Plan Review Details - Permit 10090130
Plan Review Stops For Permit 10090130
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-08 Cont ID  
Sent By jwitmer Date 2011-03-08 Time 15:48 Rev Time 0.77
Received By jwitmer Date 2011-03-08 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 08:30 Rev Time 1.25
Received By jwitmer Date 2011-02-03 Time 07:30 Sent To  
Notes
2011-02-03 08:38:06BUILDING PLAN REVIEW
 PERMIT: 10090130
 ADD: 1810 S DIXIE HWY
 CONT: MARTINO CONSTRUCTION
 TEL: (561)632-2338
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 1A) GLAZED FRONT ENTRY DOORS, NOT PART OD THE NOA
 SUBMITTED
  
 1B) 42"X 96" REAR SWING DOORS, GLAZED OR METAL ?
  
 1C) ROOFING PRODUCT APPROVAL FOR A FLAT INSULATED ROOF,
 PLEASE HIGHLIGHT WHICH SUB-SYSTEM TO BE INSTALLED, WE
 WILL ALSO NEED A ROOFING PLANS WITH WIND ZONES AND
 ASSOCIATED PRESSURES. NOTE PLEASE REVIEW TO SEE
 ENHANCED FASTENING MAY BE REQUIRED FOR ZONES 2 & 3.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-28 Cont ID  
Sent By jwitmer Date 2010-09-28 Time 07:36 Rev Time 0.77
Received By jwitmer Date 2010-09-28 Time 07:36 Sent To  
Notes
2010-09-28 11:48:03BUILDING PLAN REVIEW
 PERMIT: 10090130
 ADD: 1810 S DIXIE HWY
 CONT: MARTINO CONSTRUCTION
 TEL: (561)632-2338
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 BUILDING DESIGNOR TYPE: II-B
  
 1) SHEET# 1 WIND LOAD INFORMATION: THE PLANS INDICATE
 THE WIND EXPOSURE AS A B EXPOSURE PLEASE REVIEW FBC-B
 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS,
 INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES,
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM)
 EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 2) SINCE THIS BUILDING IS LOCATED WITHIN A EXPOSURE C
 LOCATION THE PRESSURES WILL BE GREATER THAN EXPOSURE B
 PLEASE UP DATE PLANS FOR THE GREATER PRESSURES AND
 REVIEW THE PRODUCT APPROVALS FOR THESE PRESSURES.
  
  
 3) SHEET 3 INDICATES A FLOOR PLAN WITH THE TERMINOLOGY
 WAREHOUSE SHOWROOM PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
 3A) PLEASE PROVIDE AS TO WHAT OCCUPANCY CLASSIFICATION
 THIS TENANCY WAS DESIGNED TOO, FBC-B2009
 SUPPLEMENTS.302.1 GENERAL. STRUCTURES OR PORTIONS OF
 STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO
 OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW. A
 ROOM OR SPACE THAT IS INTENDED TO BE OCCUPIED AT
 DIFFERENT TIMES FOR DIFFERENT PURPOSES SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS THAT ARE APPLICABLE TO
 EACH OF THE PURPOSES FOR WHICH THE ROOM OR SPACE WILL
 BE OCCUPIED. FOR THIS REVIEW THE OCCUPANCY SHALL BE
 CONSIDERED MERCANTILE. PLEASE EXPLAIN HOW THIS IS A
 BUSINESS OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A
 BUILDING OR STRUCTURE, OR A PORTION THEREOF, FOR
 OFFICE, PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS,
 INCLUDING STORAGE OF RECORDS AND ACCOUNTS.FBC-B 304.1.
  
 3B) PLEASE SHOW OCCUPANCY LOAD PER FBC-B TABLE
 1004.1.1.
  
 3C) THE PLANS DO NOT INDICATE A LIFE SAFETY PLAN,
 PLEASE SHOW ON SHEET# 3 THE ACTUAL FLOOR PLAN WITH
 GOODS BEING DISPLAYED,STORED AND SOLD AS WELL AS THE
 DEFINED EGRESS PATH. FBC-B 309.1, & FBC-B 1014.4.1 &
 1014.4.2.
  
 3D) THE PLANS DO NOT INDICATE IF THIS BUILDING IS FIRE
 SPRINKLERED?
  
 4) SHEET # 3 INDICATES OVER THE EXISTING OFFICE THE
 RESTROOM TO BE REMOVED PLEASE INDICATE WHAT OCCUPANCY
 WILL OCCUPY THIS ROOM?FBC-B 302.1.
  
 5) SHEET# 5 DETAIL 5-2 INDICATES THE USE OF 5 1/2
 INCHES OF SPRAY ON FOAM ONTO THE BOTTOM SIDE OF THE
 TWIN T'S. PLEASE PROVIDE COMPLIANCE WITH FBC-B 2603.4
 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN SECTIONS
 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE SEPARATED
 FROM THE INTERIOR OF A BUILDING BY AN APPROVED THERMAL
 BARRIER OF 0.5-INCH (12.7 MM) GYPSUM WALLBOARD OR
 EQUIVALENT THERMAL BARRIER MATERIAL THAT WILL LIMIT THE
 AVERAGE TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO
 NOT MORE THAN 250??F (120??C) AFTER 15 MINUTES OF FIRE
 EXPOSURE, COMPLYING WITH THE STANDARD TIME-TEMPERATURE
 CURVE OF ASTM E 119. THE THERMAL BARRIER SHALL BE
 INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE
 FOR 15 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR
 UL 1715. COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH
 SECTION 717. NOTE THIS IS ALSO LABELED A TYPE II-B
 BUILDING NEEDING TO MEET THE CRITERIA FOUND UNDER FBC-B
 603.1.
  
 6) SHEET #5 EXTERIOR WALL METAL FRAME IN-FILL WALL
 SECTIONS INDICATE THE USE OF PLYWOOD SHEATHING, PLEASE
 REVIEW FBC-B SECTION 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR TYPE II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 7) SHEET #5 EXTERIOR METAL WALL FRAME SECTION
 INDICATING THE USE OF RIB LATH AND STUCCCO, PLEASE
 REVIEW THIS NEW CHANGE IN THE 2007 FBC-B 1404.2.1.
  
 8) SHEET# 5 SECTION 3 & 5 ARE MISSING THE INSULATION TO
 THE ROOF LINE PER 11-13-402.A REQUIREMENTS SPECIFIC TO
 METHOD A. EFFICIENCIES DETERMINED BY THE ENERGYGAUGE
 SUMMIT FLA/COM METHOD A PERFORMANCE CALCULATION TO
 DEMONSTRATE COMPLIANCE WITH THIS CODE SHALL BE THE
 MINIMUM PERFORMANCE LEVEL INSTALLED IN WALLS. R-4
 INSULATION AND 1/2 INCH GYPSUM BOARD.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2011-03-21 Cont ID  
Sent By rlecky Date 2011-03-21 Time 12:06 Rev Time 0.00
Received By rlecky Date 2011-03-21 Time 12:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-09 Cont ID  
Sent By jleahy Date 2011-02-04 Time 09:30 Rev Time 0.00
Received By jleahy Date 2011-02-04 Time 09:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By jleahy Date 2010-10-01 Time 09:06 Rev Time 0.00
Received By jleahy Date 2010-10-01 Time 09:05 Sent To  
Notes
2010-10-01 09:10:08NEED ENERGY CALCULATION PER CHAPTER 13 OF THE FLORIDA
 BUILDING CODE 13-415.A,B
  
 NEED SPACE CONTROL FOR LIGHTING PER 13-415.AB.1.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-03-24 Cont ID  
Sent By wjolin Date 2011-03-24 Time 10:44 Rev Time 0.00
Received By wjolin Date 2011-03-24 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-02-03 Cont ID  
Sent By wjolin Date 2011-02-03 Time 15:37 Rev Time 0.00
Received By wjolin Date 2011-02-03 Time 15:37 Sent To  
Notes
2011-02-03 15:37:171810 SOUTH DIXIE HIGHWAY
 PERMIT #10090130
 REVIEW COMMENTS - FIRE
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY FROM INDUSTRIAL TO
 MERCANTILE.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 THE MEZZANINE STAIR IS NOT PERMITTED TO BE OPEN TO BOTH
 LEVELS PER SECTION 36.3.1 OF THE FLORIDA FIRE
 PREVENTION CODE (NFPA 101). INSIDE STAIRS SERVING AS AN
 EXIT COMPONENT SHALL BE ENCLOSED PER SECTION
 7.2.2.5.1.1 OF THE FFPC (NFPA 101).
  
 ENCLOSURE OF THE MEZZANINE OFFICE WILL REQUIRE
 ADDITIONAL EMERGENCY LIGHTING.
  
 PROVIDE STAIR AND HANDRAIL DETAILS. STAIR HANDRAILS ARE
 REQUIRED ON BOTH SIDES OF THE STAIR PER SECTION
 7.2.2.4.1.1 OF THE FFPC (NFPA 101).
  
 PROVIDE DOOR LOCKING AND LATCHING HARDWARE INFORMATION.
  
 AISLES LEADING TO EACH ARE REQUIRED. AISLES SHALL BE AT
 LEAST 36-INCHES IN WIDTH PER SECTION 36.2.5.4 OF THE
 FFPC (NFPA 101).
  
 INTERIOR WALL FINISH TO BE CLASS A OR CLASS B PER
 SECTION 36.3.3.2 OF THE FFPC (NFPA 101).
  
 TRAVEL DISTANCE TO PORTABLE FIRE EXTINGUISHERS NOT TO
 EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FUTURE 4-INCH
 PARTITION WALL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-28 Cont ID  
Sent By mcarsill Date 2010-09-28 Time 13:41 Rev Time 0.00
Received By mcarsill Date 2010-09-28 Time 13:12 Sent To  
Notes
2011-02-03 15:36:15 
  
2010-09-28 13:40:491810 SOUTH DIXIE HIGHWAY
 PERMIT NUMBER 10090130
 "BUILDING RENOVATION"
  
  
 1. BUILDING ADDRESS NOT CONTAINED IN THE TITLE BLOCK.
  
 2. ON SHEET 1 IT DECLARES THE LOCATION AS A BUSINESS
 OCCUPANCY. ON SHEET 3 IT STIPULATES "WAREHOUSE
 SHOWROOM". THE FLOOR PLAN SEEMS TO SUGGEST EITHER A
 MERCANTILE OCCUPANCY OR AS A STORAGE OCCUPANCY. PLEASE
 DECLARE CORRECT OCCUPANCY TYPE AND ADJUST OCCUPANT LOAD
 AS BOTH HAVE THESE HAVE DIFFERENT OCCUPANT LOAD FACTORS
 THAN BUSINESS. DOES RETAIL OR WHOLESALES EXCHANGES
 OCCUR AT THE PROPERTY OR ARE MATERIALS STORED AT THE
 LOCATION.
  
 3. BUILDING ADDRESS SHOWN ON PAGE 4. THE BUILDING
 ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT
 LEAST 1" WIDE THAT CONTRASTS WITH THE BACKGROUND THAT
 IS AFFIXED TO.
  
 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 5. THE TWO EMERGENCY LIGHTS DISPLAYED ON SHEET 6B MAY
 NOT BE ADEQUATE DUE TO THE SIZE OF THE SPACE. PLEASE
 EVALUATE FIXTURE COUNT AND LOCATIONS.
  
 6. PLEASE DECLARE ON PLANS THE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 7. PLEASE DECLARE IF EXISTING OR NEW PORTABLE FIRE
 EXTINGUISHERS WILL BE PRESENT.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-01-26 Cont ID  
Sent By jpapa Date 2011-01-26 Time 14:29 Rev Time 0.00
Received By jpapa Date 2011-01-26 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2011-07-14 Time 09:46 Sent To  
Notes
2011-07-14 09:47:18IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-03-24 Cont ID  
Sent By lwagner Date 2011-03-24 Time 10:44 Rev Time 0.00
Received By wjolin Date 2011-03-01 Time 11:15 Sent To  
Notes
2011-03-01 11:18:14C21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-20 Cont ID  
Sent By jgomez Date 2011-01-20 Time 11:47 Rev Time 0.00
Received By jgomez Date 2011-01-20 Time 11:23 Sent To  
Notes
2011-02-08 09:25:06C--1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-05 Cont ID  
Sent By hmoser Date 2010-10-05 Time 14:18 Rev Time 0.00
Received By hmoser Date 2010-10-05 Time 14:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-03-28 Cont ID  
Sent By lmartine Date 2011-03-28 Time 14:36 Rev Time 0.00
Received By lmartine Date 2011-03-28 Time 14:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2011-02-03 Time 08:38 Sent To  
Notes
2011-02-03 08:38:46BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-03-03 Cont ID  
Sent By rkussner Date 2011-03-03 Time 18:22 Rev Time 0.00
Received By rkussner Date 2011-03-03 Time 18:22 Sent To  
Notes
2011-03-03 18:23:50***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #11020682 FOR LANDSCAPE PERMIT
 AND PLANS--RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-01-27 Cont ID  
Sent By rkussner Date 2011-01-27 Time 10:29 Rev Time 0.00
Received By rkussner Date 2011-01-27 Time 10:29 Sent To  
Notes
2011-01-27 11:46:29***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT
 AN APPLICATION AND TWO SETS OF SIGNED AND SEALED
 LANDSCAPE PLANS. A CERTIFIED COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST, SHALL BE INCLUDED
 WITH THE SUBMITTAL.
  
 2. PLEASE APPLY FOR A SEPARATE IRRIGATION PERMIT.
 SUBMIT TWO COPIES OF THE IRRIGATION PLAN.
  
 3. PURSUANT TO SECTION 94-443 (B) (4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER FOR EACH 30 LINEAR FEET OF PORTION, THEREOF.
 CLUSTERING OF REQUIRED TREES SHALL BE SUBJECT TO CITY
 APPROVAL. A HEDGE OR OTHER SHRUB PLANTING SHALL EXTEND
 THE FULL LENGTH OF THE BUFFER. LANDSCAPING ALONG THE
 NORTH PERIMETER OF THE SITE DOES NOT MEET THIS
 REQUIREMENT.THE PROPOSED SABAL PALMS ON THE SOUTH SIDE
 OF THE BUILDING DOES NOT MEET THIS REQUIREMENT, AS
 WELL.
  
 4. PURSUANT TO SECTION 94-442 (C), PALM TREES MAY BE
 SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE SHADE
 OR FLOWERING TREES REQUIRED BY THIS ARTICLE.
  
 5. PURSUANT TO SECTION 94-445 (4) (B), WHENEVER THE
 CLUSTERING OF PALM TREES IS UTILIZED, A MINIMUM OF
 THREE PALM TREES PER CLUSTER SHALL BE REQUIRED.
  
 6. PURSUANT TO SECTION 94-443 (C) (3), OFF-STREET
 PARKING LOTS CONTAINING AT LEAST 12 INTERIOR PARKING
 SPACES SHALL CONTAIN LANDSCAPE AREAS. THE TOTAL SIZE OF
 SUCH LANDSCAPE AREAS SHALL BE EQUAL TO TEN SQUARE FEET
 FOR EACH PARKING SPACE AND SHALL BE PROVIDED WITHIN THE
 INTERIOR OF THE OF AN OFF-STREET PARKING AREA.
  
 7. PURSUANT TO SECTION 94-443 (C) (3) (A), TERMINAL
 LANDSCAPED ISLANDS SHALL NOT BE LESS THAN FIVE FEET IN
 WIDTH, EXCLUDING THE REQUIRED CURB. THE ISLAND AT THE
 WEST END OF THE PARKING ROW THAT CONTAINS SIX SPACES
 DOES NOT MEET THE MINIMUM REQUIREMENT.
  
 8. PURSUANT TO SECTION 94-444 (B), OUTDOOR GARBAGE OR
 TRASH RECEPTACLES AND OTHER MECHANICAL EQUIPMENT SHALL
 NOT BE PERMITTED UNLESS APPROPRIATE SCREENING IS
 PROVIDED. THE DUMPSTER ENCLOSURE SHALL BE LANDSCAPED
 WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.
 PAVEMENT SURROUNDING THE ENCLOSURE SHALL BE REMOVED TO
 ACCOMMODATE THE REQUIRED PLANTING.
  
 9. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEMS
 ENUMERATED IN THIS SECTION SHALL BE INCORPORATED INTO
 THE LANDSCAPE PLAN, INCLUDING THE LOCATION OF ALL
 UTILITIES (OVERHEAD AND UNDERGROUND), EASEMENTS, SITE
 LIGHTING, OVERHANGING TREE CANOPIES AND ANYTHING ELSE
 THAT MAY HAVE AN IMPACT UPON THE PROPOSED LANDSCAPING.
  
 10. PURSUANT TO SECTION 94-443 (C) (4), FOR OTHER PAVED
 AREAS UTILIZED BY MOTOR VEHICLES, INCLUDING AISLES,
 LOADING AREAS, CIRCULATING AREAS AND DRIVE-IN SERVICE
 AREAS, ADDITIONAL LANDSCAPING SHALL BE PROVIDED AS
 FOLLOWS: FOUR SQUARE FEET OF LANDSCAPED AREA SHALL BE
 REQUIRED FOR EACH 100 SQUARE FEET, OR FRACTION THEREOF.
  
 11. PLEASE PROVIDE A CITY APPROVED STRIPING DETAIL ON
 THE SITE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-10-05 Cont ID  
Sent By hmoser Date 2010-10-05 Time 14:16 Rev Time 0.00
Received By hmoser Date 2010-10-05 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-03-09 Cont ID  
Sent By lwagner Date 2011-03-09 Time 14:02 Rev Time 0.00
Received By lwagner Date 2011-03-09 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-08 Cont ID  
Sent By lwagner Date 2011-02-08 Time 14:26 Rev Time 0.00
Received By lwagner Date 2011-02-08 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By lwagner Date 2010-10-01 Time 14:39 Rev Time 0.00
Received By lwagner Date 2010-10-01 Time 14:21 Sent To  
Notes
2010-10-01 14:39:40FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET 1 SHOWS AN OCCUPANT LOAD OF 50 BUSINESS. TWO
 RESTROOMS WOULD BE REQUIRED
 FBC PLUMBING 2007 TABLE 403.1- MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES- 1 PER 25 FOR THE FIRST 50
 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-03-20 Cont ID  
Sent By astelly Date 2011-03-20 Time 12:27 Rev Time 0.00
Received By astelly Date 2011-03-20 Time 12:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-02-01 Cont ID  
Sent By astelly Date 2011-02-01 Time 17:04 Rev Time 0.00
Received By astelly Date 2011-02-01 Time 17:04 Sent To  
Notes
2011-02-01 17:23:31AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
  
  
 PARKING STALLS SHALL BE DOUBLE STRIPED PER THE STANDARD
 DETAIL SHOWN FIG. XV-2 OF SEC. 94-485 OF THE ZONING
 CODE.
  
 THE ACCESSIBLE RAMP TO THE BUILDING MUST BE SHOWN ON
 THE PLANS.
  
  
 AERIAL PHOTOGRAPHS INDICATE THAT THERE IS ONLY ONE
 ON-STREET PARKING SPACE IN FRONT OF THE PROPERTY ON S.
 DIXIE HWY. PLEASE AMEND THE DRAWINGS SO THAT THE
 ON-STREET PARKING IS PROPERLY DEPICTED.
  
 REPEAT COMMENT
 THE PROPERTIES MUST BE UNIFIED. PLEASE PROVIDE PROOF OF
 UNIFICATION.
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-23 Cont ID  
Sent By astelly Date 2010-09-23 Time 17:20 Rev Time 0.00
Received By astelly Date 2010-09-23 Time 17:20 Sent To  
Notes
2010-09-23 17:24:23AMY STELLY
 PLANNING AND ZONING
 822-1442
  
 S. DIXIE AND WILDEMERE PROPERTIES MUST BE UNIFIED.
 PARKING MUST BE RECONFIGURED TO ELIMINATE BACKING OUT
 INTO THE STREET.
 SINCE THE VALUE OF THE RENOVATION EXCEEDS 50% OF THE
 IMPROVEMENT VALUE OF THE STRUCTURE, THE LANDSCAPING
 MUST BE BROUGHT UP TO CODE.
  
 A MEETING WITH THE CONTRACTOR HAS BEEN REQUESTED.