Plan Review Details - Permit 10090025
Plan Review Stops For Permit 10090025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-07 Cont ID  
Sent By jwitmer Date 2010-10-07 Time 11:50 Rev Time 0.50
Received By jwitmer Date 2010-10-07 Time 11:50 Sent To  
Notes
2010-10-07 11:52:38BUILDING PROVISO:
 THE CURRENT PLAN INDICATES AN EXIT LIGHT IN FRONT OF
 THE STORAGE ROOM PLEASE COMPLY WITH,
 FBC-B 1014.2.2 2EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL OR PARTIAL HEIGHT FIXED WALLS
 OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE REQUIRED
 WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA TO THE
 EXIT WITHOUT OBSTRUCTIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-21 Cont ID  
Sent By jwitmer Date 2010-09-21 Time 16:37 Rev Time 0.55
Received By jwitmer Date 2010-09-21 Time 16:37 Sent To  
Notes
2010-09-21 16:57:37BUILDING PLAN REVIEW
 PERMIT: 10090025
 ADD: 1732 45TH ST
 CONT: G FOSTER CONTRACTING
 TEL: (954)254-8907
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 EXISTING BUILDING CODE, PLEASE PROVIDE TO WHICH
 COMPLIANCE METHOD THIS PROJECT WAS DESIGNED TOO.
 101.5 COMPLIANCE METHODS.
  
 101.5.1 PRESCRIPTIVE COMPLIANCE METHOD. REPAIRS,
 ALTERATIONS, ADDITIONS AND CHANGES OF OCCUPANCY
 COMPLYING WITH CHAPTER 3 OF THIS CODE IN BUILDINGS
 COMPLYING WITH THE FLORIDA FIRE PREVENTION CODE SHALL
 BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS OF THIS
 CODE.
  
 101.5.2 WORK AREA COMPLIANCE METHOD. REPAIRS,
 ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY AND
 RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 4 THROUGH 12 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE. IF THIS METHOD IS YOUR DESIGN METHOD
 PLEASE REVIEW FL EXIST
 BLDG CODE: 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 101.5.3 PERFORMANCE COMPLIANCE METHOD. REPAIRS,
 ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY AND
 RELOCATED BUILDINGS COMPLYING WITH CHAPTER 13 OF THIS
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
  
 2) SHEET A-2 INDICATES VARIOUS WALL SECTIONS LOCATED ON
 SHEET A-4 WHICH IS NOT FOUND IN THE PLANS OR SHEET
 INDEX, ADDITIONAL INFORMATION IS REQUIRED? 106.1.2.
  
 3) SHEET A-2 ALSO INDICATES TRAVEL THROUGH A STOREROOM
 TO REACH ONE OF THE EXITS: FBC-B 1014.2.2 2. EGRESS
 SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS
 OR SPACES USED FOR SIMILAR PURPOSES.
  
 EXCEPTIONS:
  
 1. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH A KITCHEN
 AREA SERVING ADJOINING ROOMS CONSTITUTING PART OF THE
 SAME DWELLING UNIT OR SLEEPING UNIT.
  
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL OR PARTIAL HEIGHT FIXED WALLS
 OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE REQUIRED
 WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA TO THE
 EXIT WITHOUT OBSTRUCTIONS.
  
 3. AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT
 CAN BE LOCKED TO PREVENT EGRESS.
  
 4. MEANS OF EGRESS FROM DWELLING UNITS OR SLEEPING
 AREAS SHALL NOT LEAD THROUGH OTHER SLEEPING AREAS,
 TOILET ROOMS OR BATHROOMS.
  
 4) PLEASE PROVIDE COMPLIANCE WITH 803.1 GENERAL.
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH
 MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN
 ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEXES.
  
 CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450.
  
 CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450.
  
 CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-09-22 Cont ID  
Sent By dwise Date 2010-09-22 Time 19:28 Rev Time 0.00
Received By dwise Date 2010-09-22 Time 19:28 Sent To  
Notes
2010-09-22 19:29:03OK BY JOHN DICKENSON - HYBYRD

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-21 Cont ID  
Sent By mcarsill Date 2010-10-21 Time 13:47 Rev Time 0.00
Received By mcarsill Date 2010-10-21 Time 13:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-21 Cont ID  
Sent By mcarsill Date 2010-09-21 Time 10:35 Rev Time 0.00
Received By mcarsill Date 2010-09-21 Time 10:15 Sent To  
Notes
2010-09-21 10:35:041732 W 45TH STREET
 PERMIT NUMBER 10090025
 "TENANT BUILD-OUT FOR SHOE STORE; REMOVE EXISTING
 WALLS-NEW GRID CEILING-ENLARGE EXISTING BATHROOMS"
  
  
 1. ON PAGE C-1, THE LOCATION MAP APPEARS TO BE
 INCORRECT. THE BUILDING IS WEST OF AUSTRALIAN AVENUE,
 NOT EAST OF AUSTRALIAN AVENUE.
  
 2. PLEASE VERIFY CORRECT ADDRESS FOR THE BUILDING.
 STAFF HAS CHECKED THE PROPERTY CONTROL NUMBER ON THE
 PERMIT APPLICATION AND IT COMES BACK TO 1700 45TH
 STREET NOT 1732 45TH STREET.
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS
 OFTEN AS NECESSARY.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 6. HOW WILL EXIT ACCESS BE MAINTAINED IN THE STORE
 ROOM. PLEASE ADVISE HOW TRAVEL PATH WILL BE MAINTAINED.
  
 7. EXISTING FIRE WALLS ARE TO BE VERIFIED THAT THE ONE
 HOUR FIRE SEPARATION EXISTS AND THAT ALL PENETRATIONS
 ARE PROPERLY SEALED WITH APPROVED MATERIALS AS
 DESCRIBED ON PAGE A-3.
  
 8. PLANS DO NOT CALL OUT OR MAKE REFERENCE TO AUTOMATIC
 FIRE SPRINKLERS OR FIRE ALARM EQUIPMENT. THERE IS A
 NOTE ON PAGE E-2 "PROVIDE KNOX BOX FOR FIRE DEPT.
 W/SIGN STATING "FIRE ALARM CONTROL PANEL INSIDE" AT
 ENTRY TO LEADING TO FACP". COULD NOT LOCATE ANY FIRE
 ALARM CONTROL PANEL ON DRAWINGS.
  
 9. PLEASE PROVIDE MORE DETAILS ON THE PORTABLE FIRE
 EXTINGUISHERS DISPLAYED ON THE PLANS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-22 Cont ID  
Sent By lmartine Date 2010-10-21 Time 10:48 Rev Time 0.00
Received By lmartine Date 2010-10-06 Time 10:46 Sent To  
Notes
2010-10-06 10:52:08C7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2010-09-27 Cont ID  
Sent By hmoser Date 2010-09-27 Time 14:58 Rev Time 0.00
Received By hmoser Date 2010-09-02 Time 11:00 Sent To  
Notes
2010-09-02 11:00:43C28
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-09-27 Cont ID  
Sent By hmoser Date 2010-09-27 Time 14:55 Rev Time 0.00
Received By hmoser Date 2010-09-27 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-09-13 Cont ID  
Sent By astelly Date 2010-09-13 Time 11:55 Rev Time 0.00
Received By astelly Date 2010-09-13 Time 11:55 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved