANICAL AND TELEPHONE ROOMS APPEAR TO
 CONTAIN NO FIRE ALARM EQUIPMENT. DOES EQUIPMENT EXIST
 OR ARE SOME PLANNED.
  
 13. PLEASE DISPLAY CIRCUITING OF INITIATING AND
 SIGNALING APPLIANCES CONTAINED ON THE FLOOR PLANS.
  
 14. WHEN ACTIVATED, THE FIRE ALARM SYSTEM SHALL PROVIDE
 THE REQUIRED AUDIBILITY THROUGHOUT THE BUILDING. PROPER
 COVERAGE OF STROBE DEVICES SHALL BE PROVIDED.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-28 Cont ID  
Sent By rmcdouga Date 2010-10-28 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2010-10-28 Time 07:42 Sent To  
Notes
2010-10-28 07:42:52SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-29 Cont ID  
Sent By jwitmer Date 2010-09-29 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2010-09-29 Time 11:22 Sent To  
Notes
2010-09-29 11:23:11INCOMING SENT TO FIRE BOX