| Plan Review Stops For Permit 10090419 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-09-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-09-21 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-09-21 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2010-09-21 12:46:31 | 1208 OLD OKEECHOBEE ROAD | | | PERMIT #10090419 | | | MASTER #10060872 | | | | | | REVIEW COMMENTS - FIRE: | | | | | | >NFPA 33 SECTION 10.11 REQUIRES "NO SMOKING OR OPEN | | | FLAMES" SIGNS AT ALL SPRAY AREAS. | | | | | | >NFPA 17 SECTION 4.4.3 REQUIRES SHUTOFF DEVICES TO BE | | | MANUALLY RESET PRIOR TO FUEL OR POWER RESTORATION. | | | | | | >NFPA 17 SECTION 5.6.1.3 REQUIRES WARNING SIGNS | | | (CAUTION: HAZARDS TO PERSONNEL) AND PREDISCHARGE | | | ALARMS. | | | | | | >NFPA 17 SECTION 5.7.1.7.1 REQUIRES THE MANUAL PULL | | | STATION TO BE MOUNTED 42-48 INCHES ABOVE THE FLOOR AND | | | LOCATED IN THE PATH OF EXIT. | | | | | | WESLEY JOLIN | | | FIRE AND LIFE SAFETY PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-805-6730 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-09-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-09-21 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-09-20 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2010-09-20 13:24:36 | INCOMING SENT TO FIRE BOX JW |
|
|
|