| Plan Review Stops For Permit 10090281 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2010-12-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-12-21 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-12-21 |
Time |
17:04 |
Sent To |
PC |
|
| Notes |
| 2010-12-21 17:04:03 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE ENERGY CALCULATIONS. PRESCRIPTIVE FORM | | | 1100B-08 SUBMITTED REQUIRES MIN. R30 CEILING | | | INSULATION. | | | | | | 2- REVISE STORM SHUTTERS INSTALLATION SCHEDULE: REVISE | | | SHUTTER SPAN. SHUTTER INSTALLATION IS VERTICAL NOT | | | HORIZONTAL. ANCHOR TYPE TO MATCH ANCHOR SHOWN ON | | | SHUTTERS DRAWINGS. | | | | | | 3- SHEET A-2.0: REVISE COMPONENT AND CLADDING PRESSURE | | | ZONES SPECIFICATIONS TO MATCH PLYWOOD ROOF SHEATHING | | | NOTE "C". | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2010-11-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-11-19 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-11-19 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2010-11-19 17:10:48 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 2- ENERGY CALCULATIONS SUBMITTED: | | | A) R30 BUTT INSULATION DOESN'T FIT ON 2X8 ROOF RAFTERS. | | | R30 BUTT INSULATION IS ABOUT 9 1/2" THICK. CLARIFY HOW | | | IS THE ROOF CROSS VENTILATION REQUIRED BY SEC. R806 | | | GOING TO BE ACHIEVED. ALSO, THE INSULATION VALUE WILL | | | NEED TO BE REDUCED IF THE BUTT INSULATION IS COMPRESSED | | | TO FIT WITHIN THE ROOF RAFTERS. | | | | | | B) PERSON WHO PREPARED THE ENERGY CALCULATIONS NEED TO | | | SIGN AND DATE AT THE BOTTOM OF THE ENERGY CALCULATIONS | | | SUBMITTED. | | | | | | 3- FLAT ROOF PRODUCT APPROVAL SUBMITTED: | | | A) CLEARLY MARK ON NOA SUBMITTED SPECIFIC APPROVED | | | ASSEMBLY TO BE INSTALLED. (REPEAT COMMENT. NOT | | | ADDRESSED). | | | | | | B) ENGINEER TO PROVIDE THE RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | | | | ***INFORMATION SUBMITTED DOESN'T SHOW THE RAS 117 | | | CALCULATIONS. ENGINEER TO IDENTIFY WHICH APPROVED | | | ASSEMBLY HE'S USING. BASE SHEET FASTENING | | | SPECIFICATIONS PROVIDED BY THE ENGINEER ARE NO CLEAR. | | | ENGINEER TO PROVIDE SKETCH SHOWING PROPOSED NAILING. | | | ENGINEER TO IDENTIFY EACH ROOF ZONE. | | | | | | ***NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY | | | GENERAL LIMITATION #9 CAN'T BE USED IN THIS AREA. | | | | | | 4- STORM SHUTTERS: | | | A) PROVIDE COMPLETE INSTALLATION SCHEDULE. (REPEAT | | | COMMENT. NOT ADDRESSED). | | | | | | B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS (EX: WALL MOUNTED, BUILD OUT, ETC) AND | | | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | | (REPEAT COMMENT. NOT ADDRESSED). | | | | | | 5- SHEET A-2.0: | | | A) ROOF ZONE #3 REQUIRES MIN. 8D RING SHANK NAILS AT 4" | | | O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2007 FLORIDA | | | RESIDENTIAL CODE. REVISE ALL ROOF SHEATHING NOTES AND | | | DETAILS AS REQUIRED TO REFLECT THIS REQUIREMENTS. | | | | | | B) REVISE COMPONENT AND CLADDING PRESSURE ZONES TABLE | | | TO REFLECT THE ROOF SHEATHING NAIL TYPE AND SPACING AS | | | REQUIRED ON ITEM 5A ABOVE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-10-06 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-10-06 |
Time |
09:46 |
Sent To |
PC |
|
| Notes |
| 2010-10-06 10:08:54 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE SURVEY OR SITE PLAN SHOWING EXACT LOCATION | | | OF PROPOSED ADDITION TO VERIFY COMPLIANCE WITH THE | | | EXTERIOR WALL LOCATION OF SEC. R302 OF 2007 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO | | | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS | | | AND COPY OF PAID RECEIPT IF FEES ARE DUE. | | | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 4- ENERGY CALCULATIONS: | | | A) TABLE 11B-1 ON BACK SHEET OF FORM 1100B-08 SUBMITTED | | | REQUIRES CEILING INSULATION TO BE R-30. THE INSTALLED | | | VALUE SHOWN IS R-19. INSTALLED VALUE NEED TO MEET OR | | | EXCEED THE R VALUE SHOWN ON THE PERFORMANCE CRITERIA | | | COLUMN. REVISE AS REQUIRED. | | | B) R VALUES SHOWN ON ALL PLANS AND DETAILS TO MATCH | | | INFORMATION PROVIDED ON THE ENERGY CALCULATIONS. | | | COORDINATE AS REQUIRED. | | | | | | 5- PROVIDE PRODUCT APPROVAL (2COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) PRECAST LINTELS AS SPECIFIED ON PLANS. | | | B) STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON PLANS. | | | | | | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. 106.3.3 | | | CITY AMENDMENTS TO FBC. | | | | | | 7- FLAT ROOF PRODUCT APPROVAL SUBMITTED: | | | A) ACCORDING TO THE MIAMI-DADE WEBSITE THE NOA | | | 07-0730.03 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE | | | CURRENT NOA. | | | B) CLEARLY MARK ON NOA SUBMITTED SPECIFIC APPROVED | | | ASSEMBLY TO BE INSTALLED. | | | C) PROVIDE THE RAS 117 CALCULATIONS FOR NAIL ENHANCING | | | AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. IF NOA | | | REQUIRES THESE CALCULATIONS TO BE SIGNED AND SEALED, | | | THEN, PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS. | | | ***NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY | | | GENERAL LIMITATION #9 CAN'T BE USED IN THIS AREA. | | | | | | 8- STORM SHUTTERS: | | | A) PROVIDE COMPLETE INSTALLATION SCHEDULE. | | | B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS (EX: WALL MOUNTED, BUILD OUT, ETC) AND | | | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | | | | | 9- SHEET A-1.0: GENERAL NOTE #7 CALLS FOR 2000PSF SOIL | | | BEARING CAPACITY, WHILE DESIGN PARAMETERS NOTE CALLS | | | FOR 2500PSF SOIL BEARING CAPACITY. REVISE AS REQUIRED | | | TO MATCH. | | | | | | 10- SHEET A-2.0: | | | A) SPECIFICATIONS FOR ROOF SHEATHING ON PROPOSED ROOF | | | FRAMING PLAN, COMPONENTS AND CLADDING PRESSURES ZONES, | | | PLYWOOD ROOF SHEATING NOTES, DETAIL F, SECTION S-1, | | | SECTION S-2 AND TYPICAL WALL SECTION DON'T MATCH. | | | REVISE TYPE PLYWOOD THICKNESS AND NAIL TYPE AND SPACING | | | TO MATCH. COORDINATE AS REQUIRED. | | | | | | B) REVISE PLYWOOD SHEATHING NOTE "C": ZONE 1 EXPOSURE | | | CAN'T BE ASSUMED FOR ALL ROOF ZONES. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2010-12-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-12-22 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-12-22 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2010-11-30 |
|
|
Cont ID |
|
| Sent By |
jdickins |
Date |
2010-11-30 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
jdickins |
Date |
2010-11-30 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2010-11-30 18:28:14 | OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE | | | NUMBER PX3182 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-10-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2010-10-01 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2010-10-01 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-12-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-12-15 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-12-15 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2010-12-15 11:40:35 | IN ZONING BOX | | 2010-12-15 11:06:00 | INCOMING SENT TO R-5. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-12-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-11-10 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-11-10 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-10-06 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-09-14 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2010-11-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-11-17 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-11-17 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2010-11-17 15:09:11 | NO FEES. STAMPED BY VAL ON 11/4/10 . MU-2010-20494. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2010-10-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-10-05 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-10-05 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2010-10-05 15:47:36 | IMPACT FEES COMMENTS: | | | | | | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO | | | VERIFY IF IMPACT FEES ARE REQUIRED. BRING BACK STAMPED | | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
N |
Date |
2010-12-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-12-22 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-12-22 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2010-12-22 08:49:37 | SEPARATE PERMITS FOR LANDSCAPE AND IRRIGATION ARE | | | REQUIRED. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
2010-12-16 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-12-16 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-12-15 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2010-12-16 18:29:41 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. TWO | | | (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | | SECTIONS 94-442 AND 94-445 OF THE ZLDR SHALL BE | | | SUBMITTED WITH THE APPLICATION AND A COST ESTIMATE THAT | | | INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND | | | LABOR, BROKEN DOWN INTO UNIT COST. THE PLAN SUBMITTED | | | STATES THAT THIS IS AN AS-BUILT PLAN BUT THERE IS A | | | PLANT LIST. PLEASE INDICATE WHAT IS EXISTING AND WHAT | | | IS PROPOSED. | | | | | | 2. PROVIDE THE XERISCAPE TABULATION SHOWING COMPLIANCE | | | WITH THE REQUIREMENTS. | | | | | | 3. PROVIDE THE SIZE ANDS SPACING FOR ALL EXISTING AND | | | PROPOSED TREES AND PLANT MATERIAL. | | | | | | 4, PLEASE APPLY FOR A SEPARATE IRRIGATION PERMIT. | | | SUBMIT TWO (2) COPIES OF THE IRRIGATION PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2010-09-23 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-09-23 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-09-23 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2010-09-23 15:31:32 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. | | | | | | 2. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. TWO | | | (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | | SECTIONS 94-442 AND 94-445 OF THE ZLDR SHALL BE | | | SUBMITTED WITH THE APPLICATION AND A COST ESTIMATE THAT | | | INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND | | | LABOR, BROKEN DOWN INTO UNIT COST. | | | | | | 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS. | | | | | | 4. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL | | | AREAS TO BE PLANTED IN A CULTIVATED LANDSCAPE, | | | IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120 | | | PERCENT COVERAGE. PLEASE APPLY FOR AN IRRIGATION PERMIT | | | AND PROVIDE TWO (2) SETS OF IRRIGATION PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2010-11-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-11-19 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-11-19 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-10-06 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-10-06 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2010-12-21 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2010-12-21 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2010-12-21 |
Time |
09:06 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2010-11-22 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2010-11-22 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2010-11-22 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2010-11-22 10:34:18 | AMY STELLY | | | PLANNING AND ZONING | | | 561-822-1442 | | | | | | PASSED W/PROVISO | | | | | | A LANDSCAPE PLAN IS REQUIRED FOR THE COMPLETION OF THE | | | ZONING REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-09-23 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2010-09-23 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2010-09-23 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2010-09-23 17:33:20 | AMY STELLY | | | PLANNING AND ZONING | | | 822-1442 | | | | | | PLEASE SUBMIT A SURVEY SHOWING THE LOCATION OF THE | | | ADDITION. | | | A LANDSCAPE PLAN MUST BE SUBMITTED PURSUANT TO THE | | | ZONING CODE. | | | | | | YOUR SUBMISSION MAY GENERATE ADDITIONAL COMMENTS. |
|
|