| 2010-09-27 11:11:14 | 550 SOUTH ROSEMARY AVENUE, SUITE 156 |
| | PERMIT NUMBER 10090476 |
| | "CHANGE OF OCCUPANCY" |
| | |
| | |
| | 1. THE FLOOR PLAN INDICATES 50 STOOLS BUT THE PLAN ALSO |
| | INDICATES A SEATING CAPACITY OF 107. ONE SMALL |
| | RECTANGLE AT THE BOTTOM OF THE PLAN IS CALLED OUT AS |
| | "STOOLS" BUT IT IS NOT CLEAR WHERE THE OTHER 57 SEATS |
| | ARE LOCATED. |
| | |
| | 2. CITY PLACE STAMP IS NOT LOCATED ON THE DRAWINGS. |
| | |
| | 3. NO INFORMATION PROVIDED ON THE DRAWINGS AS TO THE |
| | TYPE OF DOOR HARDWARE THAT IS PROVIDED. |
| | |
| | 4. NO SCALE ON PLANS TO DETERMINE OCCUPANT LOAD FOR THE |
| | SPACE USING THE OCCUPANT LOAD FACTOR CRITERIA. |
| | |
| | 5. NO INFORMATION INDICATING EXISTING FIRE SPRINKLER OR |
| | FIRE ALARM EQUIPMENT. A NOTE BY A CONSTRUCTION SERVICES |
| | DEPARTMENT EMPLOYEE INDICATES FIRE SPRINKLERS. ARE ANY |
| | CHANGES PLANNED. |
| | |
| | 6. NO INFORMATION REGARDING EXISTING FIRE WALLS. |
| | |
| | 7. NO INFORMATION ON THE TYPES OF MATERIALS TO BE USED |
| | IN THE "ART CLASS AREA". ARE PAINTS EXPECTED (WATER |
| | BASED OR OIL BASED) AND HOW MUCH QUANTITY AND WHAT |
| | STORAGE PROCEDURES WILL BE FOLLOWED. IF PAINTS ARE USED |
| | HOW WILL THEY BE APPLIED. |
| | |
| | 8. NO INFORMATION ON PORTABLE FIRE EXTINGUISHERS. |
| | |
| | 9. NO INFORMATION ON EMERGENCY LIGHTING EQUIPMENT. |
| | |
| | 10. ARE ANY CHANGES PLANNED REGARDING ARCHITECTURAL, |
| | MECHANICAL, ELECTRICAL, PLUMBING, FIRE SPRINKLER OR |
| | FIRE ALARM EQUIPMENT. |
| | |
| | 11. WHAT IS THE ANTICIPATED AGES OF THE STUDENTS FOR |
| | THE ART CLASS AREA. |
| | |
| | 12. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |