Plan Review Details - Permit 10090637
Plan Review Stops For Permit 10090637
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-11-10 Cont ID  
Sent By rmcdouga Date 2010-11-10 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2010-11-10 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-04 Cont ID  
Sent By rmcdouga Date 2010-10-04 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2010-10-04 Time 13:31 Sent To  
Notes
2010-10-04 14:23:402007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE WIND LOAD CALCULATIONS (
 REPORT HC-6) THAT ARE SIGNED AND SEALED BY THE ENGINEER
 AS REQUIRED BY FS 471 AND FAC 61G15-23.002.
  
 2) SPECIFY THE REQUIRED EMBED DEPTH OF THE SIMPSON
 TITEN HD ANCHORS SPECIFIED ITEM V (2) OF THE WIND LOAD
 CALCULATIONS.
  
 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS (DCA
 RULE9B-72) FOR THE 1/4" SIMPSON TITEN HD WITH THE
 WITHDRAWL LOADS IN CONCRETE TILE SPECIFIED IN ITEM V
 (2) OF THE WIND LOAD CALCULATIONS.
  
 4) PROVIDE 2 COPIES OF PRODUCT APPROVALS FOR ROOF TILES
 THAT HAVE BEEN TESTED WITH THIS APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-05 Cont ID  
Sent By lmartine Date 2010-11-05 Time 16:01 Rev Time 0.00
Received By lmartine Date 2010-11-05 Time 16:01 Sent To  
Notes
2010-11-05 16:01:29GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-04 Cont ID  
Sent By rmcdouga Date 2010-10-04 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2010-09-27 Time 08:39 Sent To  
Notes
2010-09-27 08:39:44TO PLUMBING
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-10-04 Cont ID  
Sent By rmcdouga Date 2010-10-04 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2010-10-04 Time 13:31 Sent To  
Notes
***NONE***