Plan Review Details - Permit 10090281
Plan Review Stops For Permit 10090281
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-12-21 Cont ID  
Sent By jgomez Date 2010-12-21 Time 16:56 Rev Time 0.00
Received By jgomez Date 2010-12-21 Time 17:04 Sent To PC
Notes
2010-12-21 17:04:03BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS. PRESCRIPTIVE FORM
 1100B-08 SUBMITTED REQUIRES MIN. R30 CEILING
 INSULATION.
  
 2- REVISE STORM SHUTTERS INSTALLATION SCHEDULE: REVISE
 SHUTTER SPAN. SHUTTER INSTALLATION IS VERTICAL NOT
 HORIZONTAL. ANCHOR TYPE TO MATCH ANCHOR SHOWN ON
 SHUTTERS DRAWINGS.
  
 3- SHEET A-2.0: REVISE COMPONENT AND CLADDING PRESSURE
 ZONES SPECIFICATIONS TO MATCH PLYWOOD ROOF SHEATHING
 NOTE "C".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-11-19 Cont ID  
Sent By jgomez Date 2010-11-19 Time 17:09 Rev Time 0.00
Received By jgomez Date 2010-11-19 Time 17:09 Sent To  
Notes
2010-11-19 17:10:48RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) R30 BUTT INSULATION DOESN'T FIT ON 2X8 ROOF RAFTERS.
 R30 BUTT INSULATION IS ABOUT 9 1/2" THICK. CLARIFY HOW
 IS THE ROOF CROSS VENTILATION REQUIRED BY SEC. R806
 GOING TO BE ACHIEVED. ALSO, THE INSULATION VALUE WILL
 NEED TO BE REDUCED IF THE BUTT INSULATION IS COMPRESSED
 TO FIT WITHIN THE ROOF RAFTERS.
  
 B) PERSON WHO PREPARED THE ENERGY CALCULATIONS NEED TO
 SIGN AND DATE AT THE BOTTOM OF THE ENERGY CALCULATIONS
 SUBMITTED.
  
 3- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) CLEARLY MARK ON NOA SUBMITTED SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 B) ENGINEER TO PROVIDE THE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 ***INFORMATION SUBMITTED DOESN'T SHOW THE RAS 117
 CALCULATIONS. ENGINEER TO IDENTIFY WHICH APPROVED
 ASSEMBLY HE'S USING. BASE SHEET FASTENING
 SPECIFICATIONS PROVIDED BY THE ENGINEER ARE NO CLEAR.
 ENGINEER TO PROVIDE SKETCH SHOWING PROPOSED NAILING.
 ENGINEER TO IDENTIFY EACH ROOF ZONE.
  
 ***NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY
 GENERAL LIMITATION #9 CAN'T BE USED IN THIS AREA.
  
 4- STORM SHUTTERS:
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EX: WALL MOUNTED, BUILD OUT, ETC) AND
 SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- SHEET A-2.0:
 A) ROOF ZONE #3 REQUIRES MIN. 8D RING SHANK NAILS AT 4"
 O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2007 FLORIDA
 RESIDENTIAL CODE. REVISE ALL ROOF SHEATHING NOTES AND
 DETAILS AS REQUIRED TO REFLECT THIS REQUIREMENTS.
  
 B) REVISE COMPONENT AND CLADDING PRESSURE ZONES TABLE
 TO REFLECT THE ROOF SHEATHING NAIL TYPE AND SPACING AS
 REQUIRED ON ITEM 5A ABOVE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-06 Cont ID  
Sent By jgomez Date 2010-10-06 Time 09:46 Rev Time 0.00
Received By jgomez Date 2010-10-06 Time 09:46 Sent To PC
Notes
2010-10-06 10:08:54RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SURVEY OR SITE PLAN SHOWING EXACT LOCATION
 OF PROPOSED ADDITION TO VERIFY COMPLIANCE WITH THE
 EXTERIOR WALL LOCATION OF SEC. R302 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 4- ENERGY CALCULATIONS:
 A) TABLE 11B-1 ON BACK SHEET OF FORM 1100B-08 SUBMITTED
 REQUIRES CEILING INSULATION TO BE R-30. THE INSTALLED
 VALUE SHOWN IS R-19. INSTALLED VALUE NEED TO MEET OR
 EXCEED THE R VALUE SHOWN ON THE PERFORMANCE CRITERIA
 COLUMN. REVISE AS REQUIRED.
 B) R VALUES SHOWN ON ALL PLANS AND DETAILS TO MATCH
 INFORMATION PROVIDED ON THE ENERGY CALCULATIONS.
 COORDINATE AS REQUIRED.
  
 5- PROVIDE PRODUCT APPROVAL (2COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
 B) STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON PLANS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. 106.3.3
 CITY AMENDMENTS TO FBC.
  
 7- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) ACCORDING TO THE MIAMI-DADE WEBSITE THE NOA
 07-0730.03 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA.
 B) CLEARLY MARK ON NOA SUBMITTED SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED.
 C) PROVIDE THE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. IF NOA
 REQUIRES THESE CALCULATIONS TO BE SIGNED AND SEALED,
 THEN, PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS.
 ***NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY
 GENERAL LIMITATION #9 CAN'T BE USED IN THIS AREA.
  
 8- STORM SHUTTERS:
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE.
 B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EX: WALL MOUNTED, BUILD OUT, ETC) AND
 SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
  
 9- SHEET A-1.0: GENERAL NOTE #7 CALLS FOR 2000PSF SOIL
 BEARING CAPACITY, WHILE DESIGN PARAMETERS NOTE CALLS
 FOR 2500PSF SOIL BEARING CAPACITY. REVISE AS REQUIRED
 TO MATCH.
  
 10- SHEET A-2.0:
 A) SPECIFICATIONS FOR ROOF SHEATHING ON PROPOSED ROOF
 FRAMING PLAN, COMPONENTS AND CLADDING PRESSURES ZONES,
 PLYWOOD ROOF SHEATING NOTES, DETAIL F, SECTION S-1,
 SECTION S-2 AND TYPICAL WALL SECTION DON'T MATCH.
 REVISE TYPE PLYWOOD THICKNESS AND NAIL TYPE AND SPACING
 TO MATCH. COORDINATE AS REQUIRED.
  
 B) REVISE PLYWOOD SHEATHING NOTE "C": ZONE 1 EXPOSURE
 CAN'T BE ASSUMED FOR ALL ROOF ZONES.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-12-22 Cont ID  
Sent By rmcdouga Date 2010-12-22 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2010-12-22 Time 08:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-30 Cont ID  
Sent By jdickins Date 2010-11-30 Time 18:27 Rev Time 0.00
Received By jdickins Date 2010-11-30 Time 18:27 Sent To  
Notes
2010-11-30 18:28:14OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-10-01 Cont ID  
Sent By jleahy Date 2010-10-01 Time 14:06 Rev Time 0.00
Received By jleahy Date 2010-10-01 Time 14:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-12-15 Cont ID  
Sent By lmartine Date 2010-12-15 Time 11:43 Rev Time 0.00
Received By lmartine Date 2010-12-15 Time 11:40 Sent To  
Notes
2010-12-15 11:40:35IN ZONING BOX
2010-12-15 11:06:00INCOMING SENT TO R-5. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-15 Cont ID  
Sent By lmartine Date 2010-11-10 Time 11:39 Rev Time 0.00
Received By lmartine Date 2010-11-10 Time 16:33 Sent To  
Notes
2010-11-10 17:00:27R09
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-06 Cont ID  
Sent By jgomez Date 2010-10-06 Time 11:01 Rev Time 0.00
Received By jgomez Date 2010-09-14 Time 14:56 Sent To  
Notes
2010-09-14 14:57:10R--10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-11-17 Cont ID  
Sent By jgomez Date 2010-11-17 Time 15:07 Rev Time 0.00
Received By jgomez Date 2010-11-17 Time 15:07 Sent To  
Notes
2010-11-17 15:09:11NO FEES. STAMPED BY VAL ON 11/4/10 . MU-2010-20494.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-10-05 Cont ID  
Sent By jgomez Date 2010-10-05 Time 15:45 Rev Time 0.00
Received By jgomez Date 2010-10-05 Time 15:45 Sent To  
Notes
2010-10-05 15:47:36IMPACT FEES COMMENTS:
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE REQUIRED. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2010-12-22 Cont ID  
Sent By jgomez Date 2010-12-22 Time 08:49 Rev Time 0.00
Received By jgomez Date 2010-12-22 Time 08:48 Sent To  
Notes
2010-12-22 08:49:37SEPARATE PERMITS FOR LANDSCAPE AND IRRIGATION ARE
 REQUIRED.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-12-16 Cont ID  
Sent By rkussner Date 2010-12-16 Time 18:07 Rev Time 0.00
Received By rkussner Date 2010-12-15 Time 16:32 Sent To  
Notes
2010-12-16 18:29:41***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. TWO
 (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZLDR SHALL BE
 SUBMITTED WITH THE APPLICATION AND A COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST. THE PLAN SUBMITTED
 STATES THAT THIS IS AN AS-BUILT PLAN BUT THERE IS A
 PLANT LIST. PLEASE INDICATE WHAT IS EXISTING AND WHAT
 IS PROPOSED.
  
 2. PROVIDE THE XERISCAPE TABULATION SHOWING COMPLIANCE
 WITH THE REQUIREMENTS.
  
 3. PROVIDE THE SIZE ANDS SPACING FOR ALL EXISTING AND
 PROPOSED TREES AND PLANT MATERIAL.
  
 4, PLEASE APPLY FOR A SEPARATE IRRIGATION PERMIT.
 SUBMIT TWO (2) COPIES OF THE IRRIGATION PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-09-23 Cont ID  
Sent By rkussner Date 2010-09-23 Time 15:15 Rev Time 0.00
Received By rkussner Date 2010-09-23 Time 15:15 Sent To  
Notes
2010-09-23 15:31:32***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. TWO
 (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZLDR SHALL BE
 SUBMITTED WITH THE APPLICATION AND A COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 4. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL
 AREAS TO BE PLANTED IN A CULTIVATED LANDSCAPE,
 IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120
 PERCENT COVERAGE. PLEASE APPLY FOR AN IRRIGATION PERMIT
 AND PROVIDE TWO (2) SETS OF IRRIGATION PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-11-19 Cont ID  
Sent By jgomez Date 2010-11-19 Time 17:22 Rev Time 0.00
Received By jgomez Date 2010-11-19 Time 17:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-10-06 Cont ID  
Sent By jgomez Date 2010-10-06 Time 09:43 Rev Time 0.00
Received By jgomez Date 2010-10-06 Time 09:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status N Date 2010-12-21 Cont ID  
Sent By astelly Date 2010-12-21 Time 09:06 Rev Time 0.00
Received By astelly Date 2010-12-21 Time 09:06 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-11-22 Cont ID  
Sent By astelly Date 2010-11-22 Time 10:32 Rev Time 0.00
Received By astelly Date 2010-11-22 Time 10:32 Sent To  
Notes
2010-11-22 10:34:18AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W/PROVISO
  
 A LANDSCAPE PLAN IS REQUIRED FOR THE COMPLETION OF THE
 ZONING REVIEW.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-23 Cont ID  
Sent By astelly Date 2010-09-23 Time 17:30 Rev Time 0.00
Received By astelly Date 2010-09-23 Time 17:30 Sent To  
Notes
2010-09-23 17:33:20AMY STELLY
 PLANNING AND ZONING
 822-1442
  
 PLEASE SUBMIT A SURVEY SHOWING THE LOCATION OF THE
 ADDITION.
 A LANDSCAPE PLAN MUST BE SUBMITTED PURSUANT TO THE
 ZONING CODE.
  
 YOUR SUBMISSION MAY GENERATE ADDITIONAL COMMENTS.