Plan Review Details - Permit 10090080
Plan Review Stops For Permit 10090080
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-28 Cont ID  
Sent By jwitmer Date 2011-04-28 Time 09:35 Rev Time 1.50
Received By jwitmer Date 2011-04-28 Time 08:00 Sent To  
Notes
2011-04-28 10:25:54BUILDING PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 SHED PERMIT: 2578J 18 FTX18FT 11-1-84 ORIGINAL PERMIT
 FOR SHED.
  
 THIS REVIEW WILL USE THE 2007 EXISTING BUILDING CODE
 CHAPTER 9 CHANGE IN OCCUPANCY FOR THE BASIS OF THIS
 REVIEW. EX. BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 EX. BLDG CODE 903.1 GENERAL. BUILDING ELEMENTS AND
 MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE
 OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 912.
  
 EX. BLDG CODE 905.1 GENERAL. MEANS OF EGRESS IN
 PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.
  
 BUILDING PROVISO:
  
 BUILDINGS AND STRUCTURES ARE TO COMPLY WITH THE 2007/09
 EXISTING BUILDING CODE 907.2, SUBJECT TO A CHANGE OF
 OCCUPANCY RESULTING IN A HIGHER IMPORTANCE FACTORS
 BASED ON THTE FLORIDA BUILDING CODE TABLE 1604.5 SHALL
 BE ANALYZED AND SHALL COMPLY WITH THE WIND LOAD
 PROVISONS OF THE FLORIDA BUILDING CODE, BUILDING.
 SECTION 1609 WIND LOADS .
  
 1609.1.1 WIND LOADS ON EVERY STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTER 6 OF ASCE 7. THE
 TYPE OF OPENING PROTECTION REQUIRED, THE BASIC WIND
 SPEED AND EXPOSURE CATEGORY FOR A SITE IS PERMITTED TO
 BE DETERMINED IN ACCORDANCE WITH SECTION 1609 OR ASCE
 7.
  
 1609.1.2 PROTECTION OF OPENINGS. IN WIND-BORNE DEBRIS
 REGIONS, GLAZING IN BUILDINGS SHALL BE IMPACT RESISTANT
 OR PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING
 THE REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E
 1996, ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING
 DOORS) OR MIAMI-DADE TAS 201, 202 AND 203 OR AAMA 506.
  
 THE BUILDING OFFICIAL HAS DETERMINED THAT THE CHANGE OF
 OCCUPANCY AND THE STRUCTURES USEAGE HAS CHANGED TO A
 HIGHER IMPORTANCE FACTOR
 THAT THE SECTIONS IN 1609.1.1 & 1609.1.2 WILL NOT ONLY
 REQUIRE WINDOWS THAT MEET THE WIND PRESSURES BUT
 REQUIRE OPENING PROTECTION BY EITHER
 THE WINDOWS MEETING THE TEST REQUIREMENTS FOR LARGE
 MISSILE IMPACT TESTING, OR BY COVERING THE WINDOWS WITH
 APPROVED SHUTTERS OR THE ALTERNATIVE
 OF WOOD STRUCTURAL PANELS MEETING THE REQUIREMENTS OF
 1609.1.2 EXCEPTION # 1 .
 1. WOOD STRUCTURAL PANELS WITH A MINIMUM THICKNESS OF
 7/16 INCH (11.1 MM) AND A MAXIMUM SPAN OF 8 FEET (2438
 MM) SHALL BE PERMITTED FOR OPENING PROTECTION IN ONE-
 AND TWO-STORY BUILDINGS. PANELS SHALL BE PRECUT SO THAT
 THEY SHALL BE ATTACHED TO THE FRAMING SURROUNDING THE
 OPENING CONTAINING THE PRODUCT WITH THE GLAZED
 OPENINGS. PANELS SHALL BE PREDRILLED AS REQUIRED FOR
 THE ANCHORAGE METHOD AND ALL REQUIRED HARDWARE SHALL BE
 PROVIDED. ATTACHMENT SHALL BE DESIGNED TO RESIST THE
 COMPONENTS AND CLADDING LOADS DETERMINED IN ACCORDANCE
 WITH THE PROVISIONS OF ASCE 7, WITH PERMANENT
 CORROSION-RESISTANT ATTACHMENT HARDWARE PROVIDED AND
 ANCHORS PERMANENTLY INSTALLED ON THE BUILDING.
 ATTACHMENT IN ACCORDANCE WITH TABLE 1609.1.2, WITH
 PERMANENT CORROSION RESISTANT ATTACHMENT HARDWARE
 PROVIDED AND ANCHORS PERMANENTLY INSTALLED ON THE
 BUILDING IS PERMITTED FOR BUILDINGS WITH A MEAN ROOF
 HEIGHT OF 45 FEET (13 716 MM) OR LESS WHERE WIND SPEEDS
 DO NOT EXCEED 140 MPH (63 M/S)
  
 COMPLIANCE WILL NEED TO BE MET BY FINAL INSPECTION.
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-05 Cont ID  
Sent By jwitmer Date 2010-10-05 Time 15:53 Rev Time 4.00
Received By jwitmer Date 2010-10-05 Time 15:53 Sent To  
Notes
2010-10-05 15:55:30BUILDING PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 SHED PERMIT: 2578J 18???X18??? 11-1-84 ORIGINAL PERMIT
 FOR SHED.
  
 THIS REVIEW WILL USE THE 2007 EXISTING BUILDING CODE
 CHAPTER 9 CHANGE IN OCCUPANCY FOR THE BASIS OF THIS
 REVIEW. EX. BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 EX. BLDG CODE 903.1 GENERAL. BUILDING ELEMENTS AND
 MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE
 OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 912.
  
 EX. BLDG CODE 905.1 GENERAL. MEANS OF EGRESS IN
 PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES THE SHED WAS BUILT IN THE
 1980???S AND COMPLIANT TO THE SBCCI WIND PROVISIONS.
 PLEASE VISIT EX. BLDG CODE 907.2 WIND LOADS. BUILDINGS
 AND STRUCTURES SUBJECT TO A CHANGE OF OCCUPANCY WHERE
 SUCH CHANGE IN THE NATURE OF OCCUPANCY RESULTS IN
 HIGHER WIND IMPORTANCE FACTORS BASED ON THE FLORIDA
 BUILDING CODE, BUILDING TABLE 1604.5, SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND LOAD
 PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING .
 SINCE THE ORIGINAL SHED WAS BUILT AS A NON-HABITUAL
 STRUCTURE THE IMPORTANCE FACTOR OF 0.77 WOULD HAVE BEEN
 USED, NOW THE BUILDING CLASSIFICATION OR CATEGORY IS
 NOW II AND A 1.00. PLEASE PROVIDE WIND DESIGN CRITERIA
 WITH PRESSURES FOR WINDOWS AND DOORS. FBC-R TABLE
 301.2(2)
  
 2) EXISTING BUILDING CODE SECTION 912.1.1 COMPLIANCE
 WITH CHAPTER 8. THE REQUIREMENTS OF CHAPTER 8 SHALL BE
 APPLICABLE THROUGHOUT THE BUILDING FOR THE NEW
 OCCUPANCY CLASSIFICATION BASED ON THE SEPARATION
 CONDITIONS SET FORTH IN SECTIONS 912.1.1.1 AND
 912.1.1.2.
  
 801.2 COMPLIANCE. IN ADDITION TO THE PROVISIONS OF THIS
 CHAPTER, WORK SHALL COMPLY WITH ALL OF THE REQUIREMENTS
 OF CHAPTERS 6 AND 7.
  
 2007EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING/ RESIDENTIAL.
  
 3) EX. BLDG CODE 912.1.2 FIRE PROTECTION AND INTERIOR
 FINISH. THE PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR
 FIRE PROTECTION AND INTERIOR FINISH, RESPECTIVELY,
 SHALL APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF
 OCCUPANCY CLASSIFICATION. PLEASE REVIEW FBC- R 315.
  
 3A) EX. BUILDING CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. PLANS FAIL TO INDICATE
 SMOKE DETECTORS WITHIN THE BEDROOM AND OUTSIDE OF THE
 BEDROOM.
  
 R313.1 SMOKE DETECTION AND NOTIFICATION. ALL SMOKE
 ALARMS SHALL BE LISTED IN ACCORDANCE WITH UL 217 AND
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CODE AND THE HOUSEHOLD FIRE WARNING EQUIPMENT
 PROVISIONS OF NFPA 72.
 R313.2 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 3B) EX. BLDG CODE 912.3 INTERIOR FINISH. IN AREAS OF
 THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 4) EX. BLDG CODE 912.4.1 MEANS OF EGRESS FOR CHANGE TO
 HIGHER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 GROUP IS MADE TO A HIGHER HAZARD CATEGORY (LOWER
 NUMBER) AS SHOWN IN TABLE 912.4, THE MEANS OF EGRESS
 SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE
 FLORIDA BUILDING CODE, BUILDING . UTILITY 5 LOWEST
 HAZARD TO A 4 R-3 OCCUPANCY.
  
 EXCEPTIONS:7 . WHERE EMERGENCY ESCAPE AND RESCUE
 OPENINGS ARE REQUIRED, AN EXISTING OPERABLE WINDOW WITH
 CLEAR OPENING AREA NO LESS THAN 4 SQUARE FEET (0.38 M2)
 AND WITH MINIMUM OPENING HEIGHT AND WIDTH OF 22 INCHES
 (559 MM) AND 20 INCHES (508 MM), RESPECTIVELY, WITH
 MAXIMUM SILL HEIGHT AT 44 INCHES (1118 MM) ABOVE THE
 FLOOR OR APPROVED PERMANENT ELEVATED AREA, SHALL BE
 ACCEPTED AS AN EMERGENCY ESCAPE AND RESCUE OPENING.
 PHOTOGRAPHS TAKEN BY THE ZONING DEPARTMENT INDICATE TWO
 A/C UNITS WITHIN THE WINDOWS, THE BEDROOM UNIT BLOCKS
 THE CLEAR OPENING REQUIRED BY EX BLDG CODE 912.4.1 EX #
 7.
  
 5) EX. BLDG CODE SEE COMMENT# 2 CHANGE OF OCCUPANCY AND
 COMPLIANCE WITH CHAPTERS 6,7 & 8. EX BLDG CODE 606.4
 REPLACEMENT OF WINDOWS AND DOORS. THE REPLACEMENT OF
 GARAGE DOORS, EXTERIOR DOORS, SKYLIGHTS, OPERATIVE AND
 INOPERATIVE WINDOWS SHALL BE DESIGNED AND CONSTRUCTED
 TO COMPLY WITH CHAPT FBC- R613.5
 FBC-R 613.5 WIND-BORNE DEBRIS PROTECTION. PROTECTION OF
 EXTERIOR WINDOWS, GLASS DOORS AND OTHER GLAZED AREAS
 SHALL BE IN ACCORDANCE WITH SECTION FBC-R301.2.1.2.
  
 FBC-R301.2.1.2 PROTECTION OF OPENINGS. WINDOWS IN
 BUILDINGS LOCATED IN WIND-BORNE DEBRIS REGIONS SHALL
 HAVE GLAZED OPENINGS PROTECTED FROM WIND-BORNE DEBRIS.
 GLAZED OPENING PROTECTION FOR WIND-BORNE DEBRIS SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF AN
 APPROVED IMPACT RESISTING STANDARD OR ASTM E 1996 AND
 ASTM E 1886, SSTD 12, ANSI/DASMA 115 (FOR GARAGE DOORS)
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
  
 PRODUCT APPROVALS SUBMITTED ARE FOR A NON-IMPACT
 GLAZING, PLEASE SUBMIT OPENING PROTECTION PRODUCT
 APPROVALS. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 6) PLEASE PROVIDE A SURVEY OR SITE PLAN INDICATING THE
 LOCATION OF THE STRUCTURE???S BACK WALL AND DISTANCE TO
 THE PROPERTY LINE. EX. BUILD CODE 912.6 EXTERIOR WALL
 FIRE-RESISTANCE RATINGS. HAZARD CATEGORIES IN REGARD TO
 FIRE-RESISTANCE RATINGS OF EXTERIOR WALLS SHALL BE IN
 ACCORDANCE WITH TABLE 912.6. UTILITY # 4 LOWEST HAZARD
 TO A R-3 HAZARD LEVEL 3.
 912.6.1 EXTERIOR WALL RATING FOR CHANGE OF OCCUPANCY
 CLASSIFICATION TO A HIGHER HAZARD CATEGORY. WHEN A
 CHANGE OF OCCUPANCY GROUP IS MADE TO A HIGHER HAZARD
 CATEGORY AS SHOWN IN TABLE 912.6, EXTERIOR WALLS SHALL
 HAVE FIRE RESISTANCE AND EXTERIOR OPENING PROTECTIVES
 AS REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING .
 PLEASE REVIEW FBC-R
 TABLE 302.1.
  
 7) EX BLDG CODE 808.1. MINIMUM REQUIREMENTS,
 ALTERATIONS MADE TO THIS CHAPTER SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THE
 FBC-B/ R.
  
 8) PLEASE NOTE ZONINGS REQUIREMENTS TO OBTAIN THE
 PROPER MECHANICAL, PLUMBING & ELECTRICAL PERMITS FOR
 THE BACK BUILDING THAT IS UNDERGOING A CHANGE IN
 OCCUPANCY.
 CURRENTLY APPLIED FOR ARE A PLUMBING PERMIT 10090078 TO
 RESURFACE A SHOWER, REPLACE A SINK & TOILET IN SAME
 LOCATION, THIS APPLICATION DOES NOT INDICATE IF IT IS
 FOR THE FRONT OR REAR BUILDING NOR DOES IT PROVIDE ANY
 INFORMATION AS TO MAKE THE BACK UNIT CODE COMPLIANT.
  
 THE SECOND PERMIT APPLIED FOR IS A SEPARATE ELECTRICAL
 PERMIT TO COTTAGE IN REAR, 10090805.
 NO ELECTRICAL PERMIT HAS BEEN APPLIED FOR IN REGARDS TO
 THE CHANGE OF OCCUPANCY.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-04-28 Cont ID  
Sent By jwitmer Date 2011-04-28 Time 10:29 Rev Time 0.33
Received By jwitmer Date 2011-04-28 Time 10:27 Sent To  
Notes
2011-04-28 10:31:43ELECTRICAL PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2008 NEC
  
 ELECTRICAL PROVISO:
  
 A POSSIBLE CONDITION. EXISTING BUILDING CODE/ LEVEL 2/
 708.3.7.2 REPLACEMENT RECEPTACLES. FOR REPLACEMENT OF
 NONGROUNDING-TYPE RECEPTACLES WITH GROUNDING-TYPE
 RECEPTACLES AND FOR BRANCH CIRCUITS THAT DO NOT HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR IN THE BRANCH CIRCUITRY,
 THE GROUNDING CONDUCTOR OF A GROUNDING-TYPE RECEPTACLE
 OUTLET SHALL BE PERMITTED TO BE GROUNDED TO ANY
 ACCESSIBLE POINT ON THE GROUNDING ELECTRODE SYSTEM, OR
 TO ANY ACCESSIBLE POINT ON THE GROUNDING ELECTRODE
 CONDUCTOR, IN ACCORDANCE WITH ARTICLE 250.130(C) OF
 CHAPTER 27 OF THE FLORIDA BUILDING CODE, BUILDING
 JAMES A. WITMER C.B.O.
 SFP-100 ONE & TWO FAMILY PLAN REVIEW
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-10-05 Cont ID  
Sent By jwitmer Date 2010-10-05 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2010-10-05 Time 15:59 Sent To  
Notes
2010-10-05 16:00:17ELECTRICAL PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2008 NEC
  
 SHED PERMIT: 2578J 18 FT X 18 FT 11-1-84 ORIGINAL
 PERMIT FOR SHED.
  
 THIS REVIEW WILL USE THE 2007 EXISTING BUILDING CODE
 CHAPTER 9 CHANGE IN OCCUPANCY FOR THE BASIS OF THIS
 REVIEW. EX. BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 EX. BLDG CODE 903.1 GENERAL. BUILDING ELEMENTS AND
 MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE
 OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 912.
  
  
 1ST REVIEW
 ACTION: DENIED
 1) EX. BLDG CODE 908.2 UNSAFE CONDITIONS. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED, ALL UNSAFE CONDITIONS
 SHALL BE CORRECTED WITHOUT REQUIRING THAT ALL PARTS OF
 THE ELECTRICAL SYSTEM BE BROUGHT UP TO THE CURRENT
 EDITION OF CHAPTER 27 OF THE FLORIDA BUILDING CODE,
 BUILDING .
  
 1A) PLEASE PROVIDE LOAD CALCULATIONS PER2008 NEC 220.
 I-IV .
  
  
 1B) 2008 NEC- NEW ARC-FAULT PROTECTION IS NOW REQUIRED
 IN RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH
 CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED
 BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER
 120 VOLTS 2110.12(B)
  
 1C) 2008 NEC-NEW MULTI-WIRE BRANCH CIRCUITS THAT SHARE
 A COMMON GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 1D) KITCHEN CABINETRY GFIC OUTLET (E3), PLEASE PROVIDE
 COMPLIANCE WITH 210.11(C)(1) SMALL-APPLIANCE BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE
 PROVIDED FOR ALL RECEPTACLE OUTLETS SPECIFIED BY
 210.52(B).
 REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), 21011.C.3
  
 1E) BATHROOM GFIC OUTLET PLANS FAIL TO INDICATE
 COMPLIANCE WITH SECTION 210.11 (C)(3) BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS.
  
 1F) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS
 REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH
 CIRCUIT. LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2
 & 220.52.3
  
 1G) LAUNDRY BRANCH CIRCUITS: LAUNDRY BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE ADDITIONAL
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 THE LAUNDRY RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F).
 THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS.
  
 1H) . DRYER OUTLET.220.54 ELECTRIC CLOTHES DRYERS ???
 DWELLING UNIT(S)
 THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A
 DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS
 (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS
 LARGER, FOR EACH DRYER SERVED.
  
 1I) A POSSIBLE CONDITION. EXISTING BUILDING CODE/ LEVEL
 2/ 708.3.7.2 REPLACEMENT RECEPTACLES. FOR REPLACEMENT
 OF NONGROUNDING-TYPE RECEPTACLES WITH GROUNDING-TYPE
 RECEPTACLES AND FOR BRANCH CIRCUITS THAT DO NOT HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR IN THE BRANCH CIRCUITRY,
 THE GROUNDING CONDUCTOR OF A GROUNDING-TYPE RECEPTACLE
 OUTLET SHALL BE PERMITTED TO BE GROUNDED TO ANY
 ACCESSIBLE POINT ON THE GROUNDING ELECTRODE SYSTEM, OR
 TO ANY ACCESSIBLE POINT ON THE GROUNDING ELECTRODE
 CONDUCTOR, IN ACCORDANCE WITH ARTICLE 250.130(C) OF
 CHAPTER 27 OF THE FLORIDA BUILDING CODE, BUILDING
  
 1J) THE BEDROOM DOES INDICATE A SMOKE ALARM WITHIN THE
 UNIT OR ONE OUTSIDE OF THE BEDROOM. FBC RESIDENTIAL
 313.2(2) AND NFPA 72.
 THE SMOKE ALARMS LOCATED WITHIN 20' OF COOKING WILL
 NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE
 ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20
 FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 2) 908.4 NUMBER OF ELECTRICAL OUTLETS. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED, THE NUMBER OF ELECTRICAL
 OUTLETS SHALL COMPLY WITH CHAPTER 27 OF THE FLORIDA
 BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY.
 2008 NEC 210.50(A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET.
  
 2008 NEC 210.50(A)(2)(1) ANY SPACE 2 FEET OR MORE IN
 WIDTH (INCLUDING SPACE MEASURED AROUND CORNERS) AND
 UNBROKEN ALONG THE FLOOR LINE BY DOORS, FIREPLACES, AND
 SIMILAR OPENINGS.
 2A) THE BEDROOM WALL COMMON WITH THE LIVING ROOM.
  
 2B) THE LIVING ROOM WALL LEFT OF THE ENTRY DOOR.
  
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-27 Cont ID  
Sent By jwitmer Date 2011-05-27 Time 13:40 Rev Time 0.00
Received By jwitmer Date 2011-04-27 Time 14:34 Sent To  
Notes
2011-04-27 14:34:43R-3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-20 Cont ID  
Sent By lmartine Date 2010-10-14 Time 10:35 Rev Time 0.00
Received By lmartine Date 2010-09-28 Time 11:54 Sent To  
Notes
2010-09-28 11:54:45R--1
 EXPEDITE PER DOUG

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-05-27 Cont ID  
Sent By jwitmer Date 2011-05-27 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2011-05-27 Time 13:38 Sent To  
Notes
2011-05-27 13:39:57PLANS STAMPED FROM P B C IMPACT FEE DEPARTMENT- NO FEES
 DUE! JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-05-19 Cont ID  
Sent By jwitmer Date 2011-05-19 Time 13:56 Rev Time 2.22
Received By jwitmer Date 2011-04-28 Time 10:32 Sent To  
Notes
2011-05-19 13:57:30PLUMBING PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- W/ 2009 FBC
 SUPPLEMENTS
 MAY 19/ 2011
  
 PLUMBING PLAN REVIEW
 PLUMBING PROVISO:
  
  
  
  
 1) A REVISION WILL BE REQUIRED FOR THE PLUMBING
 DRAINAGE FLOOR PLAN & SANITARY ISOMETRIC. THE CURRENT
 LAYOUT INDICATES THE KITCHEN AND WASHING MACHINE DRAINS
 TYING INTO A WET VENT (BATHROOM GROUP) A PLUMBING CODE
 VIOLATION PER (FBC-P909.1). THE PREVIOUS PLAN REVIEW
 REQUESTED A VIDEO OF THE SANITARY AND ISOMETRIC OF WHAT
 WAS INSTALLED WITHOUT PERMIT. THE ISOMETRIC WAS NOT
 DELIVERED BUT THE VIDEO WAS PRESENTED AND IT IS EVIDENT
 IN THE VIDEO THE PIPES ARE BACK PITCHED RETAINING WATER
 IN THE PIPES CREATING A SECOND CODE ISSUE (FBC-P
 704.1/TABLE 704.1). IT APPEARS THAT THE INSTALLATION
 MAY HAVE BEEN INSTALLED BY AN O/B, AND WE WOULD SUGGEST
 YOU CONTACT A PLUMBING CONTRACTOR TO CORRECT THE CODE
 VIOLATIONS WITH NEW SANITARY OR PORTION THERE OF AND
 REVISION. WE WOULD BE GLAD TO MEET WITH WHOEVER YOU
 WOULD LIKE BEFORE WORK BEGINS. NOTE THIS REVISION WOULD
 NEED TO BE SEALED BY THE DESIGNER OF RECORD.
  
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
2011-04-28 10:47:49WAITING FOR OWNER TO BRING IN VIDEO OF SANITARY SEWER
 FOR PLUMBING REVIEW. JW

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-06 Cont ID  
Sent By jwitmer Date 2010-10-06 Time 08:42 Rev Time 0.55
Received By jwitmer Date 2010-10-06 Time 08:42 Sent To  
Notes
2010-10-06 08:43:20PLUMBING PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
  
 SHED PERMIT: 2578J 18FTX18FT 11-1-84 ORIGINAL PERMIT
 FOR SHED.
  
 THIS REVIEW WILL USE THE 2007 EXISTING BUILDING CODE
 CHAPTER 9 CHANGE IN OCCUPANCY FOR THE BASIS OF THIS
 REVIEW. EX. BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 EX. BLDG CODE 903.1 GENERAL. BUILDING ELEMENTS AND
 MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE
 OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 912.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 EX BLDG CODE 910.1 INCREASED DEMAND. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING
 FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE PLUMBING , THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, PLUMBING PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY.
  
 VIDEO TAPE IN VHS THE SANITARY SYSTEM AND SUBMIT TO THE
 BUILDING DEPARTMENT FOR REVIEW
 BY CHIEF PLUMBING INSPECTOR FOR CODE COMPLIANCE.
  
 PROVIDE A PLUMBING ISOMETRIC OF SANITARY FROM THE VIDEO
 OF SANITARY SYSTEM.
  
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-05-25 Cont ID  
Sent By lfranco Date 2011-05-25 Time 10:54 Rev Time 0.00
Received By lfranco Date 2011-05-25 Time 10:54 Sent To  
Notes
2011-05-25 11:05:12PLANNING AND ZONING: **** PASSED, PER ZBA FINAL ORDER
 NO. 3264 - CLASS B ONLY FOR THE LOT WIDTH WAIVER TO
 ALLOW FOR ADDITIONAL ACCESSORY STRUCTURE. ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
  
  NOTE: 2. THIS PROPERTY WAS PART OF A CLASS B SPECIAL
 USE PERMIT TO ALLOW THE ACCESSORY STRUCTURE. THE FINAL
 ORDER 3264 WAS APPROVED WITH CONDITIONS ON APRIL 1,
 2010. THE FOLLOWING IS AN EXCERPT OF THE CONDITIONS:
  
  
 A. THE APPLICANT SHALL APPLY AND OBTAIN A BUILDING
 PERMIT TO RECTIFY THE CONVERSION OF THE EXISTING
 ACCESSORY STRUCTURE INTO A DWELLING UNIT, OTHERWISE,
 THE STRUCTURE WILL HAVE TO BE REPLACED WITH THE
 APPROPRIATE PERMITS AND MEETING ALL REGULATIONS OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS ("ZLDR") AND
 BUILDING CODE;
  
 B. THE SITE SHALL BE DEVELOPED IN ACCORDANCE WITH THE
 FOLLOWING PLANS, ONLY IF THE CONVERTED ACCESSORY
 APARTMENT STRUCTURE SHOWN ON PLANS IS DEEMED TO MEET
 ALL CODE REQUIREMENTS TO BECOME A DWELLING UNIT
 ("EXHIBIT A"):
  
 I. "AS-BUILT," SITE PLAN, FLOOR PLAN AND ELEVATIONS,
 SHEET A-1, SIGNED AND SEALED BY DEREK SCHENAVAR, P.E.
 OF DKK CONSULTING, INC., ON FEBRUARY 2, 2010.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-10-14 Cont ID  
Sent By lfranco Date 2010-10-14 Time 14:22 Rev Time 0.00
Received By lfranco Date 2010-10-14 Time 14:22 Sent To  
Notes
2010-10-14 14:24:59PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
 SHOW DIMENSIONS FROM SHED TO ALL PROPERTY LINES ON
 SURVEY AND PLANS.
  
 NOTE: 2. THIS PROPERTY WAS PART OF A CLASS B SPECIAL
 USE PERMIT TO ALLOW THE ACCESSORY STRUCTURE. THE FINAL
 ORDER 3264 WAS APPROVED WITH CONDITIONS ON APRIL 1,
 2010. THE FOLLOWING IS AN EXCERPT OF THE CONDITIONS:
  
  
 A. THE APPLICANT SHALL APPLY AND OBTAIN A BUILDING
 PERMIT TO RECTIFY THE CONVERSION OF THE EXISTING
 ACCESSORY STRUCTURE INTO A DWELLING UNIT, OTHERWISE,
 THE STRUCTURE WILL HAVE TO BE REPLACED WITH THE
 APPROPRIATE PERMITS AND MEETING ALL REGULATIONS OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS ("ZLDR") AND
 BUILDING CODE;
  
 B. THE SITE SHALL BE DEVELOPED IN ACCORDANCE WITH THE
 FOLLOWING PLANS, ONLY IF THE CONVERTED ACCESSORY
 APARTMENT STRUCTURE SHOWN ON PLANS IS DEEMED TO MEET
 ALL CODE REQUIREMENTS TO BECOME A DWELLING UNIT
 ("EXHIBIT A"):
  
 I. "AS-BUILT," SITE PLAN, FLOOR PLAN AND ELEVATIONS,
 SHEET A-1, SIGNED AND SEALED BY DEREK SCHENAVAR, P.E.
 OF DKK CONSULTING, INC., ON FEBRUARY 2, 2010.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  