| 2010-10-20 10:28:00 | EXTERIOR IMPROVEMENTS, BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- PLEASE CLARIFY SCOPE OF WORK TO BE PERFORMED. PLANS |
| | SUBMITTED ARE FOR NEW ROOF OVERHANG, NEW ENTRY DOOR, |
| | NEW PLANTER AND NEW WOOD FENCE ONLY. ADDITIONAL WORK |
| | REQUIRES PLANS TO CHECK FOR BUILDING CODE COMPLIANCE. |
| | INCLUDING PARKING TO VERIFY COMPLIANCE WITH CHAPTER 11 |
| | FBC. |
| | WORK DESCRIPTION ON PLANS SUBMITTED STATES, NO |
| | PLUMBING, MECHANICAL, ELECTRICAL, INTERIOR WORK OR |
| | LANDSCAPE WORK IS INCLUDED. |
| | |
| | 2- PROVIDE STRUCTURAL FRAMING DETAILS FOR NEW ENTRY |
| | DOOR TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF |
| | SEC. 1609 OF 2007 FBC. |
| | |
| | 3- PROVIDE FLOOR PLAN SHOWING HOW THE NEW ENTRY WILL |
| | AFFECT THE EXISTING FLOOR PLAN LAYOUT TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF CHAPTER 10 |
| | FBC. AND SPECIFY SIZE OF DOOR. |
| | |
| | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) NEW ENTRY DOOR. |
| | |
| | B) ROOF TILE. AND, CLEARLY SPECIFY HOW FASTENING THE |
| | TILE. IF USING ADHESIVE, THEN SEE ROOF TILE FOR LISTED |
| | ADHESIVES AND PROVIDE REQUIRED PRODUCT APPROVAL. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 6- DESIGN PROFESSIONAL TO SPECIFY ALTERATION LEVEL AS |
| | REQUIRED BY SEC. 401.4 OF 2007 FBC-EXISTING BUILDING. |
| | |
| | 7- DESIGN PROFESSIONAL TO UPDATE THE CODE TO BE USED. |
| | REFER TO 2009 REVISIONS TO THE 2007 FBC, NOT 2008 |
| | REVISIONS. |
| | |
| | 8- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |