Plan Review Details - Permit 10090234
Plan Review Stops For Permit 10090234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-11-18 Cont ID  
Sent By jwitmer Date 2010-11-18 Time 08:37 Rev Time 0.55
Received By jwitmer Date 2010-11-18 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-15 Cont ID  
Sent By jwitmer Date 2010-09-15 Time 13:45 Rev Time 0.77
Received By jwitmer Date 2010-09-15 Time 13:00 Sent To  
Notes
2010-09-15 13:55:22BUILDING PLAN REVIEW
 PERMIT: 10090234
 ADD: 477 ROSEMARY AVE SUITE# 205/207/209/211/213/215)
 CONT: TBD
 CONTACT MIKE STELLINO
 TEL: (561)650-0900
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW: DENIED
  
 1) CONTRACTOR WILL NEED TO BE SIGNED ONTO THE PROJECT
 AND LICENSURE REVIEWED.
  
 2) PLANS WILL NEED TO BE REVIEWED BY CITY PLACE AND
 THEIR STAMP AFFIXED.
  
 3) PLANS WILL NEED TO BE REVIEWED BY PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR ASSESSMENT. IT APPEARS THAT NONE
 OF THESE SPACES HAVE BEEN REVIEWED BY P B COUNTY
 FOR CHANGE OF OCCUPANCY. OUR RECORDS INDICATE:
 07060304 UNIT# 207 -EXPIRED NEVER ISSUED
 08080246 UNIT# 209 -EXPIRED NEVER ISSUED
 03110332 UNITS 213& 215, ISSUED BUT NO IMPACT FEE STAMP
 ON PLANS NOR COUNTY RECEIPT
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
 GYPSUM BOARDS IN SHOWERS & WATER CLOSETS
  
 2509.1 WET AREAS. SHOWERS AND PUBLIC TOLIET WALLS SHALL
 CONFORM TO SECTION 1210.2 AND 1210.3.
  
 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT OR GLASS MAT
 GYPSUM BACKERS IN COMPLIANCE WITH
  
 ASTM C 1178-08 STANDARD SPECIFICATION
 FOR COATED GLASS MAT WATER-RESISTANT GYPSUM
  
 ASTM C 1288-99 STANDARD SPECIFICATION
 FOR DISCRETE NON- ASBESTOS FIBER-CEMENT INTERIOR
 SUBSTRATE SHEETS
  
 ASTM C 1325-08 STANDARD SPECIFICATION
 FOR NON-ASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS
  
 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-18 Cont ID  
Sent By jleahy Date 2010-11-18 Time 15:05 Rev Time 0.00
Received By jleahy Date 2010-11-18 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-09-16 Cont ID  
Sent By jwitmer Date 2010-09-16 Time 18:47 Rev Time 0.00
Received By jwitmer Date 2010-09-16 Time 18:47 Sent To  
Notes
2010-09-16 18:49:33OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-04 Cont ID  
Sent By mcarsill Date 2010-11-04 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2010-11-04 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-27 Cont ID  
Sent By mcarsill Date 2010-09-27 Time 15:38 Rev Time 0.00
Received By mcarsill Date 2010-09-27 Time 15:23 Sent To  
Notes
2010-09-27 15:38:42477 SOUTH ROSEMARY AVENUE
 PERMIT NUMBER 10090234
 "CONSTRUCTION OF OFFICE SPACE INCLUDING MEPE; JOINING
 OF (5) SUITES INTO (1) FOR A SINGLE TENANT SPACE"
  
  
 1. THE INSTALLATION OF KEYPADS OR CARD READERS SHALL
 NOT INTERFERE WITH THE OPERATION OF ANY EXIT DOORS.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 3. WRONG LIFE SAFETY CODE REFERENCED ON PAGE E3.01.
 SHOULD READ THE 2006 EDITION
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-19 Cont ID  
Sent By lmartine Date 2010-11-18 Time 11:07 Rev Time 0.00
Received By lmartine Date 2010-10-28 Time 11:35 Sent To  
Notes
2010-10-28 11:37:11C5
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-05 Cont ID  
Sent By jwitmer Date 2010-10-05 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2010-09-10 Time 09:23 Sent To  
Notes
2010-09-10 09:23:38C--21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-11-09 Cont ID  
Sent By hmoser Date 2010-11-09 Time 15:00 Rev Time 0.00
Received By hmoser Date 2010-11-09 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-10-05 Cont ID  
Sent By hmoser Date 2010-10-05 Time 10:17 Rev Time 0.00
Received By hmoser Date 2010-10-05 Time 10:17 Sent To  
Notes
2010-10-05 10:21:47PLANS DENIED
 PLEASE REFER TO SECTION 402 NATURAL VENTILATION , 402.3
 ADJOINING SPACES 2007 FMC .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-10-29 Cont ID  
Sent By lwagner Date 2010-10-29 Time 14:36 Rev Time 0.00
Received By lwagner Date 2010-10-29 Time 13:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By lwagner Date 2010-10-01 Time 10:01 Rev Time 0.00
Received By lwagner Date 2010-10-01 Time 09:34 Sent To  
Notes
2010-10-01 10:42:55FBC 2007 PLUMBING PLAN REVIEW
 DENIED:
  
 1. IN THE WOMENS RESTROOM THE 3 WC'S FORM A CURCUIT
 VENT. A DRY VENT IS REQUIRED BETWEEN THE LAST 2 WC'S.
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 2. THE LOUNGE SINK WASTE & VENT IS NOT SHOWN ON THE
 SANITARY RISER DIAGRAM.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By eschneid Date 2010-11-08 Time 17:28 Rev Time 0.00
Received By eschneid Date 2010-11-08 Time 17:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-28 Cont ID  
Sent By eschneid Date 2010-09-28 Time 15:39 Rev Time 0.25
Received By eschneid Date 2010-09-28 Time 15:39 Sent To  
Notes
2010-09-28 15:47:10FAILED
  
 1) PROVIDE THE DIMENSION FROM THE ROOF TO THE TOP OF
 THE NEW CONDENSERS MOUNTED ON THE ROOF.
  
 2) PROVIDE PROOF (ELEVATIONS, SITE LINES, ETC.) TO
 VERIFY THAT THE NEW CONDENSERS ARE SCREENED FROM VIEW
 IN ACCORDANCE WITH THE CITYPLACE DRI REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.