Plan Review Details - Permit 10090380
Plan Review Stops For Permit 10090380
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-07 Cont ID  
Sent By rmcdouga Date 2010-10-07 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2010-10-07 Time 06:51 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-06 Cont ID  
Sent By rmcdouga Date 2010-10-06 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2010-10-06 Time 07:22 Sent To  
Notes
2010-10-06 08:47:17DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE
 EXPIRED OR HAVE BEEN SUPERSEDED. SUBMIT 2 COPIES OF THE
 CURRENT NOAS AS REQUIRED BY DCA RULE 9B-72. SEE NOA NO.
 10-0308.02 FOR THE DHS-500 STOREFRONT AND NOA NO.
 10-0121.10 FOR THE DH-350 OUTSWING DOOR.
  
 2) ADDRESS ZONING COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-06 Cont ID  
Sent By lmartine Date 2010-10-06 Time 15:23 Rev Time 0.00
Received By lmartine Date 2010-10-06 Time 15:23 Sent To  
Notes
2010-10-06 15:24:07***************EXPEDITED 2ND RUN**********************

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-06 Cont ID  
Sent By rmcdouga Date 2010-10-06 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2010-09-15 Time 09:14 Sent To  
Notes
2010-09-17 09:15:56TO ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2010-10-12 Cont ID  
Sent By eschneid Date 2010-10-12 Time 17:04 Rev Time 1.00
Received By eschneid Date 2010-10-07 Time 17:14 Sent To PC
Notes
2010-10-12 17:06:52PASSED - DOOR AND WINDOW REPALCEMENT ONLY.
  
 PROPOSED PARAPET CHANGES DO NOT MEET ARTICLE XVI OF
 ZONING AND LAND DEVELOPMENT REGULATIONS AND THUS
 CONTRACTOR, KEVIN CLER, REQUESTED REMOVAL FROM SCOPE OF
 WORK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-28 Cont ID  
Sent By eschneid Date 2010-09-28 Time 14:56 Rev Time 1.00
Received By eschneid Date 2010-09-21 Time 15:25 Sent To B
Notes
2010-09-28 15:09:02FAILED
  
 1) THE NEIGHBORHOOD COMMERCIAL ZONING DISTRICT REQUIRES
 A FIVE (5) FOOT FRONT SETBACK. THE BUILDING IS A
 DIMENSIONAL NON-CONFORMITY AS IT IS ONLY 0.6 FEET FROM
 THE FRONT PROPERTY LINE. PER SECTION 94-513(B)(1)A,
 DIMENSIONAL NON-CONFORMITY MAY NOT BE ALTERED UNLESS
 THE ALTERATION REDUCES THE IMPACT OF THE NON-CONFORMITY
 ON ADJACENT PROPERTY. THE INCREASE OF THE PARAPET
 HEIGHT UP TO SIX (6) FEET ABOVE ITS EXISTING HEIGHT,
 WITHIN THE REQUIRED FRONT SETBACK, INCREASES THE IMPACT
 OF THE DIMENSIONAL NON-CONFORMITY, AND THUS IS NOT
 PERMITTED.
  
 2) PLEASE NOTE THAT THE STOREFRONTS MAY BE ALTERED AS
 SHOWN, AS THEY ARE CREATING A LARGER SETBACK THAN THE
 CURRENT STOREFRONTS HAVE WHEN MEASURED TO THE FRONT
 PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.