Plan Review Details - Permit 10090217
Plan Review Stops For Permit 10090217
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-05 Cont ID  
Sent By shill Date 2010-10-05 Time 08:48 Rev Time 0.00
Received By shill Date 2010-10-05 Time 08:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-13 Cont ID  
Sent By shill Date 2010-09-13 Time 18:47 Rev Time 0.00
Received By shill Date 2010-09-13 Time 18:47 Sent To  
Notes
2010-09-13 18:49:41****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE PAGE 26 OF THE PRODUCT APPROAL. 6" ANCHOR
 SPACING REQUIRED FOR 1/4" TAPCONS, 10" FOR 5/16"
 TAPCONS. INSTALLATION SCHEDULE SPECIFIES ITW 1/4", 10"
 SPACING FOR THE BOTTOM. EITHER REVISE SPACING OR REVISE
 ANCHOR TO COMPLY WITH REQUIREMENTS OF THE PRODUCT
 APPROVAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-29 Cont ID  
Sent By jwitmer Date 2010-09-29 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2010-09-29 Time 10:33 Sent To  
Notes
2010-09-29 10:33:48INCOMING SENT TO S HILL DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-13 Cont ID  
Sent By shill Date 2010-09-13 Time 18:49 Rev Time 0.00
Received By shill Date 2010-09-10 Time 08:43 Sent To  
Notes
2010-09-10 08:43:29UNDER 5 K BUILDING