Plan Review Details - Permit 10090720
Plan Review Stops For Permit 10090720
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-09-30 Cont ID  
Sent By jwitmer Date 2010-09-30 Time 15:40 Rev Time 1.00
Received By jwitmer Date 2010-09-30 Time 14:40 Sent To  
Notes
2010-09-30 15:43:25 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 10090720
 ADD: 105 S NARCISSUS 302/312
 CONT: LB DEVELOPMENT
 TEL: (954)709-1926
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISO:
 712.3 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR
 THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER
 WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS
 712.3.1 THROUGH 712.3.4.
  
 712.3.1 THROUGH PENETRATIONS. THROUGH PENETRATIONS OF
 FIRE-RESISTANCE-RATED WALLS SHALL COMPLY WITH SECTION
 712.3.1.1 OR 712.3.1.2.
  
 712.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-01 Cont ID  
Sent By jleahy Date 2010-10-01 Time 08:42 Rev Time 0.00
Received By jleahy Date 2010-10-01 Time 08:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-10-19 Cont ID  
Sent By mcarsill Date 2010-10-19 Time 12:48 Rev Time 0.00
Received By mcarsill Date 2010-10-19 Time 12:45 Sent To  
Notes
2010-10-19 12:48:07105 SOUTH NARCISSUS AVENUE
 PERMIT NUMBER 10090720
  
  
 1. PLEASE PROVIDE ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FIXTURES IN TENANT SPACES 302 / 312.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
  
 APPROVED PROVISO:
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-02 Cont ID  
Sent By lmartine Date 2010-10-22 Time 13:19 Rev Time 0.00
Received By lmartine Date 2010-10-22 Time 09:21 Sent To  
Notes
2010-10-22 09:22:14INCOMING SENT TO H MOSER DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-20 Cont ID  
Sent By lmartine Date 2010-10-19 Time 13:22 Rev Time 0.00
Received By lmartine Date 2010-09-27 Time 09:58 Sent To  
Notes
2010-09-29 10:02:31B2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-10-22 Cont ID  
Sent By hmoser Date 2010-10-22 Time 13:45 Rev Time 0.00
Received By hmoser Date 2010-10-22 Time 13:45 Sent To  
Notes
2010-10-22 14:08:57PROVISO
  
 1) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR
 2007 FMC
 2) REFER TO SECTION 603.8 BUILDING CAVITIES WHICH WILL
 BE USED FOR RETURN AIR PLENUMS
 3) PLEASE REFER TO SECTION 607.5.3 FIRE PARTITIONS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-10-06 Cont ID  
Sent By hmoser Date 2010-10-06 Time 10:04 Rev Time 0.00
Received By hmoser Date 2010-10-06 Time 09:36 Sent To  
Notes
2010-10-06 10:14:35PLANS DENIED
 1) PROVIDE DUCT SIZE ON THE PLANS.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR 2007 FMC.
 5) SHOW THE LOCATION OF THE RETURN AIR ON THE
 MECHANICAL PLANS
 6) PLEASE SUBMIT A COMPLETE SET OF MECHANICAL PLANS FOR
 THE PERMIT.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  